You are on page 1of 7

2017 IEEE Calcutta Conference (CALCON)

Investigate the impact of Smart Grid Stability


Analysis on Synchronous Generator

Shouvik kumar Samanta (Research scholar) Chandan Kumar Chanda (Professor)


Department of electrical engineering Department of electrical engineering
IIEST, Shibpur IIEST, Shibpur
Howrah, India Howrah, India
e-mail: samanta_b007@yahoo.co.in e-mail: ckc_math@yahoo.com

Abstract² Nowadays, intelligence electrical automation of information and communication technologies[3](ICTS) are
distribution network has been navigating the development of increasingly getting deployed in the system to deliver the
future power system like as smart grid which could lead through requirement. As such deployments raise the complexity and
the modelled network being changed and this will change the system operational challenges and the 21st century
certainly the electric network operations. Smarter intelligent grid
electricity grid has to embrace these challenges through
is an adequately advance concept of future power system which
coordinates electricity as well as communication in system planning, design, control and operation. In the time-scale
network that provides digital information with time on real time operation ensuring the stability and security of the system be
operation in power network for the operator and finally the the most important tasks.
consumer. Small-scale or large-scale integration with distributed In recent years, The WAMS and ICT propound very effectual
generation can provide noteworthy influence on power system means of delivered these objectives [4, 5]. Everything about
stability in respect of the changes through rotor angle, voltage the stability on power system has been occurred in system due
and frequency stability. Voltage control and reactive power to utmost concern of system operation. Modern electrical
compensation are fundamental constrain to frame the grid smart power system have been developed large complexity
enhance smarter. A novel voltage stability index is represented to
network for the sake of increasing interconnections, tie-lines
determine the critical lines of a smart power grid. Furthermore,
comparative simulation between existing models and power flow of extra high voltage and large generating units installation
depended model are researched on the IEEE 9-bus standard etc. Transient stability [6] is the capability of power system
system. The simulation results exhibit that the proposed smart maintaining synchronism subjected to a heavy transient
grid model and different indexes are more effective on generator disturbance when fault on transmission lines, large load loss or
due to smart grid stability analysis. In this paper concisely sudden generation loss. The response of a system depend such
summarize the concept of physical model, calculation technique disturbances i.e. large outing of rotor angle of generator, bus
and application possibilities of generator stability which are voltages, power flows and other system constrains. Existing
described in detail in the references. Therefore, it is essential to components and systems must be re-engineered and
further develop models with considered indicator for stability
encapsulated to be congruent with new innovations and
study is determined by analyzing Smart Grid voltage magnitude,
frequency and power angle, so as to fulfil the new circumstances standards. The most significant challenges of interoperability
and reduce potential of wide scale blackouts. are, and will going on to be interoperable with the installed
legacy systems while addressing interfaces between new and
yet to be established devices through service oriented
Keywords— smart grid , power model; synchronous generator; Architecture[7](SOA) approach and domains constituting in
review the steady state smart grid voltage; IEEE 9 bus; review of the fault-dependent region of attraction locally around the
transient smart grid stability; power angle ; dqi/dvi index. controlled unstable equilibrium points[8,9]. The transient
I. INTRODUCTION stability entails to be enhanced the optimization of system
load ability where the system can be closer to its thermal
Electrical energy system all over the globe has been limits. In this section describes some of these widely accepted
undergoing unprecedented transitions level in recent times. principle characteristics that will be the basis for the theory
Primarily the transitions are operated by the requirement of which has been studied intensively in solving practical
renew the developing electrical infrastructure integrating with problems of large-scale complex power system. A power grid
low-carbon intermittent energy sources and to fulfil enriched has evolved into the most complex human-made systems.
power consumption with new kinds of demands as such smart According to recent research, it can be described as small-
home, electric transport and business ensuring the security [1] world network [10] which is highly clustered. In other words,
of supply. Several validating technologies for example as wide although many nodes are not neighbours of one another in the
area measurements [2](WAMS), power electronics and the

