Publication 511-13
Certified Ratings Program
Product Rating Manual for
Air Control Devices
Authority AMCA International Publication 511-10 was approved by the membership of the Air Movement and Control
Association International on October 14, 2010.
All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections
107 and 108 of the United States Copyright Act without the permission of the copyright owner is unlawful.
Requests for permission or further information should be addressed to the executive director, Air Movement
and Control Association International Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893
U.S.A.
Objections Air Movement and Control Association International Inc. will consider and decide all written complaints
regarding its standards, certification programs or interpretations thereof. For information on procedures for
submitting and handling complaints, write to:
Disclaimer AMCA uses its best efforts to produce publications for the benefit of the industry and the public in light
of available information and accepted industry practices. However, AMCA does not guarantee, certify or
assure the safety or performance of any products, components or systems tested, designed, installed or
operated in accordance with AMCA publications or that any tests conducted under its publications will be
non-hazardous or free from risk.
Review Committee
Related ANSI/AMCA Standard 500-D Laboratory Methods for Testing Dampers for Rating
Standards
ANSI/AMCA Standard 500-L Laboratory Methods for Testing Louvers for Rating
ANSI/AMCA Standard 540 Test Method for Louvers Impacted by Wind Borne Debris
ANSI/AMCA Standard 550 Test Method for High Velocity Wind Driven Rain Resistant Louvers
Contents
1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.1 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
3.2 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
7.2 Tolerances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Annex A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Annex B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Measurements (Normative) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Annex C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
AMCA 511-13 | 1
3.1.7 Backdraft damper ing showing the height and setback dimensions of the
A backdraft damper is a damper which, when mounted drain pan
in a duct or opening, permits airflow in one direction and • For gravity ventilators, one additional drawing as shown
prevents airflow in the opposite direction. in Section 19
2 | AMCA 511-13
6. General Guidelines for Air Control Products The licensee shall maintain, or cause to be maintained, such
manufacturing control of licensed devices manufactured by
6.1 Manufacturer’s responsibility or for the licensee that, when tested in accordance with the
required test standard, the tolerances in Section 7.2 shall be
It is incumbent on manufacturers to develop catalog perfor- maintained.
mance ratings of the licensed products so that the product
provided to their customers performs within the tolerances 7.2 Tolerances
allowed by the Certified Ratings Program.
7.2.1 Air performance
This section provides general guidelines on the process of The airflow at any rated pressure differential shall not be
developing air performance ratings from tests, and Sections less than 90.0% of the rated airflow.
8 through 21 define specific requirements for each type of
product. 7.2.2 Wind-driven rain performance
For the cataloged class, the effectiveness shall not be lower
6.2 AMCA staff responsibility than the following:
AMCA staff is also responsible for verifying that the catalog Discharge loss coefficient shall not be less than 90% of the
published by the licensee conforms to the requirements of minimum value in its class.
the program.
7.2.3 Water penetration performance
6.3 Rating development The airflow at the point of the beginning of water penetration
shall not be less than 90% of the rated airflow.
The performance ratings of an air control product or a series
7.2.4 Air leakage performance for adjustable louvers
of similar products are developed from tests conducted in
The air leakage at any rated DPs shall not be more than
accordance with ANSI/AMCA 500-D, ANSI/AMCA 500-L,
110% of the rated air leakage.
ASTM E90, ANSI/ASHRAE/SMACNA 126, or EN 1751:1998.
7.2.5 Air leakage performance for dampers
6.4 Aerodynamically similar products
The airflow at any DPs shall be less than or equal to the
corresponding air leakage requirement for the rated class.
Products which are aerodynamically similar to a certified
product may be certified without additional testing (see 7.2.6 Air leakage performance for spiral duct
Section 3.1.5). The airflow at the rated pressure shall be less than or equal
to the air leakage rating plus one cfm per 100 ft2 of duct wall
6.5 Nameplated products surface area.
AMCA 511-13 | 3
7.3 Required tests
4 | AMCA 511-13
8. Louver | Air Performance Rating Requirements (page 1 of 2)
8.1 Testing requirements 8.2 Calculated performance 8.3 Published ratings
AMCA 511-13 | 5
8. Louver | Air Performance Rating Requirements (page 2 of 2)
the mode tested (intake or exhaust),
or test data shall be provided to AMCA
that indicates that the data published
is worst case.
6 | AMCA 511-13
9. Louver | Wind-Driven Rain Rating Requirements
9.1 Testing requirements 9.2 Calculated performance 9.3 Published ratings
9.1.1 Wind-driven rain test 9.2.1 Penetration class 9.3.1 Wind-driven rain performance
All testing shall be performed in The penetration class shall be deter- Published ratings of wind-driven
accordance with ANSI/AMCA 500-L, mined by the effectiveness in accor- rain performance of louvers shall be
Figure 5.11. dance with ANSI/AMCA 500-L (see a statement of their ability to reject
Table 2). simulated rain.
9.1.2 Test sample
Wind-driven rain performance shall 9.2.2 Discharge loss coefficient Published ratings shall include the
be based on tests conducted on a The discharge loss coefficient, given following:
louver that has one of the following: in Table 1, shall be determined in
accordance with ANSI/AMCA 500-L. • Wind velocity
• A core area of 1000 mm x 1000 • Rainfall rate
mm (39.375 in. x 39.375 in.) • Core velocity
with a tolerance of ±3 mm (±1/8 • Effectiveness
in.) with an extended frame • Penetration class (see Table 2)
• Discharge loss coefficient class
• Extended frame outside dimen- (see Table 1)
sions of 1213 mm x 1213 mm
(47.75 in. x 47.75 in.) with a toler- 9.3.2 Free area
ance of +5, -0 mm (+0.19, -0 in.) Published ratings shall include a table
of louver free area for the product line.
• Outside dimensions of 1213 mm The maximum increment between
x 1213 mm (47.75 in. x 47.75 sizes shall be 305 mm (12 in).
in.) with a tolerance of +5, -0 mm
(+0.19, -0 in.) 9.3.3 Drain pan statement
If an optional drain pan is used when
testing a louver, see Section 5.3.
Table 1
Discharge Loss Coefficient Class
Class Discharge Loss Coefficient
1 0.4 and above
2 0.3 to 0.399
3 0.2 to 0.299
4 0.199 and below
Note: Table 1 also applies to entry loss coefficient
Table 2
Penetration Class (for Wind-Driven Rain)
Class Effectiveness Maximum allowed penetration, l/hr/m2 (SI) Maximum allowed penetration, oz/hr/ft2 (I-P)
75 mm/hr rainfall 202.4 mm/hr rainfall 3 in./hr rainfall 8 in./hr rainfall
13 m/s wind velocity 22 m/s wind velocity 29 mph wind velocity 50 mph wind velocity
A 99.9% to 99% 0.75 4.0 2.36 12.6
B 98.9% to 95% 3.75 20.0 11.8 67.8
C 94.9% to 80% 15.0 80.0 47.1 251.0
D Below 80% Greater than 15.0 Greater than 80.0 Greater than 47.1 Greater than 251.0
AMCA 511-13 | 7
10. Louver | Water Penetration Rating Requirements (page 1 of 2)
10.1 Testing requirements 10.2 Calculated performance
10.1.1 Water penetration test 10.2.1 Proportionality 10.2.3 Beginning point of water
All louvers tested for water penetra- Tests may be run on a single size for penetration
tion performance shall be tested in a given design type. The beginning The beginning point of water penetra-
accordance with ANSI/AMCA 500-L, point of water penetration for all sizes tion shall be the free area velocity
Figure 5.6. of that design shall be considered to at the intersection of a simple linear
be at the same free area velocity as regression of test data and the line of
10.1.2 Test sample the tested unit (see Annex C). 3 mL (0.01 oz) of water per m2 (ft2) of
Only 1220 mm x 1220 mm (48 in. x 48 free area.
in.) louvers shall be tested. The toler- 10.2.2 Linear regression formula
ance is +0, -6 mm (+0, -0.25 in.). The following formula is used for the
simple linear regression:
All louvers tested for water penetra-
tion performance shall be prod- Y = B0 + B1 (ln X)
ucts as-built, unpainted, cleaned,
degreased and without additional Where:
factory-applied coating on the product Y = Free air velocity, m/s (fpm),
surfaces which would enhance water- result for plot of curve
shedding capability. All devices tested
shall be in the full open position with- X = Water penetration, mL/m2 (oz/
out a screen across the air passages ft2), defined
of the louver.
