You are on page 1of 4

CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0338

DYNAMIC TAP CHANGER TESTING, REACTORS AND REACTANCE


Gunnar ANDERSSON Raka LEVI Edis OSMANBASIC
ABB Components – Sweden AMforum – USA DV Power - Sweden
gunnar.l.andersson@se.abb.com Raka@Amforum.org Edis@DV-Power.com

ABSTRACT TESTING VARIABLE SHUNT REACTORS


Dynamic resistance measurement (DRM), a new diagnostic Since no experience of such measurements existed before
technique that is getting a lot of attention recently by its our measurements, only expectations existed. As a
power in detecting OLTC problems is discussed in this recommended procedure, the measuring current should be
paper as applied to variable shunt reactors (VSR). Specific kept higher than the magnetization current and preferably,
another winding should be short circuited.
features in the current traces are explained. In addition, In a reactor, the magnetization current is equal to the load
discussion of principles and DRM features, and defect cases current and thus the measuring current can’t exceed it. The
are presented for tap changers of a reactance type tested primary reason is that it would require a huge instrument
using DRM methodology. since the currents often are in the range of 100-300 A.
Running full DC-current through a winding is normally not
INTRODUCTION allowed of thermal reasons either. Thus, the impedance can
not be reduced by keeping the measuring current higher
A shunt reactor consists of one winding only and is than the peak of the magnetization current.
connected between a high voltage line and ground. It can be The second thing to reduce impedance, the short circuit of
three phase or single phase. It is made to have a certain windings, is normally not possible either since there is no
inductance. Its task is normally to compensate for high other winding. The expected problem was thus, that the
capacitances to ground. It can be seen as a no-loaded impedance could be so high that the evaluation of the result
transformer with a high magnetization current. By having could be difficult.
the reactor equipped with a regulating winding and an on-
load tap-changer (OLTC), the reactance can be varied in
small steps and with a considerable range. That way, the DRM on different OLTC types
reactance can be smoothly adapted to the variations in load
and the voltage can be adjusted more exactly.
Before starting the measurements it is worth considering the
Variable Shunt Reactors (VSR) are seeing an increasing use
different response different OLTC types give to the
in the networks to stabilize line voltages. So far, DRM has
only been used on transformers. A pennant cycle OLTCs, measurement. The DRM is measuring the current through
used for these VSRs work on the principle used by most the winding. The current that changes is thus only what
corresponds to the load current in real service. The
modern vacuum type OLTCs.
circulating current that is caused by the step voltage in real
The Dynamic Resistance Measurement (DRM) service is not seen.
Without going to much into details, the so called flag cycle
Winding resistance measurements is a well known method types which include most of the non-vacuum types of
in the business. It is a measurement done with a low DC OLTC, will give the complete operating cycle to be seen on
current through a winding to make sure losses are as the DRM.
expected on a new transformer, and to see that the values However, all the pennant cycle types, a principle used by
have not changed due to defects when measuring on units in most of the vacuum type OLTCs outside USA, will only
service. This measurement could be called static resistance show the main contact operations and nothing from the
measurement. The dynamic measurement means measuring transition contacts since these are only switching circulating
the same but in addition it also records the current during current.
tap change operation from one position to the other through In addition, the vacuum types have auxiliary contacts that
the whole range of positions. are not seen either. The following measurement is done on a
By doing that, the voltage drop when the transition resistors VSR with a vacuum type OLTC working according to the
are connected can be seen. The operation time for the pennant cycle.
OLTC is also possible to measure.
The measurement should be done with a DC current The ABB OLTC model VUCG operating cycle
exceeding the knee point of the magnetization current to
keep the core saturated during the complete measurement in
order to reduce the impedance as much as possible. If The VUCG OLTC operates according to the asymmetrical
possible, one of the windings not measured should be short pennant cycle but with the exception that it operates with
circuited in order to reduce the impedance even further. the main contacts first in both directions. That is achieved
The impedance causes slow reactions in current change by a mechanical rectifier in the mechanism and gives
during measurement and high impedances make the electrical advantages such as lower breaking stresses and
interpretation of the resulting curves difficult and endanger longer contact life.
the value of the measurement.

