~ Limited Liability Company yRKS RKS-plast DATA SHEET EARTHING LINK BOX WITH SVLs KZE-O-3 TU 3599-002-98970470-2010 Moscow 2014 info@rks-plast.ru www.rks-plast.ru a, Limited liability company ORS RKS-plast 1. Application Earthing Link Box with SVLs KZE-O-3 is designed for earthing of 110-220 kV power cables screens. 2. Appearance and Dimensions Figure 1. Appearance and overall dimensions (mm) . 3. Marking and Packaging (On the inner surface of the link box there is a nameplate with manufacturer's name "RKS- plast" and other information. Link boxes are delivered on pallets. The size of the parcel and the number of link boxes per pallet can vary and depend on the size of the consignment and the transportation conditions. Other forms of packaging are subject to agreement with the Customer. info@rks-plast.ru www.rks-plast.ru -, Limited liability company Wee RKS-plast PSS Ente one ne Sa 4. Scope of supply Products can be delivered with or without fasteners. + KZE-03 -1 Cover -1 Surge arrestor- 3 Insulator - 5 ‘Tinned copper lug - 4 ~ Heat-shrinkable tube (1=200 mm.) - 4 + Rubber cord (1=2500 mm.) - 1 ~ Angle, small- 3 - Angle, large -1 = Bolt M6x25 - 24 ~ Bolt M10x20-6 Bolt M10x25 - 1 Bolt M16x25 - 2 - Bolt M16x40-3 - Bolt M16x50-1 - Nut M6—24 - Nut MI6-1 - Washer M6 - 48 - Washer M10 -8 - Washer M16 -7 ~ Signal device Alpha MK2 - 2 pes. + Fasteners (according to terms of delivery) + Product data sheet A manufacturing company has the right to change delivery set of the product without prior notification to Customer. 5. Quality control The products, which is addressed to the customer, passes 100 percent acceptance check and conforms to TU 3599-002-98970470-2010 requirements. ‘When receiving and installing the link boxes, the following incoming checks can be carried out: No. Test Criterion Method 1 [Completeness check [Check of actual quantity against quantity|Comparison Ispecification on shipping documents and| labels 2 [Labeling check [Conformity of the products marking to the|Comparison shipping documents and the labels 6. Storage and operation conditions ‘The manufacturer guarantees the conformity of the products to TU 3599-002-98970470-2010 - requirements subject to the User's adherence to the terms of transportation, storage, installation and operation, 65, Fovided thatthe device is installed correctly, device housing ensures protection degree of IP eS ——— info@rks-plast.ru www.rks-plast.ru a, Limited liability company @RKS RKS-plast cS 7. Warranty The manufacturer guarantees the products compliance with the requirements of this technical specification subject 10 User's adherence to all terms and conditions of transportation, storage, installation and operation Shelf life is 1 year from date of manufacture. ‘Warranty period is 5 years. ‘The warranty period runs from the date of installation of the fasteners. 8. Contact information 111024, Moscow, 2" Kabelnaya st., bldg.2. block 9, office no. 309 Phone: +7(495) 77-75-06 Fax: +7(495) 673-81-86 9, Marks on manufacturer’s acceptance control Compliance with requirements of TU 3599-002-98970470-2010 Control by: Spout 4, Signature: COW, Date: dt. Ot. 2O7G WE 2733 eR info@rks-plast.ru www.rks-plast.ru a, Limited liability company ORKS RKS-plast nee 10, Remarks info@rks-plast.ru www. rks-plast.ru RKS-Plast LLC @ RK: PLAST Instruction Created by: AN Nabirkia ‘Approved: Page Endorsed: AM, Shvabovsky V6 Installation instruction of Earthing Link Box with SVLs type KZE-O-3 eo eae ee Valid for ate oF issue Replaces: Allemployees 101.10 First introduced 1. Introduction 1.1. This instruction applies to installation of Earthing Link Boxes with SVL type KZE-O-3. 1.2. The requirements of this instruction shall be taken into consideration in preparation for link box installation. 2. General 2.1 Prior to installation must be checked: = Box completeness must be checked according to the packing list and the drawing. Expire date of consumable materials must be checked. Visual inspection of the parts and materials. = The installation tools must be checked. 2.2 Link box installation start after: ~ Preparation of place of the final position of link box i finished = Power supply, lighting, etc. are provided. 2.3 _ Installation must be performed according to the requirements of this instruction and applicable national regulations 2.4 Tools, materials and personne!’s clothes used during installation must be clean. 3. Safety Instructions 3.1. Requirements of the national safety regulations must be met during installation. 3.2. Flammable materials shall be kept in a closed steel box positioned at a distance of atleast 2m trom the place of work. 3.3 Work with a gas burner must be performed according to national safety regulations related to the use of LPG. 3.4 All staff must pass safety briefing 3.5 Environmental safety regulations shall be observed during installation: the work area must be fenced; waste must be collected and removed for disposal 4, Earthing Link box Installation 4.1 Determine the position of earthing link box and earthing wires. 