978-1-5386-3745-6/17/$31.00 ©2017 IEEE 241


2017 IEEE Calcutta Conference (CALCON)

network, one can be reached from others by only a few steps till the fault is removed. If rotor angle oscillate around into the
[11, 12]. As regards, this structure in power system can final position and angular speed change during transient
maintain electrically short distance between generators and condition increasing then system has no way to come at its
loads even though the size of grid is very large. This may final position and machines loose synchronism. Power flow
imply that the transmission capacity of the power network study objective has investigated through complete voltage
could reduce mostly when a failure happens through these magnitude and angle information for any bus with specified
paths. Presently, most of the research is focused on time in the power system at specified load, generator real
topological structure in smart grid network. From graph theory power and voltage conditions. In this paper efficient method to
eliminate troublesomeness has been illustrated to viable way to
studies, indexes as well as methodologies as such degree of
control resilient system with high accuracy operation.
distribution, shortest path and diameter are broadly used to
determine the vulnerable lines in power grid networks. The B. Traditional ideological structure model :
cascaded failures mechanism has been explained on these The power grid consist certain number buses,
fundamental concepts, in Ref. [13] and a power flow based generators, transformers and transmission lines etc.. Power
model of cascaded failure was proposed. Moreover, based on grid system based ideology have N no of buses and R no of
topology and load distribution, are proposed two criteria to generators and 2(N-1)-(R-1) unknowns. Due to calculate the
point out the critical lines in Ref. [14, 15]. The results explain 2(N-1)-(R-1) unknowns, here must be 2(N-1)-(R-1) equations
how to OLQN DQG LWV ORFDWLRQ FDQ DIIHFW WKH QHWZRUN¶V in which cannot produce any new unknown variables. Possible
capability. From these models, it is presumed that power flow balance power equations for any bus with regards to real
is dispatched across the least line resistance path. power and also reactive power can be expressed below. The
Consequently, the admittance is used to as weight of the lines balance equation of real power is
in a power system. Voltage Collapse, a measure of power
system performance under anomalous operating conditions, is 0 = -Pi ȈʜViʜʜVKʜ( GiK &RVșiK + BiK 6LQșiK) (1)
considered in Ref. [16]. Also Globally Voltage Security based th
Where at i bus net injected power is Pi, the real component of
Indicator (VSI) concept and function of SVC on its in
ith row as well as kth column in Y bus matrix is Gik, the
Longitudinal Power Supply Systems (LPSS) based model is imaginary component of ith row as well as kth column in Y bus
illustrated by Dey, Chanda and Chakraborty in Ref. [17]. matrix is Bik and ș ik is voltage angle difference among the ith
Several critical power system features are included in Ref. bus and kth bus. The balance equation of reactive power is
[18@VXFKDV.LUFKKRII¶V/DZVDQGSRZHUDQJOHDQGWKXVWKLV
model can have a closer approximation to a real power grid. 0 = -Qi ȈʜViʜʜVKʜ( GiK 6LQșiK - BiK &RVșiK) (2)
Most of the work just analyses the power system Where Qi is net injected reactive power at bus i.
considering with non linier system equation based algorithms
from the ‡™–‘ ƒ’Š•‘ theory. The power is controlled by
the generation and load distribution. Thus the power flow
always has a direction. Actually, the power flows from the
generation rich side to the load rich side through parallel paths
determined by complex interaction of all factors which can be
noticed by power flow analysis. As far as our knowledge, no
proper analyses have studied in terms of different flow
features and directions together. With this consideration, the
main contribution in this paper is to improve a new model and
aim to analyze the smart grid stability on grid which
approaches to analysis the generators voltages, currents, rotor
angles and speeds etc. Firstly, time bound power flow based
model is proposed. This model considers more power system
features compared with previous ones. Consequently, it is a
closer approximation with the real power grid. Higher value
stability index ranking among the lines are considered to have
less vandalism to power grid when degree of weakness [19] of
bus is lesser. Fig. 1. IEEE 9 Bus Electrical Model.

