Safety Cautions

Read the entire “Instruction Manual” carefully for important information about safety, handling,
installation, operation, maintenance, and parts replacements.
This equipment is designed and built in accordance with applicable safety standard in effect on
the date of manufacture. Unauthorized modifications will void warranty and can result in severe
injury, death and property damage. Do not make any modifications to the equipment.
Only qualified persons are to install, operate or service this equipment according to all applicable
codes and established safety practices.
Use only genuine Toshiba replacement parts and accessories. Improper components could cause
the equipment malfunction.
Do not install this equipment in areas where unusual service conditions exist. Using this
equipment in other than usual service conditions can result in equipment failure.
Do not exceed the ratings specified on the equipment nameplate or system accessories.
Underrated equipment can fail during operation causing fire, explosion, severe injury, death, and
property damage.

TRANSMISSION DISTRIBUTION & INDUSTRIAL SERVICES COMPANY


1-1, SHIBAURA 1-CHOME, MINATO-KU, TOKYO 105-8001, JAPAN
PHONE +81-3-3457-4898 FAX +81-3-5444-9169

http://www3.toshiba.co.jp/sic/english/swgr/products.htm

The data given in this catalog are subject to change without notice.

KSP-E2368 AD 4 Printed in Japan


2008-11(1.5)
Type-Form

Vacuum contactor
Rated voltage 7.2/3.6kV
Rated operational current G : 200A
H : 400A
Series
Operating mechanism No symbol : Non-latched type
Since the introduction of the first Vacuum L : Latched type
Configuration No symbol : Standard
Interrupter in 1962, Toshiba has been
-2 : Upper front terminal
continuously improving and developing
Vacuum Technology. Series Ratings Standard Special
Over 180 thousands Toshiba Vacuum
Fixed type 7.2/3.6kV 200A-6.3kA Non-latched type CV-6GA
Contactors and Combination Units have been
Latched type CV-6GAL
installed, providing reliable services in wide 400A-6.3kA Non-latched type CV-6HA CV-6HA-2
variety of applications worldwide. Latched type CV-6HAL CV-6HAL-2
Consistent with its dedication to the most
advanced vacuum technology, Toshiba offers Note : Other ratings are available, refer to catalog KSP-E2412.

new series of High-voltage vacuum contactors


and Vacuum Combination Units with fuses.
By adopting an electronics controlled circuit
and being designed compactly to ensure
reliability, handling ease and safety, the new
series of High-voltage Vacuum Contactors and
Type-Form
Vacuum Combination Units with fuses are
suitable for Motor starters, Transformer Vacuum combination unit
Series
feeders and Capacitor switching applications.
Rated operational voltage 3 : 3.3kV
6 : 6.6kV
Rated operational current G : 200A
H : 400A
Series
Draw-out/in mechanism No symbol : Fixed type
M : Manual type
No Surge Protection Required D : Handle type
Special main contact materials minimize chopping current. Operating mechanism No symbol : Non-latched type
No surge suppressor/arrester is required except for special L : Latched type
applications.
1 : Bushing type
Configuration
Series
Compact and Lightweight
Compact and slim design contactors can be applied to either Type Ratings Manual type Handle type Fixed type
two-tier motor starters or slim starters per IEC 60470(2000).
Standard 3.3kV 200A 40kA Non-latched UVA-3GAM UVA-3GAD UVA-3GA
The Contactors CV-6GA and CV-6HA have the same outline
and mounting dimensions, as well as dual voltage ratings Latched UVA-3GAML UVA-3GADL UVA-3GAL
(3.6/7.2kV). 400A 40kA Non-latched UVA-3HAM UVA-3HAD UVA-3HA
Conformity to Industrial Standard
Conforming to international standards such as IEC, BS, AS Latched UVA-3HAML UVA-3HADL UVA-3HAL
and JEM, being certified by class NK and TUV Toshiba 6.6kV 200A 40kA Non-latched UVA-6GAM UVA-6GAD UVA-6GA
Vacuum Contactors can be used widely all over the world.
Latched UVA-6GAML UVA-6GADL UVA-6GAL
400A 40kA Non-latched UVA-6HAM UVA-6HAD UVA-6HA
Latched UVA-6HAML UVA-6HADL UVA-6HAL
Excellent Breaking Performance Bushing 3.3kV 200A 40kA Non-latched UVA-3GAM1 UVA-3GAD1
Since the higher interrupting capacity and short-time
Latched UVA-3GAML1 UVA-3GADL1
withstand capability, Toshiba Vacuum Contactors are
appropriate to fuse combination for large capacity load, 400A 40kA Non-latched UVA-3HAM1 UVA-3HAD1
and to high-speed breaking.
Low Power Consumption
The control device adopts an IC circuit, the control voltage Latched UVA-3HAML1 UVA-3HADL1
either AC or DC can be easily changed by switches in the 6.6kV 200A 40kA Non-latched UVA-6GAM1 UVA-6GAD1
electronic circuit board without changing the coil and/or
other parts. Since the economizing resistors are Latched UVA-6GAML1 UVA-6GADL1
eliminated, the power consumption in holding condition
has been reduced.
400A 40kA Non-latched UVA-6HAM1 UVA-6HAD1
Latched UVA-6HAML1 UVA-6HADL1