CIRED2013 Session 1 Paper No 0338


CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0338

Measurement 1 2,7/11,2=0,24 seconds that is 6,6 times faster than with the
arc only. That explains the faster slope in the second part of
The actual VSR tested is a 127-209 MVAr at 420 kV with
the curve.
transition resistance: 11,2 ohms.
The third part, which is within the rightmost circle in the
Since we couldn’t lay back on any previous experiences, we
curve, is when the next tap is connected. That is connected
started with a measurement from position 1 to position 2
by the main contact without any resistance more than that of
which connects more turns. The DRM trace looked like the
the test loop itself. The inductance increases by 4% and the
graph on figure 1. A surprisingly fast response when the
current decreases. The time constant is small since the
resistors are connected, and slow when they are
inductance in one loop is small and the transition resistance
disconnected.
is high.
After that the current increases again but now slowly since
The picture on figure 2. is enlarged, shows the connection
the resistance now decreases by a factor of appr. 10 and the
of the resistors only. First there is a slow decrease in current
time constant increases correspondingly. It is however seen
in the picture remaining for appr. 6-7 ms. This is the arcing
that the expectation of a slow curve is not correct. At least,
time of the main vacuum interrupter. The arc has a voltage
not for the decrease in current. As we saw above, the
drop of about 17 V corresponding to a resistance of
operation time for the main vacuum interrupter was clearly
17V/10A=1,7 Ω (Winding resistance neglected). The time
seen and since this is a pennant cycle operation, only the
constant (L/R) is thus 2,7/1,7=1,6 seconds.
main vacuum interrupter operation can be seen.
The second part, between this first time and the larger slope
within the circle, remains for about 37 ms. That is the time Measurement 2
when the transition resistors are connected. This time added
to the arcing time is the true mechanical time when the main This measurement is from position 4 to 3, which is in
vacuum interrupter is open and is here about opposite direction compared to the Measurement 1 and now
turns are disconnected, see figure 3.
(7+37=) 44 ms which is as expected.

Figure 3. DRM of a tap change from position 4 to 3

Figure 1. Transition from position 1 to position 2 The picture on figure 4 is a magnified portion of the figure 3
and shows the connection of the resistors only. First, as
before, there is a slow decrease in current above the red line
in the picture remaining for appr. 6-7 ms. This is the arcing
time of the main vacuum interrupter. The arc has a voltage
drop of about 17 V corresponding to a resistance of
17V/10A=1,7 Ω (Winding resistance neglected). The time
constant (L/R) is thus 2,7/1,7=1,6 seconds.
The second part, between this first time and the larger slope
within the circle, remains for about 37 ms. That is the time
when the transition resistors are connected. That time
added with the arcing time is the true mechanical time when
the main vacuum interrupter is open and is here about
(7+37=) 44 ms which is same as in the Measurement 1.
The time constant when the resistors are connected is:
2,7/11,2=0,24 seconds that is 6,6 times faster than with the
arc only. That explains the faster slope in the second part of
the curve.
Figure 2. Magnified transition from position 1 to position 2 The third part, the one within the rightmost circle in the
curve, is when the next tap is connected. That is connected
The time constant when the resistors are connected is: by the main contact without any resistance more than that

CIRED2013 Session 1 Paper No 0338


CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0338

of the test loop itself. The inductance now decreases by of a very important network component, such as On Load
appr. 4% and the current increases. Tap Changer, and it is used as a prioritization tool for
The time constant is small since the inductance in one loop maintenance, upgrade, or its overhaul.
is small and the transition resistance is high.
After that the current increases again but now slowly since Testing reactance tap changers
the resistance now decreases by a factor of appr. 10 and the
time constant increases correspondingly. Over the last 18 years, the DRM method was used [1,2,3]
It is again seen that the expectation of a slow curve is not exclusively on resistance tap changers. Our experience with
correct. At least not for the decrease in current. As we saw testing reactance tap changers is short. The method was
above, the operation time for the main vacuum interrupter introduced in the USA only in the last couple of years [4].
was clearly seen and since this is a pennant cycle operation, The DRM current trace on the graph fig. 6 shows key points
only the main vacuum interrupter operation can be seen. of the tap changer operation, identified by the sudden
current change.