And:
The louver sample tested for water
penetration performance shall be B0 = Y i − B1 X i
the same sample tested for air
performance. Sxy
B1 =
Sxx
10.1.3 Air performance require-
ment n n
Certified air performance is required n ∑ (Yi )∑ (ln Xi )
prior to water penetration certification. Sxy = ∑ (ln X i )Yi − i =1 i =1
i =1
n
n 2
(ln X )
n ∑ i
2 i =1
Sxx = ∑ (ln X i ) −
i =1
n
8 | AMCA 511-13
10. Louver | Water Penetration Rating Requirements (page 2 of 2)
10.3 Published ratings
AMCA 511-13 | 9
11. Acoustical Louver | Sound Performance Rating Requirements
11.1 Testing requirements 11.2 Calculated performance 11.3 Published ratings
11.1.1 Sound performance test 11.2.1 Free Field Noise Reduction 11.3.1 Sound performance
All transmission loss acoustical test- Free field noise reduction shall be Acoustical ratings shall be stated as
ing shall be in accordance with ASTM determined by adding 6 dB to the free field noise reduction (dB) in the
E90. transmission loss (dB). 2nd through 7th octave bands.
10 | AMCA 511-13
12. Adjustable Louver | Air Leakage Rating Requirements
12.1 Testing requirements 12.2 Calculated performance 12.3 Published ratings
12.1.1 Air leakage test 12.2.1 Air leakage 12.3.1 Air leakage performance
All testing for air leakage through Air leakage performance of any size Published ratings of air leakage
closed adjustable louvers shall be louver shall be calculated from tests performance shall be presented in
per ANSI/AMCA 500-L, Figure 5.4 or of no less than three sizes (single either tabular form, graphical form or
Figure 5.5. panel design) of the same design. both as a statement of the maximum
tested air leakage at the following:
12.1.2 Test samples Data presented shall be a plot of L/s/
Test data shall be submitted for the m2 (cfm/ft2) of face area versus ∆Ps • A specified differential pressure
following sizes: that reflects the largest value of L/s/ • Standard air density
m2 (cfm/ft2) air leakage of the louvers • AMCA figure or figures to which air
• Minimum width x maximum height tested at each value of ∆Ps. leakage performance is tested
• Maximum width x minimum height
• Maximum width x maximum height 12.2.2 Blade spacing variations 12.3.2 Torque statement
Where the design blade spacing The following statement shall be
12.1.3 Number of tests varies, the manufacturer shall submit included:
A minimum of two tests shall be data from tests of both the smallest
conducted on each sample. The and greatest blade spacing to show “Data are based on the maximum
adjustable louver shall be cycled that all test data will fall within the torque of [#] N•m/m2 (in.-lb/ft2) applied
to full open and back to full closed specified tolerances. to the louver during the test.”
between each test.
12.2.3 Extrapolation [Any number ending with a decimal
Extrapolation above the maximum or greater than 0.02 shall be rounded
below the minimum test DPs shall not to the next higher number, e.g., 6.12
be permitted. N•m/m2 = 6.1 N•m/m2 and 6.13 N•m/
m2 = 6.2 N•m/m2 (5.12 in.-lb/ft2 = 5.1
in.-lb/ft2 and 5.13 in. lb/ft2 = 5.2 in.*lb/
ft2)]
AMCA 511-13 | 11
13. Damper | Air Performance Rating Requirements (page 1 of 2)
13.1 Testing requirements 13.2 Calculated performance
13.1.1 Pressure drop test 13.1.2.2 Round (excluding back- 13.2.1 Extrapolation
All testing for pressure drop determi- draft dampers)
nations of single-blade, multi-blade or Test data shall be submitted for the 13.2.1.1 Below test pressure
curtain dampers (excluding backdraft following sizes (diameters): Extrapolation below the minimum test
dampers) in the full open position static pressure drop shall be permit-
shall be per ANSI/AMCA 500-D, per • 305 mm (12 in.) ted, excluding backdraft dampers.
at least one of Figures 5.1, 5.2, 5.3, • 610 mm (24 in.)
5.4, or 5.5. Testing shall be conducted • 914 mm (36 in.) 13.2.1.2 Above test pressure
in both directions of airflow (front to Extrapolation above the maximum
back and back to front). If the smallest damper is larger than test static pressure drop shall not be
305 mm (12 in.) or the largest damper permitted.
Vertically mounted backdraft damp- is smaller than 914 mm (36 in.), three
ers shall be mounted per Figure 5.4 or sizes shall be tested: 13.2.1.3 Sizes
5.5 so that the airflow assists opening Extrapolation outside of test sizes
of the dampers. Horizontally mounted • Largest shall not be permitted.
backdraft dampers shall be tested per • Smallest
Test Figure 5.7A, 5.7B, 5.7E or 5.7F • Midway between the largest and
and such that the airflow assists in smallest
opening.
13.1.2.3 Rectangular (backdraft
13.1.2 Test samples dampers only)
A 610 mm x 610 mm (24 in. x 24 in.)
13.1.2.1 Rectangular (Excluding damper shall be tested. If the larg-
backdraft dampers) est size damper produced is smaller
Test data shall be submitted for the than 610 mm x 610 mm (24 in. x 24
following sizes: in.), the largest cataloged size shall
be tested. The tolerance is +0, -6 mm
• 305 mm x 305 mm (12 in. x 12 in.) (+0, -0.25 in.).
• 610 mm x 610 mm (24 in. x 24 in.)
• 914 mm x 914 mm (36 in. x 36 in.) 13.1.2.4 Round (backdraft damp-
• 305 mm x 1220 mm (12 in. x 48 ers only)
in.) A 610 mm (24 in.) diameter damper
• 1220 mm x 305 mm (48 in. x 12 shall be tested. If the largest size
in.) damper produced is smaller than 610
mm (24 in.), the largest cataloged
The tolerance is +0, -6 mm (+0, -0.25 size shall be tested.
in.). If the maximum single section
size is less than that shown above, a
multi-section damper shall be tested if
offered by the manufacturer. If any of
the sizes listed above are not offered
by the manufacturer, those sizes are
not required to be tested or listed. A
minimum of one of the sizes listed
above must be tested for a product
line to be eligible for certification.
12 | AMCA 511-13
13. Damper | Air Performance Rating Requirements (page 2 of 2)
13.3 Published ratings
13.3.3 Extrapolation
The portion of the air performance
curve obtained by extrapolation shall
be charted with a broken line and
must be a smooth continuation of the
adjacent portion of the curve.
AMCA 511-13 | 13
14. Volume Control Damper | Air Leakage Rating Requirements (page 1 of 2)
14.1 Testing requirements 14.2 Calculated performance
14 | AMCA 511-13
14. Volume Control Damper | Air Leakage Rating Requirements (page 2 of 2)
14.3 Published ratings
14.3.1 Air leakage performance When optional sizes are tested in 14.3.4.2 Round dampers
Published ratings of air leakage addition to the two required sizes, the The rating shall show the maximum
performance shall be a statement of air leakage class shall be published air leakage class from both sizes
the appropriate class at the following: as a function of the damper width. tested in both modes (pressure in
At each pressure to be cataloged, direction of flow, and back pressure).
• A specified differential pressure publish the air leakage class from the See Table 3.
• Standard air density worse performing of the two dampers
• AMCA figure or figures to which air used to establish each damper width 14.3.5 Operational statement
leakage performance is tested range. Published data shall state the
following:
14.3.2 Torque statement See the example test results and “Air leakage is based on operation
The following statement shall be corresponding published data in between 0 °C - 49 °C (32 °F - 120 °F)”
included: Annex C, Figure C.7b.
14.3.6 Air performance ratings
“Data are based on a torque of [#] Air performance ratings in the full
N•m/m2 (in.-lb/ft2) applied to close open position shall be published in
and seat the damper during the test.” accordance with Section 13.
