Bit 0: Host/Local (R/W) Bit 6: Alarm (R)
0 = Local 0 = No Alarms
1 = Host 1 = Alarms
Bit 1: Run/Stop (R/W) Bit 7: Warning (R)
0 = stop 0 = No Warnings
1 = Run 1 = Warnings
Bit 2: Load/Unload (R/W) Bit 8: On/Off Line Mode (R)
0 = Unload 0 = Not in On/Off Line Mode
1 = Load 1 = On/Off Line Mode
Bit 3: Modulating (R) Bit 9: Mod/ACS or Mod Only (R)
0 = Not Modulating 0 = Not in Mod/ASC Mode
1 = Modulating 1 = Mod/ASC Mode
Bit 4: Unused Bits 10-12: Unused
Bit 5: Stopped in Auto Restart (R) Bits 13-15: Unit Type (R)
0 = Not Stopped in Auto Restart 001 = SSR controller
1 = Stopped in Auto Restart

FIGURE 4-2 INTELLISYS SSR CONTROLLER REGISTER OISTATUSICONTROL

Register 096: Language Register 097: Units of Measure


0 = English 0 = “F and PSI
1 = Spanish 1 = “C and PSI
2 = French 2 = “C and Bar
3 = Portuguese 3 = “C and kPa
4 = “C and kg/cm2

Register 99: Rated Horse Power


0 = 50 6 = 200
1 =60 7 = 250
2 = 75 8 = 300
3= 100 9 = 350
4= 125 10=400
5= 150 II=450

FIGURE 4-3 INTELLISYS SSR CONTROLLER REGISTER CODES

Bit 0: Run/Stop (R) Bit 4: Stopped Auto Restart (R)


0 = stop 0 = Not Stopped in Auto Restart
1 = Run 1 = Stopped in Auto Restart
Bit 1: On/Off Line Mode (R) Bit 5: Unused
0 = Not in On/Off Line Mode
1 = On/Off Line Mode
Bit 2:. MODlACS Mode (R) Bit 6: Unused
0 = Not in Mod/ACS Mode
1 = Mod/ACS Mode
Bit 3: Load/Unload (R) Bit 7: Unused
0 = Unload

FIGURE 4-4 INTELLISYS SSR CONTROLLER STATUS ALARM HISTORY

16
FIGURE 4-23 INTELLISYS RECIP CONTROLLER REGISTER STRUCTURE (PART 3 of 3)

29
Bit 0: Host/Local (R/W) Bit 6: Alarm (R)
0 = Local 0 = No Alarms
1 = Host 1 = Alarms
Bit 1: Run/Stop (R/W) Bit 7: Warning (R)
0 = stop 0 = No Warnings
1 = Run 1 = Warnings
Bit 2: Load/Unload (R/W) Bit 8: Constant Speed Mode (R)
0 = Unload 0 = Not in Const. Speed Mode
1 = Load 1 = Constant Speed Mode
Bits 3-4: Load Level (R/W) Bit 9: Auto/Dual Mode (R)
00 = 25% 0 = Not in Auto/Dual Mode
01 = 50% 1 = Auto/Dual Mode
10 = 75%
11 = 100%
Bit 5: Stopped in Auto Restart (R) Bits 10-12: Unused
0 = Not Stopped in Auto Restart Bits 13-15: Unit Type (R)
1 = Stoooed in Auto Restart 111 = Recip controller

FIGURE 4-24 INTELLISYS RECIP CONTROLLER REGISTER OlSTATUSICONTROL

Register 097: Recip Type Register 098: Regulation Type


1 = LLE 0 = 2 step
2 = XLE 1 = 3 step
3 = PHE 2 = 5 step (4 output)
3 = 5 step (3 output)

FIGURE 4-25 INTELLISYS RECIP CONTROLLER REGISTER CODES

Bit 0: Run/Stop (R) Bit 4: Stopped Auto Restart (R)


0 = stop 0 = Not Stopped in Auto Restart
1 = Run 1 = Stopped in Auto Restart
Bit 1: Constant Speed Mode (R) Bits 5-6: Load Level
0 = Not inconstant Speed Mode 00 = 25% Load
1 = Constant Speed Mode 01 = 50% Load
Bit 2: Auto Dual Mode (R) 10 = 75% Load
0 = Not in Auto Dual Mode 11 = 100% Load
1 = Auto Dual Mode
Bit 3: Load/Unload (R) Bit 7: Unused
0 = Unload
1 = Load

FIGURE 4-26 INTELLISYS RECIP CONTROLLER STATUS ALARM HISTORY

30
Addendum to Intellisys Remote Interface Manual
APDD 635A / March 1997

This addendum includes IRI register definitions for the following machine types.

(1) Sierra Single Stage Booster 125-200 HP SG Controller ……………………………. Page 1


(2) Recip machines with the SG Controller ……………………………………………. Page 5
(3) Sierra 125-200 HP SG Controller …………………………………………………... Page 11

Please insert these pages after page 39 of the original manual.