1 2
RATINGS AND SPECIFICATIONS RATINGS AND SPECIFICATIONS
Type CV Type UVA
Standard 6GA 6HA 6GAL 6HAL Manual type 3GAM 3HAM 6GAM 6HAM
From Non-Latched
Upper front terminal - 6HA-2 - 6HAL-2 Handle type 3GAD 3HAD 6GAD 6HAD
Operating Mechanism Non-Latched Latched Form
Manual type 3GAML 3HAML 6GAML 6HAML
Rated Voltage (Ur) 3.6/7.2kV Latched
Handle type 3GADL 3HADL 6GADL 6HADL
Rated Operational Current (le) 200A 400A 200A 400A
Rated Insulation Voltage 3.6kV 7.2kV
Thermal Current (lth) 300A 450A 300A 450A
Rated Frequency 50/60Hz Rated Operational Voltage 3.3kV 6.6kV
Rated Short-time Withstand Current (lk) 6300A- 1s 6300A- 2s 6300A- 1s 6300A- 2s Rated Operational Current 200A 400A 200A 400A
Rated peak Withstand Current (lp) 15.8kA Rated Frequency 50/60Hz
Short-circuit Making and Breaking Current 6300A Rated Interrupting Current (With power Fuses) 40kA
(Duty) "O" - 3min. - "CO" -3min. - "CO"
Rated Power Frequency Withstand Voltage 16kV-1min. 22kV-1min.
Making Current (100times) AC4 2000A 4000A 2000A 4000A Insulation Level Impulse Withstand Voltage 45kV 60kV
Breaking Current (25times) AC4 1600A 3200A 1600A 3200A
Closing 100-110V, 115-120, 200-220, 230-240VAC/100-110,200-220VDC
Withstand Overload Current 1200A-30s 2400A-30s 1200A-30s 2400A-30s Rated Control Voltage
6 times of le - 30s 4000A-4s 4000A-12s 4000A-4s 4000A-12s Tripping 100-110V, 200-220VDC
15 times of le - 1s 6300A-1s 6300A-2s 6300A-1s 6300A-2s Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage
Coordination with Current-limiting Fuses Prospective Short-circuit Current 40kA Operating Current Closing 4.5A(Peak)
Cut-off Current (Peak) 55kA 85kA 55kA 85kA (at AC100V) Holding/Tripping 0.1A(Average Holding) / 4.0A(Peak Tripping)
Rated Power Frequency Withstand Voltage 22kV-1min. *1 Closing Time 65 - 80ms
Insulation Level Impulse Withstand Voltage 60kV Opening Time 20 - 30ms
Switching frequency (AC3) 1200 op. cycles/hr 300 op. cycles/hr Contact arrangement Non-Latched 3NO-2NC, Latched 2NO-2NC
Mechanical Life 2.5mill. 0.25mill.
Endurance Operational voltage Max. 480V, Min. 48V
Electrical Life (AC3) 0.25mill. 0.25mill.
Ratings of Auxiliary Contact Thermal current 10A
Closing 100-110, 115-120, 200-220, 230-240VAC/100-110, 200-220VDC
Rated Control Voltage AC capacity 700VA(PF. 0.35)
Tripping 24, 32, 48, 100-110, 200-220VDC
Allowable Control Voltage Fluctuation 85% to 110% of the rated control voltage DC capacity 60W(L/R 150ms)

Operating Current Closing 4.5A (Peak) Installation Floor Mount Installation


(at 100V) Holding/Tripping 0.1A (Average) 4.0A (Peak) Altitude 1000m or lower
Closing Time 65 - 80ms Ambient air temperature -5 to 40OC
Application Condition
Opening Time 20 - 30ms Relative humidity 45 to 85%
Contact arrangement 3NO-3NC 2NO-2NC Vibration Max. 20Hz 1G
Operational voltage Max. 480V, Min. 48V
Shock Max. 30G
Ratings of Auxiliary Contact Thermal Current 10A
AC Capacity 700VA (PF. 0.35) Main and Earthing circuit ; Automatic connection
Connection Method Control circuit ; Manual plug connection
DC Capacity 60W (L/R 150ms)
Installation Floor Mount Vertical Installation 2 Positions
Position
Altitude 1000m or lower "Connected" and "Disconnected"
Ambient air temperature -5 to 40OC Shutter Provision Insulation shutter provided
Application Condition
Relative humidity 45 to 85% Control Wire (color and size) Yellow, 1.25mm2
Vibration Max. 20Hz 1G Motor (kW) 750 1500 1500 3000
Shock Max. 30G
Maximum load Transformer (kVA) 1000 2000 2000 4000
Motor (kW) 750/1500 1500/3000 750/1500 1500/3000
Capacitor (kvar) 1000 2000 2000 2000
Maximum Load Transformer (kVA) 1000/2000 2000/4000 1000/2000 2000/4000
Withdrawable portion 70kg 70kg 75kg 75kg
Capacitor (kvar) 1000/2000 2000/2000 1000/2000 2000/2000 Approx, Weight
Weight 19.0kg 19.5kg 19.5kg 20.0kg Total 90kg 90kg 95kg 95kg