AMCA 511-13 | 15
15. Ultra-Low Leakage Damper | Air Leakage Rating Requirements
15.1 Testing requirements 15.2 Calculated performance 15.3 Published ratings
15.1.1 Air leakage test 15.2.1 Extrapolation 15.3.1 Air leakage performance
All tests for air leakage through closed Published ratings of air leakage
single-blade or multi-blade control 15.2.1.1 Pressure performance shall be presented in
dampers shall be per ANSI/AMCA Extrapolation above the maximum either tabular form, graphical form or
500-D, Figure 5.4, 5.5, 5.6A or 5.6B. test DPs or below the minimum DPs both as a statement of the maximum
shall not be permitted. tested air leakage at the following:
15.1.2 Test sizes
15.2.1.2 Sizes • A specified differential pressure
15.1.2.1 Rectangular test sizes Extrapolation outside the range of • Standard air density
Test data shall be submitted for the test sizes shall not be permitted. • AMCA figure or figures to which air
following sizes: leakage performance is tested
16 | AMCA 511-13
16. Bubble-Tight Damper | Air Leakage Rating Requirements
16.1 Testing requirements 16.2 Calculated performance 16.3 Published ratings
16.1.1 Air leakage test 16.2.1 Extrapolation 16.3.1 Air leakage performance
All tests for air leakage through closed Published ratings of air leakage
single-blade or multi-blade control 16.2.1.1 Pressure performance for bubble-tight damp-
dampers shall be per ANSI/AMCA Extrapolation above the maximum ers shall be presented as the follow-
500-D, Figure 5.8. test DPs or below the minimum DPs ing statement:
shall not be permitted.
16.1.2 Test sizes “Dampers are bubble-tight up to [x]
16.2.1.2 Sizes Pa ([x] in. wg) differential pressure.”
16.1.2.1 Rectangular test sizes Extrapolation outside the range of
Test data shall be submitted for the test sizes shall not be permitted. 16.3.2 Torque table and statement
following sizes: A table stating the damper size and
required torque in N•m (in.-lb) and
• Minimum width x maximum height N•m/m2 (in.-lb/ft2) shall be included.
• Maximum width x minimum height
• Maximum width x maximum height The following statement shall be
included with the table:
16.1.2.2 Round test sizes
Test data shall be submitted for the “Data are based on the following
minimum and the maximum size torque required to close and seat the
dampers to be rated. damper during the test.”
AMCA 511-13 | 17
17. UL-Classified Damper | Air Leakage Rating Requirements
17.1 Testing requirements 17.2 Calculated performance 17.3 Published rating
17.1.1 Test sample 17.2.1 Air leakage 17.3.1 Air leakage performance
Damper shall be a UL-classified Air leakage performance shall meet Published rating of air leakage shall
damper as defined in Section 3.1.8. the requirements of the UL leakage be a statement of the UL 555S
classification for the model tested. published rating class.
17.1.2 Air leakage test
17.3.2 Air leakage class
17.1.2.1 Cycling before air leakage Published ratings shall show the
test maximum air leakage class in both
Before the air leakage test, the airflow directions.
damper shall be cycled open and
closed. During this cycle, the UL test 17.3.3 Figures to which tested
velocity corresponding to the highest Published ratings shall state the
velocity to which the damper is UL AMCA figure or figures to which they
classified shall be applied across the are tested.
open damper. The UL test DPs corre-
sponding to the highest pressure to 17.3.4 Air performance requirement
which the damper is UL classified to Air performance ratings of damp-
shall be applied across the closed ers in the full open position shall be
damper. published in accordance with Section
13.3.
17.1.2.2 Test figure
All testing for air leakage shall be
per ANSI/AMCA 500-D, Figure 5.4,
Figure 5.5 or Figure 5.9 at ambient
temperatures.
18 | AMCA 511-13
18. Backdraft Damper | Air Leakage Rating Requirements
18.1 Testing requirements 18.2 Calculated performance 18.3 Published rating
18.1.1 Air leakage test 18.2.1 Air leakage 18.3.1 Air leakage performance
All testing for air leakage through Air leakage performance at each DPs Published rating of air leakage perfor-
mounted dampers shall be per ANSI/ shall be the maximum L/s/m2 (cfm/ft2) mance shall be a statement of the
AMCA 500-D, Figure 5.4 or Figure of two tests conducted. maximum tested air leakage flow
5.5. Dampers shall be mounted such rate at a specified DPs at standard air
that the airflow closes the blades. 18.2.2 Extrapolation density.
AMCA 511-13 | 19
19. Gravity Ventilator (Excluding Louver Penthouses) | Air Performance Rating Requirements
19.1 Testing requirements 19.2 Calculated performance 19.3 Published ratings
19.1.1 Pressure drop test 19.2.1 Air performance 19.3.1 Air performance
All testing for pressure drop determina- Air performance of any size gravity Published ratings of air performance
tions of gravity ventilators shall be per ventilator may be calculated from data shall include the following for all
ANSI/AMCA 500-L, Figure 5.4 or 5.5. of a tested size. The manufacturer required sizes:
is responsible for ensuring proper
For Figure 5.4 testing, the outlet corrections are made to account for • Maximum DPs at a specified
chamber shall have a cross-sectional aspect ratio changes, changes in airflow rate
area at least nine (instead of fifteen) hood dimensions, etc., (see Figure • Data corrected to standard air
times the throat area of the device 19.1, dimensions C, D and E; or, density
being tested. Figure 19.2, dimensions C and E). • AMCA figure or figures to which
air performance is tested, for all
A test shall consist of five or more 19.2.2 Extrapolation required sizes
determinations taken at approxi- Extrapolation above the maximum • Minimum curb height, if applicable
mately equal increments of airflow and below the minimum test DPs shall
rate covering the range desired. not be permitted. 19.3.2 Presentation
Ratings shall be published in tabular
19.1.2 Screens form, graphical form or both.
Gravity ventilators shall be tested with
screens installed. 19.3.3 Rounding of data
Pressure drop information shall be
19.1.3 Test (throat) sizes presented rounded to the nearest
pascal, if using SI units in literature,
19.1.3.1 Rectangular
or presented with a maximum of two
The following throat sizes (see
digits after the decimal point, if using
Figure 19.1, dimensions A and B)
I-P units.
shall be tested for rectangular gravity
ventilators: 19.3.4 Screen/appurtenance
The type of screen installed on the
• 305 mm x 305 mm (12 in. x 12 in.)
unit during the test shall be listed in
• 610 mm x 610 mm (24 in. x 24 in.)
the required appurtenance statement
• 915 mm x 915 mm (36 in. x 36 in.)
(see Section 5.3).
• Smallest
• Largest
• Midway between the largest and
smallest
20 | AMCA 511-13
C D
A B
CxD
AxB
Figure 19.1
Gravity Ventilator with Rectangular and Square Hoods
Figure 19.2
Gravity Ventilator with Round Hood
AMCA 511-13 | 21
20. Round Spiral Duct | Air Leakage Rating Requirements
20.1 Testing requirements 20.2 Calculated performance 20.3 Published ratings
20.1.1 Air leakage test 20.2.1 Data correction 20.3.1 Air leakage performance
All spiral duct air leakage testing shall Air leakage performance shall be Published rating of air leakage perfor-
be conducted in accordance with corrected from actual conditions to mance shall be a statement of the
ANSI/ASHRAE/SMACNA Standard standard conditions using the equa- maximum tested air leakage flow rate
126-2008, Section 7. tions shown in ANSI/ASHRAE/ for each gauge at 3.75 kPa (15 in. wg)
SMACNA Standard 126-2008, DPs in m3/hr per 9.29 m2 (cfm per 100
20.1.2 Bubble test Section 7.4. ft2) of duct wall surface area at stan-
A bubble test shall be conducted in dard air density.
accordance with ANSI/AMCA 500-D 20.2.2 Data conversion
prior to the air leakage test to ensure The calculated air leakage perfor- 20.3.2 Test sample information
there is no endcap leakage. mance in m3/hr (cfm) shall be Published data shall include the
converted to m3/hr per 9.29 m2 (cfm following test sample information:
20.1.3 Test pressure per 100 ft2) of duct wall surface.
Testing shall be performed at 1.5 • Length
times the normal maximum design • Gauge
pressure of 2.5 kPa (10 in. wg). • Diameter
22 | AMCA 511-13
21. Louver/Damper | Energy Efficiency Rating Requirements
21.1 Testing requirements 21.2 Calculated performance 21.3 Published ratings
21.1.1 Thermal transmittance test The performance shall be rated as a 21.3.1 Required data
All tests for thermal transmittance percentage increase in efficiency over Ratings shall include the following:
shall be conducted in accordance the reference 3-V-groove damper. • Efficiency performance, stated
with AMCA Standard 500-D. as a percentage efficiency as
compared to the reference damper
21.1.2 Test sample • Test sample size
Test data shall be submitted for a 915 • Test figure
mm x 915 mm (36 in. x 36 in.) louver/
damper. 21.3.2 Torque statement
Published ratings shall include a
21.1.3 Test temperature statement of the torque required to
Testing shall be conducted such that hold the louver/damper in the closed
the thermal chamber temperature is position.