II. PROBLEM FORMULATION ON TOPOLOGICAL MODEL III. THE PROPOSED SOLUTION FOR SYSTEM MODEL :
A. Proposed Problem on topological model: A. Electrical Power Based Intelligent Flow Smart model:
System instability occurs when fault may lead the system The intelligent analytical model explicates the physical
unbalanced or transient condition or the machine losing out of
structure and complex connections of the system. However, a
synchronism. Power flow analysis should be done to examine
the both stability of the power system at certain conditions. If power grid has several electrical features like voltage and
the system collapse, the perturbation oscillate the whole system current which can affect the operation of the whole system.
Hence, based on the physical model, electrical power model is

242
2017 IEEE Calcutta Conference (CALCON)

upgraded. The most renowned technique i.e. Newton Raphson generation to steady state smart grid voltage. Concerning
method [20] at starting all unknown variables have initial steady state smart grid voltage profile before participation of
guesses. Unknown variables i.e. voltage amplitude and angle G I, G II and G III, it is presumed that bus voltage of the entire
of load buses along with voltage angle of generator buses. system in all case studies remain fixed at 1 p.u. Voltage
Now, Taylor series is considered neglecting the terms with variation between maximum and minimum level can be
higher order for each power balance equations. The linear permitted within ±5% from the nominal voltage. Moreover,
system equations are expressed as below, the steady state smart stability profile index is observed for all
buses succeeding participation G I, G II and G III and
οɅ ο tabulated result is presented in Table 3.
ฬ ฬ ൌ െ ିଵ ฬ ฬ (3)
οȁȁ ο

:KHUH ¨3 DQG ¨4 DUH FDOOHG WKH active & reactive power D. Transient Smart Grid stability Analysis :
mismatch equations. Now J is known as Jacobian matrix of Steady state profile response of smart grid through coupling of
partial derivative form. generator to the network has been examined. This illustrates
 that steady state voltage profile of smart grid is laying in
பο୔ பο୔ between 0.945 p.u. to 1.045 p.u. with acceptable limit. Though
ப஘ பȁ୚ȁ this situation cannot safe the system to be stable if a large
 αቮபο୕ பο୕
ቮ (4) perturbation occurs on it. So there is critical to justify the
ப஘ பȁ୚ȁ transient [21] smart grid stability. Study of the transient
The linearized system equations is elucidated to check the stability examines the system response during fault occurrence
next guess of (m+1) based on voltage angles and magnitude when generator before and after participation in smart grid. In
șm+1 șm ǻș (5) stability study the considered indicator is noted by analyzing
voltage magnitude, frequency and power angle of smart grid.
and ȁȁ m+1 = ȁȁP ǻȁȁ (6)
The procedures continue until a system is getting end status. A ௗ௤೔
normal stopping condition is terminated if the mismatch E. Stability index :
equations norms are under the specified tolerance. ௗ௩೔
It is seen that at constant frequency of operation and constant
B. Newton Raphson methods algorithm consists of the terminal voltages, at any constant power input from the
following steps: ௗ௉
turbine, the critical steady state stability occurs when = 0.
1. Declare variables. ௗஔ
2. Set maximum number of iterations to perform. If in nodal point unbounded voltage is formed, it is caused as
3. Set tolerance to small value. (e.g. 1.0e-6) voltage instability [22] i.e. the capacity of the system is
4. Set an initial guess. comparatively exceed with respect of load and power
5. Set the counter of the number of iterations to zero. mismatch is created. The wVi index [23] is define by the two
6. Begin newton Raphson loop. w Qi
a. Find next guess via equation reactive powers must be equal to each other at equilibrium that
new root = root fnct(root)/fnct prime(root) means source & load side both.
b. If absolute value of fnct(new root) is less than tolerance,
then exit Newton Raphson loop. Condition for stability:
c. Increment the count of the number of iterations.
d. If we had the exceeded the maximum number of ୢሺ୕ೄ ି୕ಽ ሻ
൏ Ͳ‘”
ୢ୕ೄ
൏
ୢ୕ಽ
(7)
iterations, then exit Newton Raphson loop. ௗ௏ ௗ௏ ௗ௏
End the Newton Raphson loop.
7. If root was not found in maximum number of iterations, wQi implies degree of weakness in the ith bus. If wQi being
then warn to the terminal. w Vi w Vi
8. Write to terminal the value of root and number of
high, wVi became low that indicates minimum change in ȁ୧ ȁ
iterations performed.
w Qi
C. Steady State Smart Grid Voltage Analysis :
, reactive power Q level of the bus will vary. So wQi being
In advance power system network with integrated distributed w Vi
generation provide the steady state smart grid voltage th
higher, degree of weakness of i bus becomes lesser.
configuration improvement. However, fluctuating voltage and
its limit violation during the participation of distributed
generation could appear as large perturbation which impact on IV. THE SMART POWER GRID MODEL :
network transient stability profile. For this reason, Power
It is considered as proposed electrical power flow model
System Operators (i.e. PSO) is essential to verify worst
[24] on IEEE 9 bus test system. Therefore smart power model
situation. This part instructs the significance of distributed

