Inverter Module No. of CB CB Input No. of Rack Type Nos. of DC Overloading
No. Wp Rack modules Capacity
16 14 224 2X30 13440 4.4352
1 330 1.502
1 13 13 2X30 780 0.2574
13 14 182 2X30 10920 3.6582
2 335 1.505
4 13 52 2X30 3120 1.0452
13 14 182 2X30 10920 3.6582
3 335 1.505
4 13 52 2X30 3120 1.0452
335 14 14 196 2X30 11760 3.9396
4 335 1 15 15 2X30 900 0.3015 1.459
330 1 16 16 2X30 960 0.3168
10 14 140 2X28 7840 3.2144
5 410 1.506
5 13 65 2X28 3640 1.4924
10 14 140 2X28 7840 3.2144
6 410 1.506
5 13 65 2X28 3640 1.4924
10 14 140 2X28 7840 3.2144
7 410 1.506
5 13 65 2X28 3640 1.4924
10 14 140 2X28 7840 3.2144
8 410 1.506
5 13 65 2X28 3640 1.4924

1752 37.4845 1.499


Poly 2X30 932 7 or 7.5
Mono 2X28 820 8
3.653
980 32.66666666667
32 960

Wp Module used Avialble at site Spare


330 15180 15200 20

335 40740 40783 43

410 45920 - -
if 2X28 for mono

Inverter No. Module No. of CB CB Input No. of Nos. of DC Overloading


Wp Rack modules Capacity
16 14 224 13440 4.4352
1 330 1.502
1 13 13 780 0.2574
13 14 182 10920 3.6582
2 335 1.505
4 13 52 3120 1.0452
13 14 182 10920 3.6582
3 335 1.505
4 13 52 3120 1.0452
335 15 14 210 12600 4.221
4 1.468
410 1 16 16 896 0.36736
10 14 140 7840 3.2144
5 410 1.506
5 13 65 3640 1.4924
10 14 140 7840 3.2144
6 410 1.506
5 13 65 3640 1.4924
10 14 140 7840 3.2144
7 410 1.506
5 13 65 3640 1.4924
10 14 140 7840 3.2144
8 410 1.506
5 13 65 3640 1.4924

1751 37.51496 1.501


Poly 2X30 915
Mono 2X28 836

DC Fuse rating in
inverter 400 A

Nos. of DC Input 22
Derating 1.5

Available Rating 266.6667 A


Allowable Isc of
total strings 266.6667 A

Considaration
Risen 410Wp

Isc of module at
STC 10.7

Nos. of modules
per string 28
String Isc 10.7
Nos. of strings
required at each
CB 24.92212
String per CB 24
Total Modules Available Remaining Modules
used in inverter Modules
14220 15200 980

14040 40783 26743

14040 26743 12703


12600 12703 103