16.7 ºC (30 ºF) greater than the ambi-
ent lab temperature.
AMCA 511-13 | 23
22. Transverse Duct Connectors | Air Leakage Rating Requirements (page 1 of 2)
22.1 Testing requirements
22.1.1 Air Leakage Test 22.1.3 Test Duct Size Classification Flat oval and rectangular duct sizes
All transverse duct connector leakage Transverse connectors shall be tested have been selected based upon a
testing shall be conducted in accor- and rated in three duct size classifica- minimum 2:1 aspect ratio and with
dance with ANSI/ASHRAE/SMACNA tions, if manufactured. The duct size approximately the same perimeter
Standard 126-2008, Section 7. classifications are as shown in Table as the round duct size. The minor
4. axis will be the perimeter of the round
22.1.2 Test Pressure duct size divided by 6, then rounded
Testing shall be performed at all pres- 22.1.4 Test Sample down to the nearest 51 mm (2 in.)
sures up to the maximum rated pres- Transverse connectors shall be increment. The major axis will then be
sure classification. Pressure classifi- tested and rated in accordance with calculated to result in the same perim-
cations are as follows: one of the joint arrangements shown eter as the round duct size, rounded
in Figure 22.1a, 22.1b, and 22.2. up to the nearest 25 mm (1 in.) incre-
Pressure Required Test ment for rectangular duct. In the case
of flat oval ducts, the sample will be
Classification Pressures The test sample shall consist of
the manufacturer’s standard catalog
three 610 mm (24 in.) long duct
spiral pipe size stretched from the
SI (kPA) segments and two 305 mm (12 in.)
same tube as the round duct size.
+0.25 +0.25 long segments with sealed ends, to
+0.5 +0.25, +0.5 be assembled sequentially to form
The test sample shall be delivered
+1.0 +0.25, +0.5, +1 four transverse duct connections. The to the testing facility with transverse
+1.5 +0.25, +0.5, +1, +1.5 two ends and all longitudinal seams joints unassembled. The manufac-
+2.5 +0.25, +0.5, +1, +1.5, +2.5 shall be capped and/or sealed by the turer shall designate qualified assem-
manufacturer in a manner that will blers, and the transverse connections
-0.25 -0.25 effectively eliminate extraneous air will be applied/assembled at the test-
-0.5 -0.25, -0.5 leakage. One endcap shall contain ing facility. Independent testing facility
-1.0 -0.25, -0.5, -1 either two DN10 (3/8 in.) pipe sized personnel shall verify that application/
-1.5 -0.25, -0.5, -1, -1.5 barb fittings (for estimated leakage assembly has been performed per
-2.5 -0.25, -0.5, -1, -1.5, -2.5 up to 10 cfm), or one DN10 (3/8 in.) the manufacturer’s published installa-
pipe sized barb fitting and a 102 mm tion instructions. If the manufacturer
I-P (in. wg) (4 in.) pvc flange fitting (for leakage recommends a setting/curing time
+1 +1 above 10 cfm). All fittings should be for components of the transverse
+2 +1, +2 sealed by the manufacturer to elimi- connector, that time shall be recorded
+4 +1, +2, +4 nate potential leakage. and testing shall not occur until that
+6 +1, +2, +4, +6 time has passed.
+10 +1, +2, +4, +6, +10 The test sample shall be fabricated in
accordance with gauges, reinforce- 22.1.5 Test Procedure
-1 -1 ment, and construction, as recom- Each sample will be tested begin-
-2 -1, - 2 mended by the 2005 SMACNA HVAC ning at the lowest rated pressure,
-4 -1, -2, -4 Duct Construction Standards, for then progressing to the highest rated
-6 -1, -2, -4, -6 the maximum pressure classification pressure. Each rated pressure will
be reached and maintained for five
-10 -1, -2, -4, -6, -10 for which it will be rated. Where the
minutes. During that period, leakage
transverse connection method can
will be measured at one minute inter-
be considered part of the structural
vals and the average of the five read-
reinforcing, gauges used will based
ings will be the rated leakage at that
upon the two-foot spacing between
Table 4 pressure.
the transverse connector/reinforcing.
Duct Size Classification
Duct Size Round Duct Size Flat Oval Rectangular Duct Size Approximate
Classification Duct Size Perimeter
Small 305 mm (12 in.) φ 392/152 mm (15/6 in.) 330 mm x 152 mm (13 in. x 6 in.) 965 mm (38 in.)
Medium 610 mm (24 in.) φ 784/305 mm (31/12 in.) 660 mm x 305 mm (26 in. x 12 in.) 1905 mm (75 in.)
Large 1220 mm (48 in.) φ 1567/610 mm (62/24 in.) 1320 mm x 610 mm (52 in. x 24 in.) 3835 mm (151 in.)
24 | AMCA 511-13
22. Transverse Duct Connectors | Air Leakage Rating Requirements (page 2 of 2)
22.2 Calculated performance 22.3 Published ratings
22.2.1 Data Correction 22.3.1 Air Leakage Performance 22.3.3 Test Sample Information
Air leakage performance shall be Published rating of air leakage perfor- Published data shall include the
corrected from actual conditions to mance shall be a statement of the following test sample information:
standard conditions using the equa- average tested air leakage flow rate • Based upon four transverse joints
tions shown in ANSI/ASHRAE/ for each pressure and duct size clas- • Sample size
SMACNA Standard 126-2008, sification. All required test pressures • Gauge
Section 7.4. up to the maximum rated pressure • Duct shape
classification shall be published. • Duct seam
22.2.2 Data Conversion Leakage shall be given as cfm per
The calculated air leakage perfor- lineal foot of transverse connection. 22.3.4 Duct Size Classification
mance in m3/hr (cfm) shall be Definitions
converted to m3/hr per lineal meter 22.3.2 Performance Curves The rated duct size classifications
(cfm per lineal foot) of transverse For transverse connectors rated for shall be defined as follows:
connection. at least +1.5 kPa or -1.5 kPa (+6 in.
Rectangular,
wg or -6 in. wg), air leakage perfor-
Round or Oval Dimensions
Example: the transverse joint for a mance may be published as a graph Size Classification (Perimeter)
1220 mm x 610 mm (48 in. x 24 in.) with measured average data points
rectangular duct would be twelve fitted to a curve. The curve shall not Small 229 mm to 1600 mm
(9 in. to 63 in.)
lineal feet of transverse connection. be extrapolated beyond the rated
For metric ratings, the calculated pressure. Medium 1422 mm to 3200 mm
air leakage performance shall be (56 in. to 126 in.)
converted to cubic meter per hour per Large 2870 mm to 6100 mm
lineal meter. (113 in. to 240 in.)
305 mm 305 mm
(12 in.) 610 mm (24 in.) 610 mm (24 in.) 610 mm (24 in.) (12 in.)
Cap Cap
Figure 22.1a - Rectangle or Long Seam Round and Oval Flange Connections
305 mm 305 mm
(12 in.) 610 mm (24 in.) 610 mm (24 in.) 610 mm (24 in.) (12 in.)
End End
Cap Cap
305 mm 305 mm
(12 in.) 610 mm (24 in.) 610 mm (24 in.) 610 mm (24 in.) (12 in.)