Standard IEC60470 (2000) IEC60470


Standard
*2 JEM1167 (1990) JEM1225 (1986)
*1 : Special withstand voltage (32kV-1min.) will be supplied by request.
*2 : CE marking can be available by request.

3 4
APPLICATION AND SELECTION NOTICE FOR APPLICATION
OPERATING COIL EXCITATION CAPACITOR APPLICATION
The current limiting fuses shall be combined for capacitor switching application.
Non-Latched The series reactor shall be connected, especially back-to-back application.
Mainly applied to frequent switching operation such as motor.
(Continuous Excitation) Service life of capacitor switching
The switching, opening and closing, of capacitor produces severe condition for contactor, such as high
frequency inrush current and interpole recovery voltage higher than twice of normal voltage.
Latched Mainly applied to non-frequent switching operation and/or to the important load which
(Instantaneous Excitation) The criteria of maximum number of capacitor switching are shown in the figure below. The vacuum interrupters should be
require to be contact closed even by power loss.
replaced when the number of switching operations reached to point shown in figure.

PROTECTION COORDINATION
The protection coordination with upper/lower stream relay shall be evaluated by considering total system and load
characteristics.
The single-phase protection shall be performed which may be occurred by power fuses.
(Apply 2E-relay or fuse blown detection which is provided on combination unit as standard.) 100

APPLICATION GUIDE TO SURGE


No surge protection is required except for special application, however the insulation coordination shall be evaluated by following 50

Switching Life
(Thousand Op.)
table. 40

30
Load Protection Notice
20
The surge suppressor shall be installed for machine rated at
55kW or below, and/or be subject to inching operation.
The surge suppressor shall be installed between starting
Rotating Machine Not required contactor and autotransformer for machine started by 10
autotransformer.
The suppressor shall be installed for machine which has inferior
insulation. 20 30 50 100 200 300 400

S witc h in g Cu r r e n t ( A )
The surge arrester shall be installed for transformer rated at
Dry-type Transformer Not required
150kVA or below and exciting inrush is interrupted.

The installation of suppressor and insulation coordination shall Fig. 1 Capacitor Switching Life (with 6% reactor)
Oil-immersed Transformer Not required be evaluated when the low surge level apparatus are connected
on secondary circuit of transformer.

Capacitor Not required Refer to the clause for capacitor application.


TERMINAL CONNECTION
Either terminals, upper or lower, can be used for power or load side on contactor.
The upper terminals shall be connected to power side on combination unit for the protection coordination.
The surge suppressor is composed of capacitor and series resistor, and is one of the most excellent protection mediums. The
device features suppression as well as a decrease of surge generation. Particularly being free from limitation on the number
of operating times, this device is suitable for protecting motors and transformer required performing frequent operations.
CONTROL TRANSFORMER
The contactor can be operated with following burden of control transformer.
The surge arrester has no effect of suppressing the surge generation, this suppresses overvoltage to within a fixed level.

Type Form (Contactor) Control Transformer VT


CV-6GA(L), 6HA(L) 400VA or more 100VA 10P10

5 6
OUTLINE DIMENSIONS OPERATING CIRCUITS
RECOMMENDED
30 368 30 PARTITION 202 Non-latched type
DISTANCE
13 69 115 115 69 31 2 15 High-Voltage Vacuum Contactors P or R
30

E OFF
The typical operating circuit is shown in Fig. 4 indicating REMOTE
SWITCH
E

type CV-6GA/6HA contactor. E E ON *2


*1 VMC
FRONT COVER 30 Make sure to use the "NO" contacts of quick operating 4
16 15 14 13 12 11
4 COS

100-110VAC/DC
200-220VAC/DC
3 1 4

6
relay (4) self-holding circuit. Do not use the "NO" START
INTERLOCK
5
INTERRUPTERS
auxiliary contacts of vacuum contactor, this may cause STOP
INTERLOCK DU
MAIN CIRCUIT TERMINALS

124
26 25 24 23 22 21
12 DIA-6 HOLES the welding of main contacts when the start (ON) button 52CC 52CC
10
2E-RY
INDICATOR is pushed incompletely. (refer to the marked 1 in figure) 6
GL RL
4
400

2
Make sure to switch the closing coil on DC side. Should

371
N or T

6
OFF 30
ON TRIP LEVER the coil be switched on AC side, a discharging circuit will VMC : Vacuum contactor
MAIN CIRCUIT TERMINALS 52CC : Closing coil
TRIPPING HOLE be formed by rectifiers against coil, resulting in prolonged

217
DU : Drive unit
87654321

(DIA 9)
180

4 : Control relay
DIA 15

(REAR) opening time and lowered breaking performance.