243
2017 IEEE Calcutta Conference (CALCON)

must have multiple sources and multiple sinks which are to resolute the solution. When a fault occurs at bus 6 and each
denoted by nodes. line runs for five seconds at setting step time ' t with 0.0010
sec. Solution precession for the initial LF is 0.0001000000.
Each contingency data is noted in which is taken one steady
state data before the fault arises and 03 sampled data obtained
for five sec. duration after the fault occurs. From the ˜9L˜_4L|
table we investigate that the bus no.7-2 is the weakest bus in
the above IEEE 9 bus test system. The outcomes from
theoretically the test system indicate that system approaches
that collapse point to the generator 2 most severely. The
results from practically by simulation the test system indicate
that system approaches that collapse point to the generator 2
most severely hence prove.
Case- I:
Fig. 2. Electrical Power Active Flow Model of the IEEE 9 Bus System.

V. SYSTEM SIMULATION, CASE STUDY


ANALYSIS & RESULTS
This part presents general overview of various event
frameworks for the fact-finding and its assumption. In
pursuance of illustrating the several kinds of distributed
generator influence on smart grid have been investigated. This
analysis performs through steady state as well as transient
stability technique. The considered scenarios are as bellow:
Case 1: Steady state voltage profiles in load flow study have
been estimated employing Newton-Raphson Method to
validate voltage pattern and perhaps overloading and
convergence point.
Case 2: In short circuited condition transient stability analysis
Fig. 3. Electrical Load Flow Model on IEEE 9 Bus System.
has conducted notably when G I, G II and G III are integrated
into the smart grid. The components i.e. frequency, voltage
and power angle are being measured. Case-II & III.
Case 3: In the assessment of transient stability was executed
particularly when perturbation or fault occurs in the grid
system. The network parameters are estimated by frequency,
voltage and power angle.

I. The objective of standard system bus model is to power


flow of active & Reactive through transmission line with
specified thermal limit. The computation with load flow
equation is done by virtue of Newton Raphson technique
which has taken data as initial conditions and the rotor angle.
We consider non-linear numerical technique in the simulation
process to solve the IEEE 9 bus system load flow which
indicated the direction among buses & generator to or from
load with simulated value. A new technique approach to check
the power matching between generators to load shown in the
fig.3. It resolves the smart power network through normal Fig. 4. Short Circuit Simulation data on 0.2 sec on IEEE 9 Bus System.
steady-state operation.