End End
Coupling
Coupling
Slip End
Slip End
Cap Cap
AMCA 511-13 | 25
23. Duct Access Door | Air Leakage Requirements (page 1 of 2)
23.1 Testing requirements 23.1.5.1 Positive pressure
Access doors designed to be used in
23.1.1 Air leakage test The access door frame shall be ducts with positive pressure shall be
All tests for air leakage through an sealed to the duct by the laboratory in tested at 0.25 kPa (1 in. wg) incre-
access door mounted in ductwork accordance with the manufacturer’s ments of static pressure between the
shall be per ANSI/AMCA 500-D, Test published instructions. If the manu- following:
Figure 5.4, 5.5, 5.6A, 5.6B or 5.8. facturer’s instructions list more than
one method for installing or sealing 1. 0.25 kPA (1 in. wg)
23.1.2 Test sizes the access door to the duct, all instal-
lation and sealing methods shall be and
23.1.2.1 Rectangular or oval test tested.
sizes 2. The maximum pressure at which
Test data shall be submitted for the The duct work shall be provided the access door is to be rated
following sizes: by the licensee in accordance with
Figure 23. The duct shall be sealed 23.1.5.2 Negative pressure
• Minimum width x minimum height with an endcap on each end and Access doors designed to be used
• Maximum width x maximum height have at least 305 mm (12 in.) from the in ducts with negative pressure shall
access door to the ends of the duct be tested at 0.25 kPa (1 in. wg) incre-
23.1.2.2 Round test sizes (see Figure 23). ments of static pressure between the
Test data shall be submitted for the following:
minimum and maximum size access To allow the laboratory to put the duct/
doors to be rated. access door assembly under vacuum 1. -0.25 kPA (-1 in. wg)
and pressure, one of the following two
23.1.3 Modes tested and
configurations shall be used:
Access doors designed to be used in
ducts with positive pressure shall be 2. The minimum pressure the access
1. One endcap shall be provided with
tested per ANSI/AMCA 500-D Test door is to be rated.
a 102 mm (4 in.) hole (Figure 24a)
Figure 5.5, 5.6A or 5.8.
or 23.1.5.3 Positive or negative pres-
Access doors designed to be used sures
in ducts with negative pressure shall Access doors designed to be used in
2. One endcap shall be provided with
be tested per ANSI/AMCA 500-D Test ducts with either positive or negative
two barbed fittings for attachment
Figure 5.4 or 5.6B. pressure shall be tested at 0.25 kPa
of 0.25 in. I.D. air hoses (Figure
(1 in. wg) increments of static pres-
24b)
Access doors designed to be used in sure between:
ducts with either positive or negative
For round access doors, the duct 1. 0.25 kPA (1 in. wg)
pressure shall be tested twice. The
shall be a minimum of 3 times larger
first test shall be per ANSI/AMCA
in perimeter than the arc-length of and
500-D Test Figures 5.5, 5.6A or 5.8,
access door and at least 305mm (12
and the second test shall be per ANSI/ 2. The maximum pressure at which
in.) from the cap and connection to
AMCA 500-D Test Figure 5.4 or 5.6B. the access door is to be rated
the tunnel.
23.1.4 Testing configuration and between
If the access door is designed to be
The access door shall be tested while
installed in spiral duct work, it must be
installed in a test duct. The test duct 1. -0.25 kPA (-1 in. wg)
tested in spiral duct work.
shall be oriented such that the access
door faces down during the test. and
23.1.5 Test pressure
Test pressures used for published 2. The minimum pressure the access
The sample duct shall be constructed
values shall be within 25 Pa (0.10 door is to be rated.
from the lightest gauge material in
in. wg) of the published incremental
which the access door will be rated.
pressures.
There shall be at least 153 mm (6 in.)
between the access door frame and
the corners of the duct.
26 | AMCA 511-13
23. Duct Access Door | Air Leakage Requirements (page 2 of 2)
23.2 Calculated performance 23.3 Published ratings
AMCA 511-13 | 27
152 mm (6 in.) min.
305 mm 305 mm
(12 in.) min. (12 in.) min.
Bottom View
*test assembly supplied by manufacturer
Figure 23
Access Door Test Setup
28 | AMCA 511-13
W
0.5W
0.5H
End View
Figure 24a
Endcap
Figure 24b
Endcap — Alternate Configuration
AMCA 511-13 | 29
Annex A
Electronic Catalogs (Normative)
A.1 Introduction statement shall appear on the same screen as the perfor-
mance data:
This annex details the special requirements for licens-
ing electronic catalogs under the AMCA Certified Ratings “AMCA licensed for [certification type] ratings.”
Program for air control devices (AMCA Publication 511).
or
A.2 Scope
When performance data are certified but non-certified modi-
This annex covers performance data for all products that fications, such as appurtenances, accessories, etc., are
can be licensed by AMCA to use the AMCA Certified applied to the performance ratings, the following statement
Ratings seal in accordance with the requirements of AMCA shall appear on the same screen as the performance data:
Publication 511.
“AMCA licensed for [certification type] without
In addition to the requirements covered in this annex, all appurtenances.”
other requirements outlined in AMCA Publication 511 shall
be met when certifying performance in an electronic catalog. where [certification type] is one of the following:
When presenting certified and non-certified data on the Access instructions to the secondary qualifying statements
same screen, a clear differentiation must be made between shall be clearly displayed on the primary screen.
the data that are licensed and the data that are not licensed.
A.4.1.2 Licensed product statement
A.4 Statements The secondary statements shall contain the licensed prod-
uct statement required by Section 5.1.
A.4.1 Primary statements
A.4.1.3 Licensed product statement
A.4.1.1 Location The secondary statements shall contain the licensed perfor-
Primary statements shall be located on the same screen as mance statement required by Section 5.2.
the certified performance data.
A.4.1.4 Non-certified modifications statement
A.4.1.2 Statement When a certified device is licensed to bear the AMCA
When performance data are licensed and the corrections, Certified Ratings seal and non-certified modifications have
appurtenances and accessories applied to the air control been applied to the ratings, the following additional qualify-
device duplicate the test conditions, the following primary ing statement shall appear on the secondary screen:
30 | AMCA 511-13
“The AMCA licensed performance data has been modi-
fied for installation, appurtenances, accessories, etc., not
included in the certified data. The modified performance is
not AMCA licensed but is provided to aid in selection and
application of the device.“
AMCA 511-13 | 31
Annex B
Measurements (Normative)
C
L W L W L W W
A B
A
A
C H C H C H L H
C1 = B
B
B
Figure B.1
Typical Louver and Frame Cross Section Showing Minimum Distance Formula (continued →)
32 | AMCA 511-13
L[ A + B + (N ×C )]100
Free Area = L[ A + B + (N ×C )] Percent Free Area =
W ×H
Note:
When measuring two louvers placed back to back, the free area for the combined louvers shall be determined
as the smaller of the two free areas.
AMCA 511-13 | 33
B.2 Calculating damper area
C
L W L W L W W
A B
A
A
C H C H C H L H
C1 = B
B
B
Figure B.2
Calculating Damper Area
34 | AMCA 511-13
Annex C
Developing Air Control Product Catalogs (Informative)
AMCA 511-13 | 35
C.1 Louver Air Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
Recorded Data :
Det. p br tb p bc t do t wo t d5 P S8 t d8 ∆Pn
1 29.380 76.4 29.244 75.7 56.7 81.2 0.610 79.8 4.700
2 29.380 76.4 29.244 75.7 56.7 81.2 0.390 79.8 3.000
3 29.380 76.4 29.244 75.7 56.7 81.2 0.240 79.8 1.800
4 29.380 76.4 29.244 75.7 56.7 81.2 0.110 79.8 0.800
5 29.380 76.4 29.244 75.7 56.7 81.2 0.040 79.8 0.305
Figure C.1a
Example Louver Air Performance Test Report
These data are not certified by AMCA
36 | AMCA 511-13
Company ABC
Model AL123
1.0
Test Information
Tested in accordance with ANSI/AMCA 500-L, Figure 5.5
Test sample size is 1220 mm x 1220 mm (48 in. x 48 in.)
