You are on page 1of 1

Example,

Trihal standard losses type transformer, with electrical data as given below:

1) Calculation of R%:

R% = 100 x [(Full load loss (W)-no load loss (W))/(transformer rated power (kVA)x1000)] 

= 100 x [(12300 (W)-2800 (W))/(1600 (kVA)x1000)] 

= 0.594 %

2) Then, using the impedance relation; Z = √ (R² + X²), we can calculate X% to be:

X% = √ (Z%² - R%²) = √ (6² - 0.594²)

= 5.97 %,

Hence X/R = X%/R% = 5.97 / 0.594 = 10.05

You might also like