128

AUXILIARY 345-+ 1
SWITCH (refer to the marked 2 in figure) Fig. 4 Non-latched type operating circuit
166 179

195-+ 1
13 300 60 10 195 10
166 134
18 373 21 219 11 DIA - 4 HOLES
Latched type
EARTHING CONTROL MOUNTING HOLES 300 +-1
TERMINAL TERMINAL
COUNTER LATCH MECHANISM (FRONT) High-Voltage Vacuum Contactors REMOTE SWITCH
(M8 BOLT)
(OPTION) (FOR LATCHED TYPE) DETAIL OF MOUNTING The typical operating circuit is shown in Fig. 5 specifying P
HOLES (TOP VIEW)
type CV-6GAL/6HAL contactor. E ON E E E OFF 2E-RY

Fig. 2 Types CV-6GA ( L ) /CV-6HA ( L )


The electrical trip free circuit must be furnished in control COS VMC
START 4 11 15 14 13 12
INTERLOCK
circuit. (outside of contactor) 3 1 4

100-110VDC
200-220VDC
A stable DC power source such as battery is 16
5

RECOMMENDED 202 DU
PARTITION recommended for control circuit. If the DC power source 26
21
25 24 23 22
30 368 30 DISTANCE 60 13
D 52CC 52CC 52TC

13 69 115 115 69 31 2 is not available, employ the AC closing and capacitor trip 6
4
GL RL
15 device for tripping.
2 7
30

N
MAIN CIRCUIT Make sure to use the "NO" auxiliary contacts (11-21) of
VMC : Vacuum contactor
TERMINALS 52CC : Closing coil
vacuum contactor in trip circuit, and "NC" auxiliary 52TC : Trip coil
DU : Drive unit
FRONT COVER 30 contacts (16-26) of vacuum contactor for control relay 4 : Control relay

INTERRUPTERS circuit.
6

MAIN CIRCUIT TERMINALS Fig. 5 Latched type operating circuit


12 DIA-3 HOLES
124

M10 SCREW
10 30
INDICATOR
400

371
6

OFF
ON TRIP LEVER (REAR)
(FOR LATCHED TYPE)
345 -+ 1
217

TRIPPING HOLE
87654321
180

DIA-15

(DIA 9) 166 179 3


128

AUXILIARY SWITCH
4
195-+ 1

10
166 134 1 TIMER
11 DIA-4 HOLES 5
13 300 60 10 195 10 2 52
300 -+ 1 CC
18 373 21 215 OSCILLATION POWER
(FRONT) 6
EARTHING CONTROL LATCH MECHANISM MOUNTING HOLES DETAIL OF MOUNTING SWITCHING
TERMINAL TERMINAL (FOR LATCHED TYPE) HOLES (TOP VIEW)
(M8 BOLT)

Fig. 3 Types CV-6HA ( L ) -2

Fig. 6 Configuration of Drive -Unit

7 8
OUTLINE DIMENSIONS

RECOMMENDED REQUIRED MINIMUM


PARTITION INSULATION DISTANCE
RECOMMENDED REQUIRED MINIMUM
PARTITION INSULATION DISTANCE. INSULATION SHUTTER DISTANCE LIFTING HOLES INSULATION SHUTTER
DISTANCE DISCONNECTED CONNECTED (20 DIA-2 HOLES) POWER SOURCE
LIFTING HOLES POSITION POSITION PRIMARY CONDUCTORS
DISCONNECTED CONNECTED POWER SOURCE 3-M12 SCREWS, DEPTH 20
(20 DIA-2 HOLES) TERMINALS 10 115 125 125 115 10 100 588 116
POSITION POSITION
555 139 13 DIA-3 HOLES 90
10 115 125 125 115 10 100
12 466 12 METAL 130 130

10
10 COVER
125 125 5 DIA 36
METAL
COVER METAL

107 45
15 30 HANDLE (PF) PARTITION
(PF)