Air performance data are based on intake performance 0.01
1 10 20 30
Width - Inches
8 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
12 0.24 0.40 0.65 0.90 1.14 1.39 1.63 1.88 2.13 2.37 2.62 2.86 3.11 3.36 3.60 3.85
18 0.33 0.55 0.89 1.23 1.57 1.90 2.24 2.58 2.92 3.26 3.59 3.93 4.27 4.61 4.94 5.28
Height - Inches
24 0.47 0.80 1.28 1.77 2.25 2.74 3.22 3.71 4.19 4.68 5.16 5.65 6.13 6.62 7.10 7.59
30 0.61 1.03 1.66 2.28 2.91 3.54 4.17 4.79 5.42 6.05 6.68 7.30 7.93 8.56 9.19 9.81
36 0.78 1.32 2.12 2.92 3.72 4.53 5.33 6.13 6.93 7.74 8.54 9.34 10.14 10.94 11.75 12.55
42 0.92 1.56 2.51 3.46 4.41 5.36 6.31 7.26 8.21 9.16 10.11 11.06 12.01 12.96 13.91 14.86
48 1.06 1.79 2.88 3.98 5.07 6.16 7.25 8.34 9.44 10.53 11.62 12.71 13.80 14.90 15.99 17.08
54 1.23 2.08 3.35 4.61 5.88 7.15 8.41 9.68 10.95 12.21 13.48 14.75 16.02 17.28 18.55 19.82
60 1.38 2.32 3.73 5.15 6.56 7.98 9.39 10.81 12.22 13.64 15.05 16.46 17.88 19.29 20.71 22.12
66 1.52 2.55 4.11 5.67 7.22 8.78 10.34 11.89 13.45 15.01 16.56 18.12 19.68 21.23 22.79 24.35
72 1.69 2.84 4.57 6.30 8.04 9.77 11.50 13.23 14.96 16.69 18.43 20.16 21.89 23.62 25.35 27.08
78 1.83 3.08 4.96 6.84 8.72 10.60 12.48 14.36 16.24 18.12 19.99 21.87 23.75 25.63 27.51 29.39
84 1.97 3.32 5.34 7.36 9.38 11.40 13.42 15.44 17.47 19.49 21.51 23.53 25.55 27.57 29.59 31.62
90 2.14 3.60 5.80 7.99 10.19 12.39 14.58 16.78 18.98 21.17 23.37 25.57 27.76 29.96 32.16 34.35
Catalog ID: AL123 April, 2011
96 2.28 3.84 6.19 8.53 10.88 13.22 15.56 17.91 20.25 22.59 24.94 27.28 29.63 31.97 34.31 36.66
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.1b
Example Louver Air Performance Catalog
AMCA 511-13 | 37
C.2 Louver Wind-Driven Rain Test Report and Catalog Example
Corrected Data
Velocity Core Velocity Specified Nominal Corrected Water Water
Through Through Rainfall Supply Flow Penetrated Penetration Penetration
Determination Cal. Plate Louver Rate Water Flow Effectiveness Classification
v co vc qw q snom q dcor E
(fpm) (fpm) (gal/hr) (gal/hr) (gal/hr) (%)
1 0 0 20.135 45.955 0.0678 99.7 A
2 132 106 20.135 43.374 0.1245 99.4 A
3 197 218 20.135 42.210 0.1870 99.1 A
4 287 286 20.135 40.926 0.3382 98.3 B
5 380 386 20.135 39.383 0.6180 96.9 B
6 472 499 20.135 39.147 1.2218 93.9 C
7 587 586 20.135 37.797 1.6916 91.6 C
8 680 686 20.135 36.560 2.7802 86.2 C
9 780 761 20.135 34.432 3.1490 84.4 C
10 865 853 20.135 33.848 3.7163 81.5 C
11 991 987 20.135 33.069 4.9987 75.2 D
38 | AMCA 511-13
Company ABC
Model WDRL123
Company ABC certifies that the WDRL123 shown hereon
is licensed to bear the AMCA Seal. The ratings shown
are based on tests and procedures performed in accor-
dance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Program.
Width - Inches
8 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
12 0.24 0.40 0.65 0.90 1.14 1.39 1.63 1.88 2.13 2.37 2.62 2.86 3.11 3.36 3.60 3.85
18 0.33 0.55 0.89 1.23 1.57 1.90 2.24 2.58 2.92 3.26 3.59 3.93 4.27 4.61 4.94 5.28
Height - Inches
24 0.47 0.80 1.28 1.77 2.25 2.74 3.22 3.71 4.19 4.68 5.16 5.65 6.13 6.62 7.10 7.59
30 0.61 1.03 1.66 2.28 2.91 3.54 4.17 4.79 5.42 6.05 6.68 7.30 7.93 8.56 9.19 9.81
36 0.78 1.32 2.12 2.92 3.72 4.53 5.33 6.13 6.93 7.74 8.54 9.34 10.14 10.94 11.75 12.55
42 0.92 1.56 2.51 3.46 4.41 5.36 6.31 7.26 8.21 9.16 10.11 11.06 12.01 12.96 13.91 14.86
48 1.06 1.79 2.88 3.98 5.07 6.16 7.25 8.34 9.44 10.53 11.62 12.71 13.80 14.90 15.99 17.08
54 1.23 2.08 3.35 4.61 5.88 7.15 8.41 9.68 10.95 12.21 13.48 14.75 16.02 17.28 18.55 19.82
60 1.38 2.32 3.73 5.15 6.56 7.98 9.39 10.81 12.22 13.64 15.05 16.46 17.88 19.29 20.71 22.12
66 1.52 2.55 4.11 5.67 7.22 8.78 10.34 11.89 13.45 15.01 16.56 18.12 19.68 21.23 22.79 24.35
72 1.69 2.84 4.57 6.30 8.04 9.77 11.50 13.23 14.96 16.69 18.43 20.16 21.89 23.62 25.35 27.08
78 1.83 3.08 4.96 6.84 8.72 10.60 12.48 14.36 16.24 18.12 19.99 21.87 23.75 25.63 27.51 29.39
Catalog ID: WDRL123 April, 2011
84 1.97 3.32 5.34 7.36 9.38 11.40 13.42 15.44 17.47 19.49 21.51 23.53 25.55 27.57 29.59 31.62
90 2.14 3.60 5.80 7.99 10.19 12.39 14.58 16.78 18.98 21.17 23.37 25.57 27.76 29.96 32.16 34.35
96 2.28 3.84 6.19 8.53 10.88 13.22 15.56 17.91 20.25 22.59 24.94 27.28 29.63 31.97 34.31 36.66
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.2b
Example Louver Wind-Driven Rain Catalog
AMCA 511-13 | 39
C.3 Louver Water Penetration Test Report and Catalog Example
Appurtenances : None
Remarks :
Net
Test Results : Weight Beginning of water penetration per
Det. QS V Free Area (oz./ft2) AMCA Publication 511 Subsection C3.2
1 3271.8 697.6 0.002
based on AMCA measured free area :
2 3527.4 752.1 0.004
799.4 fpm
3 3765.8 802.9 0.012
4 3990.1 850.8 0.025
-999.0 ######
-999.0 ######
-999.0 ######
-999.0 ######
-999.0 ######
-999.0 ######
Figure C.3a
Example Louver Water Penetration Test Report
40 | AMCA 511-13
Company ABC
Model AL123
Company ABC certifies that the AL123 shown hereon is licensed to bear the AMCA Seal. The
ratings shown are based on tests and procedures performed in accordance with AMCA Publi-
cation 511 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Performance and Water Penetration ratings.
Test Information
Tested in accordance with ANSI/AMCA 500-L, Figure 5.5
Test sample size is 1220 mm x 1220 mm (48 in. x 48 in.)
