ENGLISH
10/97
More than 100 measures
Volt
Amp.
PF.
cosO
kw
kVA
kVAr
Hz
+kWh
+ kvarh
Thd
Harm
CF.
Dc
NANOVIP PLUS
PORTABLE DIGITAL POWER ANALYZERNANOVIP PLUS
SUPERB PERFORMANCE IN A COMPACT PACKAGE
> POWER &
iy vi Liked For single-phase and balanced three-phase systems
iy ANALYZER The NANOVIP PLUS is a hand-held portable instrument capable of
measuring over 100 fundamental parameters for display via a large high-
eeummmmmiaeemeiin| contrast LCD. The product of many years R & D by the ELCONTROL
ENERGY laboratories, it makes serious power quality analysis more
affordable than ever before.
Volt, Amps. Watts, VAr, VA,W, Hz posineg kWh (import/export), posineg kvarh
(inductive/capacitive)
All measurements are true RMS. Accuracy is 1% or better including clamp error
between 7 W and 150 KW (200A clamp) or 35 W to 750 kW (10008 clamp),
DC measurement capability (requires Hall effect clamp for curent,
‘Automatic recagrition of clamp type in use (200A or 10008) - removes,
the need for addtional set-up by the user.
= PEAK feature captures max current/power values or min voltage
value (user selectable)
¥M function provides data hold and allows realtime comparison of new
readings against stored values.
“HARMONICS MEASUREMENTS
+ Measurement of harmonic values of V & | (1 st 10 24th) expressed as absolute and
percentage values, plus their DC component and displacement values.
‘Total Harmonic Distortion (THD) of V & | with reference to the fundamental or total
AMS value.
“= Crest factor for V & | expressed as absolute and percentage values
“DC ripple component for V & | as RMS percentage values.
V8 I ripple as RMS value.
‘SETUP
+ Auto set-up for standard current clamps
+ Manual override facility for non-standard ratios fully programmable for any CT.
+ Standard or co-generation energy motoring
+ 50/60Hz fundamental selection for harmonies analysis
+ DC selection
+ S232 parameter set-up for serial communication to PC.
RESET
«+ Reset of energy metersPower & harmonic analyzer
NANOLINK
NANOLINK is a DOS utiy for realtime transmission of the values measured by
the NANOVIP PLUS to PC via a standard RS232 port.
Basic features include:
* Display all measurements and instrument status
‘Control survey startstop times
+ Survey sampling rato
+ Set-Up of on-board clock
* Data storage to standard text fle
uns in Windows™ in background or foreground,
‘CONNECTION DIAGRAMS
Ona single-phase system Ona three-phase system Used as a clamp moter For DC measurements
uy > 1 ———
rey
N ls
*N.B. The clamp motor isnot Included. The Eleontro Hall Effect clamp meter must bu used. (Cod.4AABW)
NANOVIP Power analyzer
7 MEASUREMENT FUNCTIONS iN THE PALM OF YOUR HAND
+= Volt (rms), Amp (ms), P-F. cos, W, var, VA, Hz
+ PEAK function for storing the measurements in
correspondence to the V, A, W peaks (selectable)
* MEM functions for measurements of deviations of
V, A, W, cos with respect to the recorded values
+ Measurements from 7W to 150kW (7S0kW with 1000
clamp meter)
+ Measurements as true RMS value
+ Automatic voltage and current scale change
+ AC and DC measurements (with DC clamp meters)
+ High accuracy
Very user-friendlyNANOVIP Power analyzer
GENERAL TECHNICAL DATA
+ Inputs:
Voltmeter: (L1-N) max 600 Vrms up to 600 Hz.
‘Ammeter: 1 Volt up to 600 Hz
‘+ Number of scal
3 voltage scales: 3 current scales.
+ Automatic scale change:
‘Scale change response time: 1 sec. max
Passage to the scale above takes place at 105% of the scale in
use
Passage to the scale below takes place at 20% of the scale in
use
Instrument dimensions: 80x175x32,5 mm (without cover).
Instrument weight: 500 9.
Kit weight: 1,1Kg. (without instrument
SERVICE AND TESTING CONDITIONS
+ Ambient operating conditions:
‘Amiiont temperature range: from -10°C to 450°C.
Relative humidity range (R.H.): from 20% to 80%,
* Storage temperature: trom -20°C to +60°C.
* Condensation: not permitted,
+ Reference standards: IEC 348, VDE 411 class 2, for operating
voltages < 600 VAC rms, IEC 1010 600 V CAT tl,
EMC: EN50081-1, EN 50082-2, ENS5022
POWER SUPPLY
4 18V batteries (size AA).
MEASUREMENT OF THE PRIMARY PARAMETERS
+ Measuring method:
with fixed sampling and analagicidigital conversion
+ Sampling frequency: 2.50 kHz,
+ Number of samples per phase: 250 (100 msec)
+ Measuring frequency: ~0,5 sec.
+ Zero self-correction: every minuto.
MEASURING ACCURACY FOR PRIMARY
PARAMETERS
+ Measuring error in ambient from 18°C to 25°C (after 10°
warm-up): (see table)
+ Measuring error outside this temperature range:
FS for every °C outside the range.
*Voltage measurement accuracy and sensitivity
Direct input with max voltage = 600 Vins at Full Scale.
Input voltage crest factor > 1,6
Input impedance > 4Mo.
“The accuracy does not consider the clamp meter error.
‘Voltage and curront measurement accuracy in relation to
frequency: for signai frequencies in the range 30-90 Hz no error
‘apart from those indicated in the previous tables.
+ Measuring precision of secondary parameters:
Measurements of active power, cos,
active energy: IEC 1036 class 1
‘+ Measurements of the other secondary parameters: the error
Is expressed by the formula which defines the parameter, in
relation to V and I
02%
"WARNING - E\GONTROL ENEAGY dcinas a abit 1 any same ofa50 Or ropa CREE by ane or ssc usa of He pom (Site!
6 ELCOMTROL ence...
Nominal sonsiivty Full Saale “TAOS. 1 1006S.
range NANOVIP
s7Vims mV aT OSS, + 0.5% Rdg
Wavims iim 174V O.S%FS. + 0.3% Rdg
7soVes —480mV 750 OSS. + 03% Rdg
‘Sensitivity and precision in current measurements:
Direct input with max. voltage -1 Vrms at Full Scale
Crets Factor of input current 23
ftom 20% FS. 8 100%FS.
“Binge! Sensitvty Full Scale (*) ae
SomV 32nV SOV OSS. + 0.5% Rdg
za2nV MOKY aa mY KFS. + 0.8% Rg
vo eow v O3%FS. + 03% Rg
() Corresponding Full Scales at 10-46,4 -200 Amps., with
slandard 2004/1
50 - 282 - 1000 Amp., with optional 1000A/1\’ clamp meter
(Error= Sum of the errors of the Nanovip and tne clamp meter)
DIMENSIONS (in mm)
175.
+9254
OE
Completa wit
1 NANOVIP kit case
+ NANOVIP PLUSINANOVIP.
1 Set votimeter cables
1 clamp moter 2008/1
‘Vrms AC with wires
1 Insttuction booklet
1 Guarantee ceriicate
1 NANOLINK Software
(only for NANOVIP PLUS)
SPARE PARTS
ZETIA temo moter 200avac
COUCMELAAERTIED | Set voitage cables ior NANOVIP
POETS * vANovir xir caso
Via Vizzano 44 - 40044 Pontecchio Marconi (Bologna) ltaly
Tel. +39 51 6782006 - Fax +39 51 845544
http:/www.elcontrok