6
CONTROL 18 DIA 25
INDICATOR
CONNECTOR 48

264
HANDLE (VMC)

154
INDICATOR

505
(VMC) METAL
605

535

45 107
535

535
CONTROL COUNTER PARTITION
CONNECTOR COUNTER (OPTION) 33

6
(OPTION) 33

293
15 30 18
293

257
91

204
186

148
186

124
114
148

104
124
114

104

60
60

19
METAL
19

412
130 412 LOCK LEVER PARTITION
LOCK LEVER 41 103 41 103 MANUAL TRIP LEVER 130 472
145 155 38 527 235 472 145 155 (LATCHED TYPE) 38 527 235 10 489
MANUAL TRIP LEVER MOUNTING HOLES
MOUNTING HOLES 191 192 (LATCHED TYPE) 800 LOAD TERMINALS 191 192 810
20 210 210 20 13 DIA-3 HOLES
EARTHING TERMINAL 20 210 210 20
246 246 13 DIA-4 MOUNTING HOLES (VT) (8mm 2 ) 13DIA-4MOUNTING HOLES (VT) LOAD PRIMARY CONDUCTORS EARTHING TERMINAL
247 247 3-M12 SCREWS, DEPTH 20 (8mm 2 )

Fig. 7 Types UVA-3GAM(L)/UVA-3HAM(L) UVA-6GAM(L)/UVA-6HAM(L) Fig. 9 Types UVA-3GAM(L)1/UVA-3HAM(L)1 UVA-6GAM(L)1/UVA-6HAM(L)1

REQUIRED MINIMUM REQUIRED MINIMUM


INSULATION DISTANCE RECOMMENDED INSULATION DISTANCE
INSULATION SHUTTER PARTITION LIFTING HOLES
LIFTING HOLES DISTANCE (20 DIA-2 HOLES) INSULATION SHUTTER
RECOMMENDED DISCONNECTED CONNECTED
PARTITION DISCONNECTED CONNECTED (20 DIA-2 HOLES) POWER SOURCE
POSITION POSITION PRIMARY CONDUCTORS
DISTANCE POSITION POSITION 10 115 125 125 115 10 100 588 116
10 115 125 125 115 10 100 555 139 POWER SOURCE 3-M12 SCREWS, DEPTH 20
TERMINALS 90
13 DIA-3 HOLES METAL
METAL COVER 130 130
12 466 12

10
COVER
10

5 DIA 36
125 125

107 45
15 HANDLE METAL
HANDLE 30 INDICATOR (PF) PARTITION
INDICATOR (PF)
6

18 DIA 25
CONTROL 48
CONTROL

264
CONNECTOR COUNTER
CONNECTOR COUNTER (VMC)
154

605
(OPTION) (VMC) (OPTION) METAL
605

535

45 107
PARTITION
535

535

139
139
6

293 18
30
293

15 91

204
257

170
186

164
170
186

124

20
114
164

104
124

20
114

104

19
130 METAL 412
19

103
103 130 412 PARTITION
145 155 DRAWOUT 8 38 527 235 472
DRAWOUT 8 38 527 235 LOAD 472
145 155 TERMINALS MOUNTING HOLES MECHANISM 489
MECHANISM 191 192 25 808 10
MOUNTING HOLES 191 192 25 808 13 DIA-3 HOLES
DRAWOUT EARTHING TERMINAL 20 210 210 20
20 210 210 20 MECHANISM (8mm 2 ) MANUAL TRIP LEVER 13 DIA-4 MOUNTING HOLES (VT)
MANUAL TRIP LEVER 13 DIA-4 MOUNTING HOLES (VT) 252 328 EARTHING TERMINAL
252 328 (LATCHED TYPE)
(LATCHED TYPE) LOAD PRIMARY CONDUCTORS (8mm 2 )
3-M12 SCREWS, DEPTH 20

Fig. 8 Types UVA-3GAD(L)/UVA-3HAD(L) UVA-6GAD(L)/UVA-6HAD(L) Fig. 10 Types UVA-3GAD(L)1/UVA-3HAD(L)1 UVA-6GAD(L)1/UVA-6HAD(L)1

