INSTALLATION INSTRUCTIONS
Dimensional Drawing "JV-52, JV-54, JV-56
prcuanox svcrzom
v3) [ cm
|
|
i, JE .__
+ »
-+—_——« ¢ ie
be ae |
Model Dimensions
(inches)
Suction | Discharge
ato{[w{ut]c {salu s D
wws2 | ™ | 34 | 41% | ot | 20% [ «1 | 09 24
wss | 7 | 38 | 45 | 77 | 30% | 72 | 45 3 2%
wss | 12 | 38 | so | 7 | 38 | 2 | 55 4 3
Howe Compressor ManualINSTALLATION INSTRUCTIONS.
‘Typical Groud Floor Installation Drawing
"JV" Series Reciprocating Compressor
/~ COMPRESSOR UNIT
STEEL BASE
_ EXISTING
= Algor
CONCRETE PAD
Typical Ground Floor Installation Drawing
"JD" Series Reciprocating Compressor
DIRECT DRIVE COMPRESSOR UNIT
STEEL BASE
ro
exstn
\ CONCRETE PAD
Howe -Compretor ManualThe compressor should be installed in a dry, well lighted room with sufficient space around the
unit for inspection and service.
‘Ample ventilation is necessary for trouble free operation. ‘The heat given off by both the motor
‘and compressor must be removed from the air in the mechanical room, otherwise the motor
may overheat and bearing temperatures may become excessive. Natural ventilation may be
sufficient where there are two or more windows and a large enough room for frequent air
changes. If this is not the case then forced ventilation is necessary, ventilating fan motors can
be controlled by a room thermostat located in the mechanical room. The importance of
adequate cooling cannot be overemphasized. Motors which will occasionally operate at more
than the nameplate rating will definitely have a shorter life if is not sufficiently cooled.
Space for flywheel and crankshaft removal should be provided. See individual compressor
drawings for dimensions
FOUNDATIONS
‘Compressors mounted on a concrete floor should have a minimum of 8" thickness. The
concrete foundation mixture should be made in accordance with good concrete practice.
‘The foundation should be isolated from the surrounding floor by leaving space on all sides of
the base for the installation and isolating material such as cork board or felt.
Whatever type of foundation is used, the compressor unit MUST be level.
DRAINS
Its important that the unit be located near a floor drain. Since a considerable amount of water
must be carried away when draining units with water-cooled condensers (for repair of seasonal
shut downs) a floor drain is especially important.
Howe J Compressor Manual