SETTING LIGHT
DISPLAYED ONLY WITH OPTIONS > ANALOG OUTPUT

TYP. A. O . 0-20mA Er.4- T 4-20 T Er.4-20 ••• 0-10 V +-10 V

 

TYP. A. O . Setting the type of analog


  output

Menu Range Description


0-20mA 0…20 mA
Er.4- T 4…20 mA with error message indication and broken loop indication (<3,6 mA)
4-20 T 4…20 mA with broken loop indication (<3,6 mA)
TYP. A.O.

Er.4-20 4…20 mA with indication of error statement (<3,6 mA)


4-20mA 4…20 mA
0-5mA 0…5 mA
0-2 V 0…2 V
0-5 V 0…5 V
0-10 V 0…10 V
+-10 V ±10 V

DEF = 4…20 mA

Type of analog output - 0...10 V > TYP. A.O. = 0-10 V Example

4-20mA 0-5mA 0-2 V 0-5 V 0-10 V MIN A. O .

MIN A. O . 0
Assigning the display
value to the beginning

of the AO range

MIN A. O . Assigning the display value

range
 
to the beginning of the AO DEF = 0

- range of the setting: -99999…999999

Display value for the beginning of the AO range > MIN A.O. = 0 Example

0 MAX A. O .

!
Items for “Limits” and “Analog output”
are accessible only if incorporated in the
instrument.

36 | INSTRUCTIONS FOR USE OM 402UNI