9 10
OPERATING CIRCUITS INTERLOCKS
Test The electrical and mechanical interlocks are provided How to furnish the front door with interlocks
R
L4 on Combination unit as described below to prevent
AC When performing interlocks between the handle operation
T LS2 misoperation and to ensure high safety.
L5 type unit and front door, conduct the design by adopting
2E-RY The unit can not be withdrawn from the "CONNECTED" following steps, referring to Fig. 13.
position, while the contactor is "ON".
E OFF Preparation of small door
The unit can not be inserted into the "CONNECTED"
STOP
Provide the front door with a small door for handle
INTERLOCK position, while the contactor is "ON".
operation. (approx. size 95X200)
LS2 The contactor can not be closed, unless the unit is either
E L4 L5 Interlock to prevent door opening at connected position
E E ON in the "CONNECTED" or "DISCONNECTED" position.
L8 The interlock pin in the connected position is at "B"
COS The cubicle door can not be opened, unless the unit is
4
START
position. Attach a stopper for the interlock pin to door so
4 in the "DISCONNECTED" position. (note)
Normal 4
INTERLOCK T2 T4 T6 T8 T10 T12 that the interlock pin can be clasped and the door can
Service T1 T3 T5 T7 T11 The unit can not be inserted into the "CONNECTED"
not be opened. The stopper may be installed with
Main Power Supply 1 2 3 4 5 6 7 8 9 10 11 12 position, unless the cubicle door is closed. (note)
R S T T1 T13 T12 T2 T14 T5 T17 T18 T6 T7 T8 T10 T3 T11 T4 13 14 15 16 17 18 19 20 21 22 23 24 screws for emergency door open by removing screws.
The operating handle can not be extracted,
T13 T15 T17 T19 T21 T23 Interlock to prevent handle operation at door opening
T14 T16 T18 T20 T22 T24 unless the unit is either in the "CONNECTED" or
Provide a rod on door side for interlock lever release
AUS (CONTROL CONNECTOR HOUSING) "DISCONNECTED" position.
16 15 14 13 12 11 and adjust the length of rod.
PF DU LS3 The contactor is "OFF" by inserting the operating
F VT F1 Provide the small hole (approx. 12X22) at location of
LS1 LS4 NOTE
1. LS1 is ON at the position of both handle. (Refer to Notes on page 11.)
5 26 25 24 23 22 21
ON-OFF indication for confirmation of unit position.
connected and disconnected. The unit can be padlocked at the "CONNECTED" and
52CC 52CC 2. LS2 provided only on handle operation
52 6
type, but not connected to connector "DISCONNECTED" position.
housing, is OPERATE by inserting the
handle. Make sure to open the
contactor by handle insertion.
3. LS3 operates only at the connected
U V W T19 T21 T15 T23 T24 T16 position.
T20 T22 4. LS4 indicates fuse blown.
(Note) The f r ont door must be adj ust ed w hen t he Symbol marked indicate for handle operation type
Load
(Fuse blown detector) i nt er l ocks ar e em pl oyed.
Fig. 11 Non-latched type (AC operation) 8 Stopper

8 - 10
Parts Position
Interlock Shaft Arm Name Plate Inserting 2 Interlock Pin (DIA 8)
P Draw-out Position Position Position for ON-OFF Direction of
DC Position Indicator Handle

23
N L4
E ON E LS2 2E Disconnected Position "A" "B" "D" OFF "B"
E E OFF 2EX
L8
COS Connected Position "B" "C" "E" ON "C"

Small Door 3 Shaft


START
INTERLOCK
95 5 Interlock Lever
2EX 1 Rod
2EX 18 53
8 9 Rod Support
Hole
4
4 Name Plate for 5 Interlock Lever
ON-OFF Indication 1 Rod 6 Arm
4
Shutting The Door 32 "D" "E"
2 Interlock Pin Cancels The Interlock "C"
Main Power Supply 1 Rod
Depressing

10
R S T T1 T13 T12 T3 T15 T2 T14 T6 T18 T4 T16 T7 T8 T10 T11 T5 Position 2 Interlock Pin

200
20
AUS
PF "B"
104
F VT F1 16 11 15 14 13 12
DU LS3
LS1

81

81

65
LS4

68
68

65
5 26 21 25 24 23 22
52TC
52 D 52CC 52CC
3 Shaft "A"
28 32
6 113 7 Lock Lever Cubicle Door Mounting Hole of
74
Combination Unit
Mounting Hole of Combination Unit 7 101
U V W T19 T21 T23 T24 T17
T20 T22
Load
Fig. 12 Latched type (shunt trip) Fig. 13 Withdraw mechanism and hole for handle operation type

11 12
OUTLINE DIMENSIONS OUTLINE DIMENSIONS
Double Barrel Fuses Fused Contactors
RECOMMENDED REQUIRED MINIMUM
PARTITION INSULATION DISTANCE Non-latched type UVA-3GA UVA-3HA UVA-6GA UVA-6HA
DISTANCE POWER FUSE Type Form
DISCONNECTED CONNECTED (DOUBLE BARREL) Latched type UVA-3GAL UVA-3HAL UVA-6GAL UVA-6HAL
POSITION POSITION Rated operational voltage (kV) 3.3 6.6
10 115 125 125 115 10 100 555 139
Rated operational current (A) 200 400 200 400
10
POWER SOURCE
Rated interrupting current (kA) 40 40
TERMINALS

(PF)
METAL 15
COVER (PF) REQUIRED MINIMUM LIFTING HOLES
RECOMMENDED (20 DIA-2 HOLES)
INSULATION DISTANCE

6
PARTITION POWER SOURCE
DISTANCE TERMINALS
10 115 125 125 115 10 543 (13 DIA-3 HOLES)

154
B

(VMC)
A

9 466 9

535
125 125

10
6
30
15
293

257
(PF)

6
METAL
COVER
INDICATOR 15

154
LOAD TERMINALS (VMC)

605

535
535
CONTROL COUNTER 15 30
POWER FUSE RATED FUSE SIZE A B CONNECTOR (OPTION)