Air performance data are based on intake performance
0.3 1.0
Water Penetration (oz./ft2 of Free Area)
0.1
0.1
0.0
700 800 900 1000 0.01
1 10 20 30
Free Area Velocity (FPM)
Free Area Velocity (FPM x 100)
Width - Inches
8 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
12 0.24 0.40 0.65 0.90 1.14 1.39 1.63 1.88 2.13 2.37 2.62 2.86 3.11 3.36 3.60 3.85
18 0.33 0.55 0.89 1.23 1.57 1.90 2.24 2.58 2.92 3.26 3.59 3.93 4.27 4.61 4.94 5.28
Height - Inches
24 0.47 0.80 1.28 1.77 2.25 2.74 3.22 3.71 4.19 4.68 5.16 5.65 6.13 6.62 7.10 7.59
30 0.61 1.03 1.66 2.28 2.91 3.54 4.17 4.79 5.42 6.05 6.68 7.30 7.93 8.56 9.19 9.81
36 0.78 1.32 2.12 2.92 3.72 4.53 5.33 6.13 6.93 7.74 8.54 9.34 10.14 10.94 11.75 12.55
42 0.92 1.56 2.51 3.46 4.41 5.36 6.31 7.26 8.21 9.16 10.11 11.06 12.01 12.96 13.91 14.86
48 1.06 1.79 2.88 3.98 5.07 6.16 7.25 8.34 9.44 10.53 11.62 12.71 13.80 14.90 15.99 17.08
54 1.23 2.08 3.35 4.61 5.88 7.15 8.41 9.68 10.95 12.21 13.48 14.75 16.02 17.28 18.55 19.82
Catalog ID:
60AL123
1.38 2.32 April,
3.73 2011
5.15 6.56 7.98 9.39 10.81 12.22 13.64 15.05 16.46 17.88 19.29 20.71 22.12
66 1.52 2.55 4.11 5.67 7.22 8.78 10.34 11.89 13.45 15.01 16.56 18.12 19.68 21.23 22.79 24.35
72 1.69 2.84 4.57 6.30 8.04 9.77 11.50 13.23 14.96 16.69 18.43 20.16 21.89 23.62 25.35 27.08
78 1.83 3.08 4.96 6.84 8.72 10.60 12.48 14.36 16.24 18.12 19.99 21.87 23.75 25.63 27.51 29.39
Note:
84 1.97 3.32 5.34 7.36 9.38 11.40 13.42 15.44 17.47 19.49 21.51 23.53 25.55 27.57 29.59 31.62
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
90 2.14 3.60 5.80 7.99 10.19 12.39 14.58 16.78 18.98 21.17 23.37 25.57 27.76 29.96 32.16 34.35
lation information,
96 pictures,
2.28 3.84etc.,6.19
may 8.53
be added
10.88 as necessary.
13.22 15.56 17.91 20.25 22.59 24.94 27.28 29.63 31.97 34.31 36.66
Figure C.3b
Example Louver Water Penetration Catalog
AMCA 511-13 | 41
C.4 Louver Sound Performance Test Report and Catalog Example
The octave band transmission loss values calculated approximate what would be measured if the spectrum in the
source room had the same sound pressure level in each one-third octave band.
60.0
50.0
Sound Pressure Level (dB)
40.0
30.0
20.0
10.0
0.0
100
125
160
200
250
315
400
500
630
800
1000
1250
1600
2000
2500
3150
4000
5000
Frequency (Hz)
Test Sound Pressure Level Background Clearance Background Sound Pressure Level
Test Sound Pressure Level must be at least 5 dB greater than Background Sound Pressure Level.
If the Background Clearance exceeds the Test Sound Pressure Level, result is "an estimate of the lower limit."
Figure C.4a
Example Acoustical Louver Sound Performance Test Report
42 | AMCA 511-13
Company ABC
Model AL123
Test Information
Tested for air performance in accordance with ANSI/
0.01
AMCA 500-L, Figure 5.5 1 10 20 30
Test sample size is 1220 mm x 1220 mm (48 in. x 48 in.)
Air performance data are based on intake performance Free Area Velocity (FPM x 100)
Width - Inches
8 12 18 24 30 36 42 48 54 60 66 72 78 84 90 96
12 0.24 0.40 0.65 0.90 1.14 1.39 1.63 1.88 2.13 2.37 2.62 2.86 3.11 3.36 3.60 3.85
18 0.33 0.55 0.89 1.23 1.57 1.90 2.24 2.58 2.92 3.26 3.59 3.93 4.27 4.61 4.94 5.28
Height - Inches
24 0.47 0.80 1.28 1.77 2.25 2.74 3.22 3.71 4.19 4.68 5.16 5.65 6.13 6.62 7.10 7.59
30 0.61 1.03 1.66 2.28 2.91 3.54 4.17 4.79 5.42 6.05 6.68 7.30 7.93 8.56 9.19 9.81
36 0.78 1.32 2.12 2.92 3.72 4.53 5.33 6.13 6.93 7.74 8.54 9.34 10.14 10.94 11.75 12.55
42 0.92 1.56 2.51 3.46 4.41 5.36 6.31 7.26 8.21 9.16 10.11 11.06 12.01 12.96 13.91 14.86
48 1.06 1.79 2.88 3.98 5.07 6.16 7.25 8.34 9.44 10.53 11.62 12.71 13.80 14.90 15.99 17.08
54 1.23 2.08 3.35 4.61 5.88 7.15 8.41 9.68 10.95 12.21 13.48 14.75 16.02 17.28 18.55 19.82
60 1.38 2.32 3.73 5.15 6.56 7.98 9.39 10.81 12.22 13.64 15.05 16.46 17.88 19.29 20.71 22.12
66 1.52 2.55 4.11 5.67 7.22 8.78 10.34 11.89 13.45 15.01 16.56 18.12 19.68 21.23 22.79 24.35
72 1.69 2.84 4.57 6.30 8.04 9.77 11.50 13.23 14.96 16.69 18.43 20.16 21.89 23.62 25.35 27.08
Catalog
78 ID:
1.83AL123
3.08 4.96 April,
6.84 2011
8.72 10.60 12.48 14.36 16.24 18.12 19.99 21.87 23.75 25.63 27.51 29.39
84 1.97 3.32 5.34 7.36 9.38 11.40 13.42 15.44 17.47 19.49 21.51 23.53 25.55 27.57 29.59 31.62
90 2.14 3.60 5.80 7.99 10.19 12.39 14.58 16.78 18.98 21.17 23.37 25.57 27.76 29.96 32.16 34.35
Note: 96 2.28 3.84 6.19 8.53 10.88 13.22 15.56 17.91 20.25 22.59 24.94 27.28 29.63 31.97 34.31 36.66
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.4b
Example Acoustical Louver Sound Performance Catalog
AMCA 511-13 | 43
C.5 Adjustable Louver Leakage Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
Figure C.5a
Example Adjustable Louver
These data are not Air
certified by Leakage Test Report
AMCA
44 | AMCA 511-13
Company ABC
Model AL123
Company ABC certifies that the AL123 shown hereon is licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified Ratings Program.
Test Information
Tested in accordance with ANSI/AMCA 500-L, Figure 5.4
Air leakage data are based on intake performance
Data are based on the maximum torque of 120 in-lb/ft2 applied to hold
the louver during the test.
Air leakage is based on operation between 50 °F and 104 °F
10
9
8
7
60
60
12
Static Pressure (in. w.g.)
x
x
60
12
60
5
1
1 2 3 4 5 6 7 8 9 10 20 30
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.5b
Example Adjustable Louver Air Leakage Catalog
AMCA 511-13 | 45
C.6 Damper Air Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
Figure C.6a
Example Damper Air Performance Test Report
These data are not certified by AMCA.
46 | AMCA 511-13
Company ABC
Model DAMP
Company ABC certifies that the DAMP shown hereon is licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified Ratings Program.
Test Information
Tested in accordance with ANSI/AMCA 500-D, Figure 5.3
1.0
∆Ps Pressure Drop (in. wg)
2
x2 8x1 x1
12
4 2
244
0.1
8
x4
12
6
x3
36
0.01
1 10 100
Free Area Velocity (FPM x 100)
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.6b
Example Damper Air Performance Catalog
AMCA 511-13 | 47
C.7 Volume Control Damper Leakage Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
Figure C.7a
Example Volume Control Damper Air Leakage Test Report
48 | AMCA 511-13
Example 1
The company certifying the leakage performance only conducted tests on the two required sizes. The maximum single section
width of this model is 60 in. Because only the two required sizes were tested, the catalog data does not have to distinguish the
leakage performance at different widths.
Example 2
The same company certifies the same damper as in Example 1. This time they test one optional size, 16 in. x 36 in., along with
the two required sizes. This allows them to catalog leakage class 1A performance at 1 in. wg on dampers 16 in. and wider.
Leakage Class
Damper 1 in. wg 4 in. wg 6 in. wg 8 in. wg
Leakage Class Test Results
Width
1 in. wg 4 in. wg 6 in. wg 8 in. wg
Less than
12 x 48 in. 1 1 1 1 1 1 1 1
16 in.
16 x 36 in. 1A 1 1 1 16 to
1A 1 2 2
60 x 36 in. 1A 1 2 2 60 in.
Example 3
The same company again certifies the same damper as in Example 1. This time they test two optional sizes, 16 in. x 36 in. and
a 48 in. x 36 in., along with the two required sizes. This not only allows them to catalog leakage class 1A performance at 1 in.
wg on dampers 16 in. and wider, but also allows them to catalog class 1 performance at up to 8 in. wg on dampers all the way
up to 48 in. wide.