4.2 Place the link box in the final position and fix it wth 4 M12 bolts to a pre-prepared construction with the torque of 60 Nm. 4.3 Insert the earthing cables through the inputs of the link box and adjust to the final position, Earthing cable phasing must correspond to the cable line design. Mark the points of cutting and input on earthing cable sheath. Fit the earthing cable and mark the point of cutting on the sheath, 4.4 Cut the earthing cable according to marks, remove insulation on distance for fiting cable lug +5 mm, 4.5 Rasp the end of earthing cable conductors. 46 _ Rasp the cable sheaths with sandpaper to the length of 100 mm from the sheath cut off 4.7 _ Fit and press the lugs on the conductors (start pressing from the conductor cut towards to the sualtion according to the marks on the lug). x 4.8 Clean the lugs and rasped cable sheath with refined gasoline. 49 Fita 100 mm heat-shrinkable tube on link box input and shrink it 4.10 Walt for cooling of heat-shrinkable tube below +80 °C. Do not touch until the heat-shrinkable tubes cool down, 4.11 Insert the earthing cables through the inputs of the link box and bolt it to the insulator having pre- installed a bonding strip, 4.12 Torque of bolt connection of lugs should be 60 Nm. ‘Signature of Origin RKS-~Plast LLC Oo R PLAST Tnstallation instruction of Page Earthing Link Box with SVLs type KZE-0-3 | __7P-18-10-002 | 26 418 Connect the SVL and the bonding strip with a wire, SVL bolt torque shall not exceed: 25 KN for SVL type OPN-PB and 30kN for SVL type OPN- KP/TEL. 4.14. Clean the outer surface of link box inputs and earthing cable sheath with refined gasoline. 4.15. Fita 100 mm heat-shrinkable tube on link box input and shrink it. 4.46 Wait for cooling of heat-shrinkable tube below +30 °C, Do not touch until the heat-shrinkable tubes cool down, 4.17. Clean from dirt and dry inner surface of the link box housing. 4.18 Clean from dirt and dry inner surface of the link box cover and outer surface of housing in gasket area with refined gasoline. 4.49 Place the link box cover, handles shall be outside of the housing. Adjust the holes in cover with the holes in the flange of the housing, Insert M6 bolts in the holes and fix them with nuts. Washers under bolt heads and nuts should be used. Tighten the bolts with torquo 15-20 Nm. 4.20 After installation of the lid on the housing and bolt tightening. insert Signaling device Alpha MK2 included into scope of supply of box into unplugged holes on the lid to pravent unauthorized access to the box and tighten until stop like plastic collar. Two signaling devices Alpha M2 located cornerwise against each other should be installed per one box. 421. Important! Bolts should be installed in all holes of the cover — totally 24 pieces. If the set of fastoners is incomplete the sealing between the cover and the housing flange will not guaranteed. Torque of bolts connection should be 15-20 Nm. 4.22. Prior to operation ofthe link box make sure the housing is earthed with not damage earthing cable. Signature of Originator RKS-Plast LLC Installation instruction of Earthing Link Box with SVLs type KZE-0-3 | _TD-18-10-002 316 Appendix 1 Part list of earthing link box with SVL type KZE-0-3 tem Designation Description ‘Quantity, |] No. pes. | 1 Housing Stainless steel 7 ] 2 Cover Stainless steel 1 3 _| Surge arrester OPNp-6/7.6 3 ‘4 | insulator 108K 10-8 5 5 | Gasket On box shell, | Heat-shrinkable tbe L=200 mm. a 7__| Bonding strip Copper, S=400 mn? 3 8 | Bonding strip Copper, S=400 mm? 1 ‘9 | Cable tug GPH 120-400x16 KU-EV Lo 10 Bok M25 2 414_| Bolt M10x20 8 12 | Bolt M10x25 1 13 | Bolt M16x25_ 2 14 | Bolt M16x40_ 2 15 _| Bolt M16x50_ 4 16 [Nuts 24 7 Nuthte 1 418_| Washer M6 48 49 | Washer M10 8 20 | Washer Mi6 7 Signature of Originator RKS-Plast LLC Installation instruction of k Box with SVLs type KZE-O-3 Earthing. ‘ED-18-10-002 | re Installation tools for KZE-0-3 Tem Designation ‘Quantity, pes Zig-zag ruler, 2m “Tape measure, 10m Side calliper Wrench 8x10 mm Wrench 10x13 mm Wrench 17x19 mm. Wrench 22x24 mm. Ratchet wrench 12" Ratchet box wrench, "10-100 Nm Box wrench head, 4" 6 mm ‘Box wrench head, 4°10 mm. Box wrench head, "17 mm. ‘Box wrench head, 4°24 mm. Universal pliers, 200 mm Alligator wrench, 20-63 mm. Cable knife 214" Fiat rasp for metal with handle, 300 mm Hacksaw, 300 mm Hacksaw blade, 300 mm Marker 1-2 mm, white Gas burner kit, Propane/butane mix gas-cylinder, 601 Hydraulic foot pump PO 7000 Hydraulic compress head AH 450 Hexagonal compress mould for RH 450, type 38 CU-450 ‘A tool for cable sheath and insulation removing ‘A too! for peeling of semiconducting layer and insulation ‘Carbon dioxide fire extinguisher First aid kit ‘Asbestos cloth 1000x1000 falatets| ele abe hse shelalale|abla atop ott) Signature of Originator: ‘Consumable materials required for installation of one KZE-0-3, iter Designation ‘Quantity per box No. + | Refined gasoline. SL 2_| Cleaning rags (cotton) kg. 3_| Sandpaper (arade 80) 0,05 m=, ‘4 | Gloves “Hycron”™ 2 pairs RKS-Plast LLC © PLAST Installation instruction of Page Earthing Link Box with SVLs type KZE-0-3 | _TD-18-10-002 se Appendix 3 Signature of Originator RKS-Plast LLC Page 616 Installation instruction of Earthing Link Box with SVLs type KZE-0-3 | _12-18-10-002 Appendix 4 Dimensions of earthing link box with SVL type KZE-O-3 ‘Signature of Oniginator

You might also like