294
FPG1-C50A

257
50DIA 575 645
FPG1-C60A

124
114
FPC3-M250A / C175A 85DIA 627 697

104
19
Fig. 14 Types UVA-3GAM(L)/UVA-3HAM(L) UVA-6GAM(L)/UVA-6HAM(L) 103 12 455
LOAD TERMINALS EARTHING
MOUNTING
190 190 MANUAL TRIP LEVER 479 55 (13 DIA-3 HOLES)
(LATCHED TYPE) TERMINAL
HOLES 191 192 (8mm 2 )
12 DIA-4 MOUNTING HOLES
(VT)
436
Earthing Switch
Fig. 16 Types UVA-3GA(L)/UVA-3HA(L) UVA-6GA(L)/UVA-6HA(L)
INSULATION SHUTTER
3 136 12 466 12

MOVABLE UNIT
535

DRAWOUT
MECHANISM
45 O

182

175
65
20

130 42 472
EARTHING
25 808 74 CLIPS EARTHING
DRAWOUT EARTHING
907 MECHANISM WIRE TERMINAL
(8mm 2 )
EARTHING
MECHANISM

Fig. 15 Earthing Switch Configuration

13 14
: Provided as Standard : Option upon request : Supplied : Not supplied
Contactor Combination Units Contactor Combination Units
Name of parts Manual Handle Fixed Remarks Name of parts Manual Handle Fixed Remarks
CV CV type type type
type type type
Counter Option Control wire With plug (2mm2 X 2m)
LS3 Connected position (1NO-1NC) Control test wire With plug and socket (2mm2 X 2m)
Position switch
LS7 Disconnected position (1NO) Operating handle For Handle type
Blown fuse detector LS4 1NO LC9 100/110VAC for 100-110V coil
For
Capacitor
VT (1unit) Provided only on Non-latched LC10 Latched 200/220VAC for 200-220V coil
trip device
type
Additional VT Max. 2VT CIT-10Q 100/200VAC for 100-110V coil

Partition between CR Surge suppressor NV60K304T1 (See Page 5)


Insulation barrier
power and load terminals Mechanical interlock (See Fig. 20)
Insulation fuse barrier For the earthing side
Shutter padlock provision Padlock not provided CONNECTOR

DIA 27
WIRE
Position padlock provision Padlock not provided INSERT SIDE 10X20.5 HOLE
DIA 6 HOLE
Earthing switch For load side cable

66

70
86

49
400 4.5 44
2000 46 24

Fig. 18 Control wire Fig. 19 Operating handle


: Supplied : Not supplied
Contactor Combination Units
Name of parts Manual Handle Fixed Remarks
CV type type type
Capacitor trip device
Wipe gauge For checking contact wear The capacitor trip device will be used for latched contactor when DC power source is not available. The device charges from
Trip rod For latched type only AC power, and supplies DC power to the trip coil at trip command. The alarm contact is provided on CIT-10Q.
Connector housing and pins Crimping tool No.720725-1
as loose parts Tyco Electronics AMP. CO. Mechanical interlock
The mechanical interlock shall be used in the
Wipe gauge reversing starter to prevent mechanically from closing CV-6GA,6HA
CV-6GAL,6HAL

The wipe gauge can be used for checking the forward and reverse contactors simultaneously.
contact wear of vacuum interrupters. Refer to the Wipe gauge The following vertical pitch interlocks are available for CV-
instruction manual for using this gauge. t 0.5 6 series contactors.
28

SHAFT (VMC)
VMC : OFF
120 OFF
ON
Vertical pitch 450mm and 550mm

O
8.8
Trip rod Trip rod
The trip rod may be used for manual tripping for
DIA 7

PITCH BETWEEN CONTACTORS


latched contactor and combination unit, however
this operation shall be maintenance purpose or 60

P
emergency case only.

400
Housing (Pins) VMC : OFF

HOUSING

128
Connector housing and pins as loose parts 136 13
These parts are for the connection of control 10 195 10 45 300 45
66