Example Catalog Table
Leakage Class
Damper 1 in. wg 4 in. wg 6 in. wg 8 in. wg
Width
Leakage Class Test Results
Less than
1 in. wg 4 in. wg 6 in. wg 8 in. wg 1 1 1 1
16 in.
12 x 48 in. 1 1 1 1
16 x 36 in. 1A 1 1 1 16 to 60 in. 1A 1 1 1
48 x 36 in. 1A 1 1 1 48.01 to
1A 1 2 2
60 x 36 in. 1A 1 2 2 60 in.
Figure C.7b
Example Volume Control Damper Air Leakage Test Results and Corresponding Published Data
AMCA 511-13 | 49
Company ABC
Model DAMP
Company ABC certifies that the DAMP shown hereon is licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Performance ratings.
Test Information
Air leakage is based on operation between 32 °F and 120 °F
Tested for air leakage in accordance with ANSI/AMCA Standard 500-D, Figure 5.4
Tested for air performance in accordance with ANSI/AMCA 500-D, Figure 5.3
Torque
Data are based on a torque of 7.5 in-lb/ft2 applied to close and seat the damper during the test.
Leakage Performance
Leakage Class
Damper Width 1 in. wg 4 in. wg 6 in. wg 8 in. wg
Less than 16 in. 1 1 1 1
16 in. to 48 in. 1A 1 1 1
48.01 in. to 60 in. 1A 1 2 2
Air Performance
1.0
∆Ps Pressure Drop (in. wg)
2
x2 8x1 x1
12
4 2
244
0.1
8
x4
12
6
x3
36
0.01
1 10 100
Free Area Velocity (FPM x 100)
Catalog ID: AL123 April, 2011
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.7c
Example Volume Control Damper Air Leakage Catalog
50 | AMCA 511-13
C.8 Ultra-Low-Leakage Damper Leakage Test Report and Catalog Example
Appurtenances : None
Remarks :
Figure C.8a
Example Ultra-Low-Leakage Damper Air Leakage Test Report
These data are not certified by AMCA
AMCA 511-13 | 51
Company ABC
Model ULL-DAMP
Company ABC certifies that the ULL-DAMP shown hereon is licensed to bear the AMCA
Seal. The ratings shown are based on tests and procedures performed in accordance with
AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings
Program.
Test Information
Air leakage is based on operation between 32 °F and 104 °F
Tested for air leakage in accordance with ANSI/AMCA Standard 500-D, Figure 5.4
Torque
Data are based on a torque of 7.5 in-lb/ft2 applied to close and seat the damper during the
test.
Leakage Performance
2
0
0
x1
x6
x6
60
60
12
Static Pressure (in. w.g.)
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.8b
Example Ultra-Low Leakage Damper Air Leakage Catalog
52 | AMCA 511-13
C.9 Bubble-Tight Damper Leakage Performance Test Report and Catalog Example
Appurtenances :
Remarks :
Ambient Conditions
Bubble Solution
Bubble solution used was equal parts liquid detergent, glycerin, and water.
Det. Ps9 No Bubbles exceed 1/16 in. No Bubbles exceed 1/4 in. Test
(in. wg) Diameter in 1 second Diameter in 1 minute. Result
1 1 Yes No Yes No Pass
2 15 Yes No Yes No Pass
3 30 Yes No Yes No Pass
Additional Comments
Figure C.9a
Example Bubble-Tight Damper Air Leakage Test Report
AMCA 511-13 | 53
Company ABC
Model BT-DAMP
Company ABC certifies that the BT-DAMP shown hereon is licensed to bear the AMCA
Seal. The ratings shown are based on tests and procedures performed in accordance with
AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings
Program.
Test Information
Air leakage is based on operation between 32 °F and 120 °F
Performance Data
Dampers are bubble-tight up to 30 in. wg differential pressure.
Torque Table
Required Torque
Damper Size (in.) in-lb in-lb/ft2
12” round 25 31.8
36” round 150 21.2
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.9b
Example Bubble-Tight Damper Air Leakage Catalog
54 | AMCA 511-13
C.10 Backdraft Damper Leakage Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
Figure C.10a
Example Backdraft Damper Air Leakage Test Report
These data are not certified by AMCA
AMCA 511-13 | 55
Company ABC
Model BD-DAMP
Company ABC certifies that the BD-DAMP shown hereon is licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 511 and comply with the requirements of the AMCA Certified Ratings Program.
The AMCA Certified Ratings Seal applies to Air Leakage and Air Perfomance ratings.
Test Information
Air leakage is based on operation between 32 °F and 120 °F
Tests for air leakage were conducted in accordance with ANSI/AMCA Standard 500-D, Figure
5.4, in the intake direction, on a 24 in. x 24 in. sample
4
Static Pressure Drop (in. wg)
0.1
1
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 80 100
0.01
100 1,000 10,000
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.10b
Example Backdraft Damper Air Leakage Catalog
56 | AMCA 511-13
C.11 Gravity Ventilator Air Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
Curb height: 12 in.
Screen: 1/2 in. x 1/2 in. galvanized mesh
Recorded Data :
Det. p br tb p bc t do t wo t d5 P S8 t d8 ∆Pn
1 29.380 76.4 29.244 75.7 56.7 81.2 0.610 79.8 4.700
2 29.380 76.4 29.244 75.7 56.7 81.2 0.390 79.8 3.000
3 29.380 76.4 29.244 75.7 56.7 81.2 0.240 79.8 1.800
4 29.380 76.4 29.244 75.7 56.7 81.2 0.110 79.8 0.800
5 29.380 76.4 29.244 75.7 56.7 81.2 0.040 79.8 0.305
Figure C.11a
Example Gravity
These data are Ventilator
not certified by Air
AMCAPerformance Test Report
AMCA 511-13 | 57
Company ABC
Model GV
Company ABC certifies that the GV shown hereon is licensed to bear the AMCA Seal. The
ratings shown are based on tests and procedures performed in accordance with AMCA Publi-
cation 511 and comply with the requirements of the AMCA Certified Ratings Program.
Test Information
Tested in accordance with AMCA Figure 5.5.
Test data include the effects of a 1/2 in. x 1/2 in. galvanized mesh screen
The model GV curb height is 12 in.
Performance Data
Pressure drop data were obtained in the exhaust mode
4
x1
x2
1.0
6
x3
12
24
36
∆Ps Pressure Drop (in. wg)
0.1
0.01
100 1000 10000
Free Area Velocity (FPM)
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.11b
Example Gravity Ventilator Air Performance Catalog
58 | AMCA 511-13
C.12 Spiral Duct Leakage Performance Test Report and Catalog Example
Remarks :
Calculated Data
Figure C.12a
Example Spiral Duct Air Leakage Performance Test Report
AMCA 511-13 | 59
Company ABC
Models SP26 SP24 SP22 SP20
Test Sample
Length: 10 ft
Diameter: 24 in.
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.12b
Example Spiral Duct Air Leakage Catalog
60 | AMCA 511-13
C.13 Duct Access Door Leakage Performance Test Report and Catalog Example
Appurtenances : None
Remarks :
-999.000 -999.00
-999.000 -999.00
-999.000 -999.00
-999.000 -999.00
Figure C.13a
Example Duct Access Door Air Leakage Performance Test Report
AMCA 511-13 | 61
Company ABC
Model AD
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.13b
Example Duct Access Door Air Leakage Catalog
62 | AMCA 511-13
C.14 Flat Oval Spiral Duct Leakage Performance Test Report and Catalog Example
ANSI/ASHRAE/SMACNA Standard 126-2008 Flat Oval Spiral Duct Leakage Test Report
Remarks :
Calculated Data
Figure C.14a
Example Flat Oval Spiral Duct Air Leakage Performance Test Report
AMCA 511-13 | 63
Company ABC
Models FO26 FO24 FO22 FO20
Test Sample
Length: 10 ft
Duct Size: 12 in. x 30.85 in.
Note:
This sample catalog contains only the items required for certification. Additional information, such as construction details, instal-
lation information, pictures, etc., may be added as necessary.
Figure C.14b
Example Flat Oval Spiral Duct Air Leakage Catalog
64 | AMCA 511-13
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
Email : info@amca.org Web: www.amca.org