II. When the fault occur in smart grid, transient stability TABLE I. DATA FOR BUS VOLTAGE
assessment was observed particularly where G I, G II and G
III are integrated into Smart Grid.
Bus V1 V2 V3 V4 V5 V6 V7 V8 V9
Voltage         
III. In next context of the scenario there have some complexity ͳͺ ͳ͸Ǥͷ ͳ͵Ǥͺ ʹ͵Ͳ ʹ͵Ͳ ʹ͵Ͳ ʹ͵Ͳ ʹ͵Ͳ ʹ͵Ͳ
(KV)
in that Process i.e. short circuit analysis from fig.4, because
simulation on the Electrical Transient Analyzer program helps

244
2017 IEEE Calcutta Conference (CALCON)

TABLE II. THE TYPES OF BUSES

Sl. Type of Buses No. of Total


No Buses
1 Swing bus 1
2 V-control bus 2 9
3 Load bus 6

wVi
TABLE III. INDEX TABLE FOR SYSTEM MODEL Fig. 7. Short Circuit Impedance of Generators.
w Qi
Sl. No. Bus No. ࣔࢂ࢏
ࣔȁࡽ࢏ ȁ
1 1-4 -j5.06*10 -3
2 4-6 - j1.28*10 -6
3 6-9 -j1.2047*10 -7
4 9-3 -j8.47*10 -3
5 5-4 -j1.190*10 -6
6 5-7 -j1.75*10 -8
7 Fig. 8. Electrical Power of Generators.
7-2 -j0.0121
8 7-8 -j7.51*10 -7
9 8-9 -j3.17*10 -7

Fig. 9. Speed Characteristics of Generators at fault time 0.2sec.

Fig. 5. Generator Relative Power Angle.

Fig. 10. Reactive Power of Generators.

A. For figure 5, Generator 2 in Swing mode when at fault bus


6 Power angle of Generator 1 & 3 fluctuates & that of
Fig. 6. Electrical Generator Absolute Power Angle.
JHQHUDWRU  UHPDLQV PRUH RU OHVV FRQVWDQW įǤ ‹…‡

‡‡”ƒ–‘” ʹ ‹• ‹ •™‹‰ ‘†‡ǡ ‹– ”‡ƒ‹• •–ƒ„Ž‡
™Š‡”‡ƒ• ‰‡‡”ƒ–‘” ͳ ƒ† ‰‡‡”ƒ–‘” ͵ —†‡”‰‘ Š‡ƒ˜›
•™‹‰Ǥ
B. For figure 6, Generator 2 in absolute power angle Swing
widely negative mode when at fault bus 6 and Generator
1 & 3 have positive power angle.
C. For figure 7, Reflection of generator current in terms of
synchronous impedance since we are observing bus
voltage at transient condition is constant more or less. In

245
2017 IEEE Calcutta Conference (CALCON)

