Lr No: JNTUH/CEH/CIVIL/MTL/QUA/TEM/L4/2019

Date: 11-10-2019
Client: CPWD Vishakhapatnam
Reference: Your Lr.No:23(67)/VCSD-V/2019/L4
Name of Organisation: Teemage Builders (P) Ltd
Agreement No: 17/VCD/2018-2019
Name of Work: O.T.M Complex - Indian Coast Guard - Visakhapatnam, Project ID: 1903010

LOAD TEST FOR THICK SOLID SLAB

Details of the Specimen:


1) Element ID: SL -05,
2) Thickness: 150 mm
3) Element Sectional Details : 3000 X 2150 X 150 mm
4) Grading of Concrete: M 50

Table 1: Observation Details after Loading (Load Test)

S. No Date Time Load (Kgs) Deflection Remarks


(mm), Dial
gauge
reading
1 03:25 PM 0 Kg 0 After 1 hr of
2 3:35 PM 900 Kg 0/55 Loading,
(0.55 mm) observed dial
3 3:44 PM 1800 Kg 1/03 gauge reading
4 4:00 PM 2700 Kg 1/48 is 3/65 i.e.
5 11/10/2019 4:11 PM 3600 Kg 2/83 3.65 mm
6 4:20 PM 4500 Kg 3/15
7 4:30 PM 5400 Kg 3/45
8 4:40 PM 6150 Kg 3/65
9 5:40 PM 6150 Kg 3/65
(After 1 hr
Loading)
Table 2: Observation Details after Unloading (Load Test)

S. No Date Time Load (Kgs) Deflection Remarks


(mm), Dial
gauge
reading
1 5:45 PM 5400Kg 3/52 After 1 hr of
(3.52 mm) Unloading,
2 5:50 PM 4500 Kg 3/25 observed
3 6:00 PM 3600 Kg 3/05 deflection is
4 6:05 PM 2700 Kg 2/65 0.61 mm
5 11/10/2019 6:10 PM 1800 Kg 1/93
6 6:15 PM 900 Kg 1/35
7 6:20 PM 0 Kg 0/65
8 7:20 PM 0 Kg 0/61
(1hr Wait)

Observations:
1) The deflection observed for the Slab is well within the permissible limits. Further, there was
no damage or cracks on the surface of the of Slab.

Chief Coordinator
ICS, JNTUH-CEH