Figure 4. Magnified transition from position 4 to 3


Figure 6 Reactance DRM graph main features
Three phase test
A three phase graph of the tap changer transition on this
Case 1
particular tap changer operating on a VSR is given in the One case of a defective reversal switch was detected in a
figure 5. It was obtained with the new generation of the test 67kV substation in California that indicated overheating
instruments recording three phase DRM simultaneously. condition and contact problem based on DGA. The graph of
the DRM on phase 2 of this transformer showed a big
difference in the performance of the tap changer through
position 16Low to N, while from N (neutral) to 16Raise the
trace followed expected pattern for a normally operating
tap changer. In order to confirm the findings, a test was
performed in the opposite direction, where the same side
with the problem before indicated a problem again. This
conclusion was enough for the crew to get into the unit and
find tap changer in bad condition. Figure 7 shows the four
graphs obtained in two directions of the tap changer motion
for phase 2, as well as phases 1 and 3.
Figure 5 Three phase transitions

REACTANCE TAP CHANGERS


Almost all of the European tap changers are of the
resistance type. In contrast to this, USA transformers use
reactance tap changers for voltage regulation. A reactance
type tap changer is a special design where circulating
current is limited by application of preventive auto-
transformer (reactor), in contrast to the resistance tap
changers where this task is given to plain resistors. Figure 7 Reversal switch problem seen by DRM
The DRM test methodology is an ideal tool for diagnostics

CIRED2013 Session 1 Paper No 0338


CIRED 22nd International Conference on Electricity Distribution Stockholm, 10-13 June 2013

Paper 0338

Case 2 [2] H.F.A. Verhaart, 1995, “A diagnostic to determine the


A case of a heavy coking on the lower stationary transfer condition of the contacts of the tap changer in a power
switch of the phase X1 was detected by increased DGA transformer”, CIRED, Brussels, Belgium, paper 1.13.
results. The exact position of the troublesome switch was
indicated by carefully analyzing the DRM graphs of the all [3] Luis Miguel Perea, Angel Ramos Gómez, José Luis
three phases. The overlay of the phase X1 and X3 on the Lozano, 2000, “Dynamic resistance measurements in
graph of figure 8 below shows the deviation of the current LTC”, Proceedings of the EuroDoble Colloquium.
line (in the red circle) pin-pointing the defect to the
particular phase and operation of particular transfer switch. [4] R.Levi, B.Milovic, 2011, “OLTC dynamic testing”,
Proceedings TechCon USA, San Francisco

[5] Jur Erbrink, Doctoral thesis: “OLTC Diagnosis on High


Voltage Power Transformers using Dynamic
Resistance Measurements”, Technische Universiteit
Delft, 28. March 2011.

[6] “Report of the second Workshop on DRM”, 2012,


organized by AMforum, Stockholm, February,

Figure 8. DRM trace indicating coking on transfer switch

CONCLUSION
The dynamic resistance measurement on variable shunt
reactors can be performed without any problems. The
response when changing resistances will be fast enough to
clearly show the ripple as well as transition times.
The result for an OLTC operating according to the flag
cycle can be assumed to be fairly the same. Although the
measurements in this paper were made on a large shunt
reactor, it can be stated that the same conditions will apply
even to smaller shunt reactors.
In view of the complexity of analysis [5] for extreme
number of types and manufacturers of existing tap changers,
a working group was formed by the AMforum association to
collaborate and exchange experience and data in order to
better understand, and if possible standardize test
procedure. Certain conclusions and recommendations of the
working group were implemented here [6].

REFERENCES

[1] H.F.A.Verhaart, KEMA, 1994, “Tussenrapport over


faaloorzaken van distributie- en koppeltransformatoren
op basis van de onvoorziene nietbeschikbaarheid”,
rapport 43613-T&D 94-102278.

CIRED2013 Session 1 Paper No 0338

You might also like