generator 2 maximum impedance change occurs. [3] ³Report to NIST on the Smart Grid Interoperability Standards
Roadmap´ June 17, 2009.
Generator 1 and generator 3 almost same impedance
[4] 6HUJLR&DEHOORDQG(ULQ:&KDPEHUV´0XOWLSOHVRXUFHV6KRUWHVWSDWKV
level. Since generator2 is in swing bus mode. LQ D JHQXV J JUDSK´LQ WK $&0-SIAM Symposium on Discrete
D. For figure 8, Electrical Power of Generator 2 is peak 0.2 Algorithms (SODA), pages 89±97, 2007
sec during fault time. [5] P.-Y. Chen, S.-M. Cheng, and K.-&&KHQ³6PDUWDWWDFNVLQVPDUWJULG
E. For figure 9, at the instant on that point the occurrence of FRPPXQLFDWLRQ QHWZRUNV´ Communications Magazine, IEEE, vol. 50,
fault is slightly fluctuation of generator 2 Speed occurs. no. 8, pp. 24±29, August 2012.
Whereas the speed of gen1 & gen 3 remains almost [6] 3.,\DPER57]RQRYD³7UDQVLHQW6WDELOLW\$QDO\VLVRIWKH,(((-
Bus Electrical Power SystHP´,(((&RQI.
unaffectedǤ
[7] :DOWRQ - DQG :KLFNHU / ³ 9LUWXDO (QWHUSULVH 0\WK DQG 5HDOLW\´,
F. For figure 10, Generator 2 has no reactive power delivered Journal of Control, Vol. 22, No. 8, pp.22-25,1996.
whereas generator 1 has delivered maximum reactive [8] "Proposed terms and definitions for power system stability", IEEE
power. Generator 3 has slow down or less reactive power Trans. Power Apparatus and Systems, vol. PAS-101, pp.1894-
than Generator 1. 1897,1982.
This demonstrates that it is a noteworthy power swing [9] A. Atputharajah, T.K. Saha, ³Power system blackouts²literature
review´ LQ International Conference on Industrial and Information
between the generators. The elimination of each important Systems, pp. 460±465, ICIIS, 2009.
line out of the system can affect other transmission lines [10] '- :DWWV 6+ 6WURJDW] &ROOHFWLYH G\QDPLFV RI µVPDOO-ZRUOG¶
which having to transmit more power so as to keep the load networks, Nature 393 , 440±442, June,1998.
balance of the system. The overloaded lines of the real power [11] $%DUDEiVL³(PHUJHQFHRIVFDOLQJLQUDQGRPQHWZRUNV´6FLHQFH
grid are leaded to further failures and ensures in cascaded (5439) ,509±512, 1999.
based blackout. [12] 0 (SSVWHLQ DQG 3 +LQHV ³$ ³UDQGRP FKHPLVWU\´ DOJRULWKP IRU
identifying collections of multiple contingencies that initiate cascading
VI. CONCLUSION IDLOXUH´ Power Systems, IEEE Transactions on, vol. 27, no. 3, pp.
1698±1705, August 2012.
This paper suggests the power flow based smart model for [13] 4&KHQDQG/0LOL³&RPSRVLWHSRZHUV\VWHPYXOQHUDELOLW\HYDOXDWLRQ
analytic approach that aim to evaluate the smart grid stability WRFDVFDGLQJIDLOXUHVXVLQJLPSRUWDQFHVDPSOLQJDQGDQWLWKHWLFYDULDWHV´
on grid generator voltages and rotor angles of a generator Power Systems, IEEE Transactions on, vol. 28, no. 3, pp. 2321±
2330,August 2013.
which identified by this proposed model for matching realistic
[14] D. Witthaut, M. Rohden, X. Zhang, S. Hallerberg, M. Timme, ³Critical
situations. The analysis results also support power system links and nonlocal rerouting in complex supply networks´, vol no. 2,
planning and design provided a reference for predicting pp. 1±21, 2015.
cascaded failures. A new Smart Stability index is established [15] ( %RPSDUG 5 1DSROL DQG ) ;XH ³$QDO\VLV RI VWUXFWXUDO
to determine vulnerable lines and weak generator. By YXOQHUDELOLWLHV LQ SRZHU WUDQVPLVVLRQ JULGV´ International Journal of
performance of the topological model we establish minimal Critical Infrastructure Protection, vol. 2, pp. 5-12, 2009.
