You are on page 1of 4

Polymer vs Porcelain Suspension

Insulator Equivalence -
What To Use?

The superiority of polymer


insulators over porcelain insulators
leads to several differences in
characteristics and application
criteria for these two insulation
systems. Examined in this article are
the various criteria used in selecting
insulators and the development of a
suitable method for selecting the
correct size polymer insulator.

Types of Equivalence
Several different methods of
making equivalence comparisons
come to mind when comparing
polymer and porcelain insulators.
The first broad category is physical
Size difference is apparent as equalled-strength insulators are side-by-side.
equivalences, including the strength
rating of the insulators, and the
section length (coupling length) of Ohio Brass polymer suspension with an SML equal to or greater
the porcelain insulator string and insulators, the equivalent measure than this M & E value.
the polymer insulator unit. is the specified mechanical load
The second broad category is (SML). The SML test is a 90-second Section Length Equivalence
electrical equivalences. Among these tension withstand test at the SML The modular construction of the
are the leakage distance, the 60 Hz value. Ohio Brass polymer insula- Hi*Lite XL insulators can match
wet and dry flashover values, and tors are available in strength ratings within 11⁄2" any section length
the positive and negative impulse equal to or exceeding porcelain desired. Often the structure design
critical values. insulator M & E strengths. has progressed well before insula-
Typically, a porcelain suspension tor selections are made, and there is
Physical Equivalence insulator is proof tested at 50 little room for variations in section
The ultimate strength of porcelain percent of its M & E value. Ohio length. Ohio Brass Hi*Lite XL
suspension insulators is character- Brass Hi*Lite XL polymer insulators polymer insulators are produced in
ized by the porcelain mechanical are proof tested at a value of 50 variable section lengths to meet any
and electrical (M & E) value. This percent of the SML. This routine need, so the section length of
value is determined from a mechani- test load (RTL) is performed on porcelain previously used can be
cal strength test performed on every Ohio Brass Hi*Lite suspen- matched closely.
individual suspension bells. The sion insulator.
applied electrical stress tests the Therefore, in selecting the proper Electrical Equivalence
integrity of the relatively thin strength Hi*Lite XL insulator, After the section length of the
porcelain section between the cap consider only the porcelain M & E Hi*Lite XL polymer insulator is
and pin to indicate the load at which rating which was previously used selected, the electrical characteris-
mechanical failure initiates. For and select a Hi*Lite XL insulator tics must be verified for suitability
bells with a leakage distance of Lightning Impulse Voltages
172.5 inches. The Hi*Lite XL Lightning impulse voltages are
insulator with equivalent section the most challenging to insulate
length is Catalog No. 511212, which against. Even manufacturers’
has a leakage distance of 192 inches. literature indicates that a major
In this case the Hi*Lite XL insulator design criteria of high voltage
offers 11 percent more leakage insulators is that they should not
distance in the same section length. flashover under any condition
except lightning.
Switching Impulse Because lightning is such an
Transient Performance unpredictable phenomenon, few
Due to improvements in breaker utilities know the stroke currents
technology, switching transients for which they have designed. They
have been greatly reduced over the only know the impulse critical
past 50 years. For example, in the positive and negative values listed
1930’s, switching transients were for the porcelain insulator strings in
measured as high as 5.5 per unit, use.
The low-profile, high-strength Hi*Lite while today’s breakers will limit the Often overlooked is that porce-
insulator. voltages to three per unit or less. lain insulator strings frequently
Therefore, for the 230 kV system, include one to two “insurance
with the system voltage. In per- the maximum switching surge units”. These insurance units were
forming this analysis, three voltage voltage to which the insulators included in the string in the event
stresses are typically considered: 60 would be subjected is 563 kV. that units were damaged during
Hz power frequency, switching 230 kV shipment or installation or punc-
impulse, and lightning impulse
voltage.
(√ 3 x √ 2 x 3.0 ). tured in service.
For example, in the 230 kV case,
The simplest way to coordinate the 15 bells would have positive
60 Hz Power Frequency insulation levels with expected and negative impulse critical values
A major cause of transmission switching surge voltages is by of 1345 and 1360 kV, respectively.
line flashovers is contamination using the 60 Hz wet and dry values. However, if two damaged insula-
build-up on the insulator string. There is some debate as to whether tors are assumed in the string, these
These flashovers can occur at the 60 Hz wet or dry value should values are reduced to 1185 and 1190
nominal system voltage. be used in the coordination. We kV respectively. By contrast the
Leakage distance is the primary will assume that switching will Hi*Lite XL insulator is not prone to
factor which determines an occur during a storm when the damage; it is always electrically
insulator’s performance under insulators are wet. intact. The positive and negative
contaminated conditions. When an The 15 porcelain bells will have a impulse critical voltages for the
Ohio Brass Hi*Lite XL polymer 60 Hz wet flashover of 600 kV, Hi*Lite insulator are 1215 and 1233
insulator is selected with a section while the Hi*Lite insulator, Catalog kV, respectively; in both cases they
length equal to the porcelain strings No. 511013, has a 60 Hz wet flash- are higher.
that were previously used, the over of 700 kV. In both cases, the Therefore, the lightning impulse
specific leakage distance of the values exceed the 563 kV expected performance of the equivalent
Hi*Lite insulator will be greater switching surge voltage. section length Hi*Lite XL insulator
than the specific leakage distance of Therefore, a Hi*Lite XL insulator will be equal to or greater than the
the porcelain insulator (leakage chosen with section length equal to porcelain insulator string.
divided by dry arc). porcelain string length will have
For example, at 230 kV, one equal or better switching impulse
typical porcelain string used is 15 voltage performance.
Linemen prefer working with lightweight polymer insulators.

