CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Suspended Ceiling Seismic Loads Based on ASCE 7-16 & ASCE 7-10
T
Wp = 3.5 kips, (15.6 kN)
D
h= 60 ft, (18.29 m), average roof height (ASCE 7-16/10 13.3)
H= 48 ft, (14.63 m), this floor top level height
D= 6 ft, (1.83 m) Wp
T= 8 in, (203 mm), from floor top to bottom anchorage point
FH
SEISMIC COEFFICIENTS
SDS =
FV
1 (ASCE 7-16/10 11.4)
Ip = 1.5 (ASCE 7-16/10 13.1.3)
ap = 1 (ASCE 7-16/10 Table 13.5-1 or Table 13.6-1)
Rp = 1.5 ( ASCE 7-16/10: 2.5 for ceilings on Table 13.5-1, 1.5 for lighting fixtures on Table 13.6-1)
FH = 2.40 Wp (SD) = 1.71 Wp (ASD) = 6.00 kips, (26.7 kN), ASD level horizontal load
FV = 1.90 Wp (SD) = 1.36 Wp (ASD) = 4.75 kips, (21.1 kN), ASD level downward load
ANALYSIS
FV = (1 + KV ) Wp