70
86

MOUNTING
HOLES 257 426
circuit in combination unit. 11 DIA -4 HOLES

46 24
Fig. 20 Outline of mechanical interlock

Fig. 17 Standard accessories

15 16
Inquiry No. : P/O No. :
Motor application Designation and type form
3.3kV 6.6kV
Applicable Quantity :
Power fuse Vacuum Standard value Standard value Vacuum Power fuse
Current
(A)
Type
Contactor
(A)
of load current
(A)
motor
(kW) of load current
(A)
Contactor
(A)
Type
Current
(A)
UVA A
Use this sheet for confirmation on each rating and specification
10 11.7 37 45 4.8 5.6
13.8 55 6.6
M25
18.8 75 9.1
22.1 90 10.5
Type UVA
M25
26.7 110 12.8 Rated operational voltage 6 : 6.6kV 3 : 3.3kV
FPC3-3X25N FPG1-6X75N
M50 32.5 132 15.1
200 38.5 160 18.4 Rated operational current G : 200A H : 400A
48 200 23.7
M100 74.1 315 36.9
Series A 1
200 M50
92.1 400 46.1 M : Manual D : Handle Bushing
102.6 450 51.3 Draw-out/in mechanism
M200 FPC3-3G25N type type type
140.9 630 70.6
FPC3-6X75N M150
171.9 750 82.1 No symbol : L : Latched
M250 178 800 89 Operating mechanism Non Latched type
195.1 900 97.6
M300
FPC3-3X25N
400 216.2 1000 108.1 FPC3-6G75N M200
type
267 1250 134.4
M350 Rated interrupting current 40kA (with power fuse) 6.3kA (without power fuse)
320.3 1500 160.2
1750 194 FPC3-6X75N M250 Non Latched Operating voltage AC/DC100-110V AC/DC200-220V
2000 217 type others (specify : V)
400
2500 270
FPC3-6H75N M400 Rated
3000 322 Closing voltage AC/DC100-110V AC/DC200-220V
control
Notes 1. Full-load current represents the average value of Toshiba Motors (2, 4, 6 poles). Check the motor characteristics. Latched others (specify : V)
2. The standard for power fuse selection is : full-load current X 6, 5 second-2 times. voltage
type Tripping voltage DC100-110V DC200-220V
Transformer application others (specify : V)
3.3kV
Applicable
6.6kV Refer to Fuse selection table. Quantity (set No.) shall be scribed in parentheses ( ).
Power fuse Vacuum Standard value Standard value Vacuum Power fuse
transformer Three-phase Single-phase Without power fuse
Current Contactor of load current (kVA) of load current Contactor Current
Type (A) (A) Type
(A) (A) (A) (A)
5.3 30 2.7
T20 T30 T40 T50 T60 T75
T20
8.8 50 4.4 FPG1 (3.3/6.6kV) C15 C20 C25 C40 C50 C60 2 X C50 2 X C60
13.2 75 6.6

FPG1-6X75N
17.5 100 8.8
T20 - - - M25 M40 M50
T30 26.3 150 13.2
Quantity (set No.) M25 M50 M100
T50 35 200 17.5
FPG1-6X75N
T60 200 43.8 250 21.9
T30 Power fuse T50 T100 T150 M200 M250 M300 M350 2 X M250
T75 54.5 300 26.3

T150 FPC3-3X25N
70 400 35
200
T50
selection FPC3 (3.3kV) C40 C75 C100 T225 - - T350 -
87.5 500 43.8
109 600 54.5 T75
C150 C175 C200 C275 2 X C175
T225 FPC3-3G25N
131.2 750 65.7 Quantity (set No.) M150 M200 M250
M250 175 1000 87.5 FPC3-6X75N T175
M300
FPC3-3X25N
218.7 (1250) 109.4
FPC3-6G75N T225
T175 T225 - M400
T350 400 263 1500 131.2
FPC3 (6.6kV) C100 C150 C175 T400
2 X M250 350 2000 175 FPC3-6X75N M250
2500 218.7 -
3000 263 400 FPC3-6H75N T400
4000 350 Quantity (set No.)
Notes 1. The standard for power fuse selection is : full-load current X 10, 0.1 second. 1 X VT 3300/110V 3300/220V
2. 2 X M : double barrel/phase.
VT 2 X VT 6600/110V 6600/220V
Capacitor application (with series reactor) Not required Others (specify : V)
3.3kV 6.6kV LS3 Connected position switch UVA type : standard
Power fuse Applicable Power fuse
Vacuum Standard value Standard value Vacuum
Current Contactor of load current
capacitor
of load current Contactor Current
Limit switch LS7 Disconnected position switch UVA type : option
Type (kvar) Type
(A) (A) (A) (A) (A) (A) LS4 Blown fuse detector UVA type : standard
5.3 30 2.7
C15 8.8 50 4.4
C15
Insulation barrier between fuses
13.2 75 6.6 Insulation fixing barrier
C40
17.5 100 8.8 Standard accessories Insulation shutter
26.3 150 13.2
C50
FPG1-6X75N
35 200 17.5
Connector housing and pins as loose parts
C40
C60 200 43.8 250 21.9 FPG1-6X75N
2 X C50 55.6 300 28
Counter
200 Insulation barrier (Partition between power and load terminals)
74.2 400 37 C50
2 X C60
93 500 46.4 C60 Insulation fuse barrier for the earth (Phase to earth)
C150 FPC3-3G25N
111 600 55.6 2 X C50 Options Shutter padlock provision
148 800 74.2
C175 185 1000 97
2 X C60 Position padlock provision
C200 232 1250 116 C150 Earthing switch for load side cable
FPC3-3X25N
C275 400 278 1500 139 FPC3-6X75N
C175
2 X C175 372 2000 185
Notes 1. The standard for power fuse selection is : full-load current X 5, 0.1 second.
Accessories Please refer to page 16 to specify the quantities each
2. 2 X C : double barrel/phase.

17 18