way to find out fault and recover with lowest time consumed [16] 0 6WXEEH $ %LKDLQ DQG - 'HXVH ´6LPXODWLRQ RI 9ROWDJH &ROODSVH´
Electrical Power and Energy Systems, vol 15, no 4, August 1993.
that is beneficial stake-holder of power trading owner. After
[17] 6 'H\ & . &KDQGD DQG 'U $ &KDNUDEDUWL ³&RQFHSW RI D *OREDO
all a smart power grid is a dynamic and complex intelligent Voltage Security Indicator (VSI) and Role of SVC on it in Longitudinal
system. Considering all features in one model is impossible. Power Supply (LPS) Systems´ Electric Power System Research, vol 68,
This paper elucidates the generator most severity for grid pp 1-9,2004.
analysis and how to quantify the weak bus. In practice, rate of [18] ' 1JX\HQ < 6KHQ DQG 0 7KDL ³'HWHFWLQJ FULWLFDO QRGHV LQ
power flow can alter every once in a while. Depending on LQWHUGHSHQGHQW SRZHU QHWZRUNV IRU YXOQHUDELOLW\ DVVHVVPHQW´ IEEE
Transactions on Smart Grid,, vol. 4, no. 1, pp. 151±159, March 2013.
demand, season and weather power generation can vary. First
[19] A chakraborty,A De & C k Chanda, ³Development of a Unique Network
and foremost smart grid is an interdependent complex Equivalencing Technique for Determining Voltage Stable States in a
network. Hence, there are good scopes of model the coupling Multi-bus Longitudinal Power System using Load Flow Analysis´, IE(I)
networks in smart grid for researchers and then extend journal,PP.196-202, vol 85,March 2005.
approaches to identify new collapse point.In future work, [20] <DQJ ' =KRX% 'X ; ³A Simplification Method of Power Flow
Calculation Based on Newton-5DSKVRQ´Journal of Shenyang Institute
dynamic model will be implemented considering above those of Engineering ,Natural Science, 4(1), 37±40, 2008.
factors. [21] - <DQ < 7DQJ + +H DQG < 6XQ ³&DVFDGLQJ IDLOXUH DQDO\VLV ZLWK
DC power flow model and transient stability analysLV´ IEEE
ACKNOWLEDGMENT Transactions on Power Systems,, vol. 30, no. 1, pp. 285±297, January
The uttermost gratitude goes to professors are from IIEST, 2015.
Shibpur giving their valuable suggestion and profound [22] P. Kundur, K. Morison and B. Gao 'Practical considerations in voltage
stability assessment', Int. Journal of Electrical Power & Energy Systems,
discussion helped to enhance the standard of this paper. Vol 15, No 4, Special issue, pp 205 - 216, Aug 1993.
REFERENCES [23] P. Borremans, et.al.,³ Voltage stability ± fundamental concepts and
comparison of practical criteria´, Cigre' Report, 38 - 11, 1984.
[24] A. Dwivedi, X. Yu, A maximum-flow-based complex network approach
[1] K. Morison, L. Wang, P. Kundur, ³Power system security assessment´, for power system vulnerability analysis, IEEE Trans. Ind. Inform. 9 (1)
IEEE Power Energ. Mag. ,30±39, 2 ±october,2004. ,81-88, 2013.
[2] Wilson I.E., Harvey S., Vankeisbelck R., and Kazi A.S ³26026
(QDEOLQJWKHFRQVWUXFWLRQYLUWXDOHQWHUSULVH´,7FRQSS-110,2001.

246
2017 IEEE Calcutta Conference (CALCON)

ANNEXTURE Pole 32 2 2
Frequency(Hz) 50 50 50
Xd 0.1460 0.8958 1.3125
TABLE IV. GENERATOR DATA
;¶d 0.0608 0.1198 0.1813
;´d 12 0.1 0.16
Generator No. 2 1 3 Xq 0.0969 0.8645 1.2578
Rated MVA 247.5 192 128 ;¶T 0.0969 0.1969 0.25
MW 163.2 247.5 108.8 Xl 0.0336 0.0521 0.0742
H(s) 23.64 6.4 3.01 Td0 8.96 6.00 5.89
KV 16.5 18 13.8 Tq0 0 0.535 0.600
Power factor 1.0 0.85 0.85 Stored Energy 2364 640 301
Type Hydro Steam/Turbo Steam/Turbo (MW)
Speed(rpm) 188 3000 3000

247

You might also like