Conclusion
All of the various electrical Table:
equivalences indicate that selecting 1. Mechanical: Choose Hi*Lite XL specified mechanical load
an Ohio Brass Hi*Lite XL polymer (SML) equal to or greater than porcelain M &
insulator with a section length E.
equal to that previously used in 2. Section Length: Choose Hi*Lite XL section length to (or
porcelain insulators will result in an greater than) porcelain section length.
assembly with equivalent or 3. Leakage Distance: If step 2 is followed, Hi*Lite XL specific
superior electrical performance. leakage distance will be greater than porce-
The following table summarizes lain.
the selection process. Selecting 4. Switching Surge: If step 2 is followed, Hi*Lite XL performance
Hi*Lite XL polymer insulators (60 Hz wet flash-over) will be greater than
equivalents based on section length porcelain.
is the appropriate criterion. 5. Impulse (Lightning): If step 2 is followed and allowances made for
“insurance units,” Hi*Lite XL values are
greater than porcelain.
®

UNITED STATES MEXICO


HUBBELL POWER SYSTEMS, INC. HUBBELL DE MEXICO, S.A. DE. CV
210 N. Allen Av. Coyoacan No. 1051
Centralia, Mo 65240-1395 Col. Del Valle
Phone: 573-682-5521 03100 Mexico, D.F.
Fax: 573-682-8714 Phone: 52-55-9151-9999
e-mail: hpsliterature@hps.hubbell.com Fax: 52-55-9151-9988
e-mail: vtasdf@hubbell.com.mx

CANADA ASIA
HUBBELL CANADA, INC. HUBBELL S.E. ASIA PTE. LTD.
870 Brock Road South 23 Tagore Lane #03-16
Pickering, Ontario L1W 1Z8 Tagore 23 Warehouse
Phone: 905-839-1138 Singapore 787601
Fax: 905-831-6353 Phone: 65-6454-4772
e-mail: infohps@hubbellonline.com Fax: 65-6454-4775
e-mail: hpsliterature@hps.hubbell.com

Web: http://www.hubbellpowersystems.com
E-mail: hpsliterature@hps.hubbell.com

™ ® ® ® ®

Reprinted from
Hi-Tension News 9301-H
Fall/Wint. 1993

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.
©Copyright 2004 Hubbell • 210 North Allen Street • Centralia, MO 65240
EU1205-HR