of2
1. The reply of query no. 8 under volume 2. Clarification-1 is replaced with the following
texts
the type tests for insulator seis are not available as offered combination of insulator
& fitting manufacturer with proposed design. the tests shall be performed for all the
sulator sets of the 4QDKV fine (except low duty sets) and only suspension set of
I32kV line under this project during execution stage in presence of Employer's
Engineers.”
2. Section 11. ACCC Conductors,
Page no, 11-16 is replaced with the revised page no, 11-16 (Rev, 1). [Attachment-2]
Clause [4 D.C, Resistance Test on Stranded Conductor, Page 11-24
The texts “The value obtained shall be corrected to the value at 200C as per relevant
HEC /BS/equivalent standard. The resistance corrected at 200C shall conform to the
requirements indicated in the STP.” are replaced with the following texts:
The value obtained shall be corrected 10 the value at 20 deg C as per relevant
IECHBS/equivalent standard. The resistance corrected at 20 deg C shall conform to
the requirements indicated in the STP.”
Clause [8 Radial Crush Test, Page 11-25
The texts “AHI the strands shall be subsequently disassembled and tensile tested. All
the strands shall exhibit full strength retention” are replaced with the following texts
All the core straudy/core shall be subsequently disassembled and tensile tested, All
the core strands/core shall exhibit full strength retention
Clause 1.15 Coefficient of linear expansion for composite core’ core wires. Page 11
26
The texts ~The temperature and elongation on a sample shall be continuously
‘measured and recorded at interval of approximately 15 degree C from 15 degree C to
‘maximum continuous operating temperature by changing the temperature by suitable
means.” are replaced with the following texts:
The temperature and elongation on a sample shall be continuously measured and
recorded at interval of approximately 1S degree C from laboratory ambient
temperature to maximum continuous operating temperature by changing. the
temperature by suitable means,
Clause 1.35 Galvanic Protection Barrier Layer Thickness, Page 11-30
The tests “The minimum thickness shall be at least 0.5 mm” are replace
following texts
Page 2 oS
we