Addendum
To
APDD 635A
March 1997
SIERRA SINGLE STAGE BOOSTER 125-200 HP CONTROLLER

Register Variable Read/ Range Notes


(40XXX) Write
001 Status/Control R/W See FIGURE 4-41
003 Package Discharge Pressure R
004 Airend Inlet Pressure R
005 Airend Discharge Pressure R
007 Oil Filter In Pressure R
008 Bearing Oil Pressure R
009 Airend Inlet Temp. R
011 Airend Discharge Temp. R
012 Bearing Oil Temp. R
013 Package Discharge Temp. R
064 Running Hours (<10,000 hours) R
065 Ten Thousand Running Hours R Multiply value by 10,000
066 Load Hours (<10,000 hours) R
067 Ten Thousand Load Hours R Multiply value by 10,000
093 Service Level R 0 or 1 0=Level 1, 1=Level 1
094 Service Type R 0 or 1 0=Hours, 1=Months
095 Service Interval R 0-3 3, 6, 9, or 12 months
096 Language Selection R See FIGURE 4-42
097 Units of Measure R See FIGURE 4-42
098 Rating Pressure R
099 Starter Type R 0 -3
112 Offline Pressure R/W 75 - (rated+3) rated = rated pressure
113 Online Pressure R/W 65-(offline-10) offline = offline pressure
114 Condensate Release Time (seconds) R/W 2-10
115 Condensate Inteval Time (seconds) R/W 90-270
116 Start-Delta Time (seconds) R 10-20
117 Auto Start/Stop Time (minutes) R/W 2-60 No Write if AS/S is off
119 Max. Airend Temperature R/W 328-428
120 PORO Time (seconds) R/W 10-120 No Write if PORO is off
121 Auto Start/Stop On/Off R 0 or 1 0=Off, 1=On
122 PORO On/Off R 0 or 1 0=Off, 1=On
123 Remote Start/Stop On/Off R 0 or 1 0=Off, 1=On
124 Sequence Control On/Off R 0 or 1 0=Off, 1=On
125 Condensate Level On/Off R 0 or 1 0=Off, 1=On
126 Load Delay Time (seconds) R/W 0 - 60
127 Lead/Lag R/W 0 or 1 0=Lead, 1=Lag
128 Lag Offset R/W 0-45 psi
129 Contrast R 0 - 10
130 Lead/Lag Cycle Length (Hours) R/W 0 - 750
131 Scheduled Start (Hours) R/W 0 - 23
132 Scheduled Start (Minutes) R/W 0 - 59
133 Scheduled Stop (Hours) R/W 0 - 23
134 Scheduled Stop (Minutes) R/W 0 -59
135 Real Time Hours R 0 - 23
136 Real Time Minutes R 0 - 59
137 Month of Year R 1 - 12
138 Day of Month R 1 - 31
139 Year R 0 - 99

1
Register Variable Read/ Range Notes
(40XXX Write
252 Part Number R High 16-bits
253 Part Number R Lower 16-bits
254 Software Version R
255 Warning Code R See FIGURE 4-44
256-270 Alarm Code History R See FIGURE 4-44
288-302 Airend Inlet Pressure Alarm History R
304-318 Airend Discharge Press. Alarm History R
320-334 Package Discharge Press. Alarm History R
336-350 Oil Filter In Pressure Alarm History R
352-366 Bearing Oil Pressure Alarm History R
384-398 Airend Inlet Temp Alarm History R
400-414 Airend Discharge Temp Alarm History R
512-526 Bearing Oil Temp Alarm History R
528-542 Package Discharge Air Temp Alarm History R
544-558 Run Hours Alarm History R
560-574 Run Hours, Ten Thosand, Alarm History R
576-590 Load Hours Alarm History R
592-606 Load Hours, Ten Thousand, Alarm History R
608-622 Status Alarm History R See FIGURE 4-43
999 IRI Version Number R Reads from IRI only

FIGURE 4-40 INTELLISYS SIERRA SINGLE STAGE BOOSTER 125-200HP CONTROLLER


REGISTER STRUCTURE

2
Bit 0: Host/Local (R/W) Bit 6: Alarm (R)
0 = Local 0 = No Alarms
1 = Host 1 = Alarms
Bit 1: Run/Stop (R/W) Bit 7: Warning (R)
0 = Stop 0 = No Warnings
1 = Run 1 = Warnings
Bit 2: Load/Unload (R/W) Bit 8: On/Off Line Mode (R)
0 = Unload 0 = Not in On/Off Line Mode
1 = Load 1 = On/Off Line Mode
Bit 3: Unused Bit 9:Unused
Bit 4: Unused Bits 10-12: Unused
Bit 5: Stopped in Auto Restart (R) Bits 13-15: Unit Type (R)
0 = Not Stopped in Auto Restart 100 = Sierra controller
1 = Stopped in Auto Restart
FIGURE 4-41 INTELLISYS SIERRA SINGLE STAGE BOOSTER 125-200HP CONTROLLER
REGISTER 01-STATUS/CONTROL

Register 096: Language Register 097: Units of Measure


0 = English 0 = °C and Bar
1 = Spanish 1 = °C and PSI
2 = French 2 = °C and kPa
3 = Portuguese 3 = °F and PSI
4 = °C and kg/cm2

Register 099: Starter Type


0 = Full Voltage
1 = Star-Delta
2 = No Starter
FIGURE 4-42 INTELLISYS SIERRA SINGLE STAGE BOOSTER 50-100HP CONTROLLER
REGISTER CODES

Bit 0: Run/Stop (R) Bit 4: Stopped Auto Restart (R)


0 = Stop 0 = Not Stopped in Auto Restart
1 = Run 1 = Stopped in Auto Restart
Bit 1: On/Off Line Mode (R) Bit 5: Unused
0 = Not in On/Off Line Mode
1 = On/Off Line Mode
Bit 2: Unused Bit 6: Unused

Bit 3: Load/Unload (R) Bit 7: Unused


0 = Unload
1 = Load
FIGURE 4-43 INTELLISYS SIERRA SINGLE STAGE BOOSTER125-200HP CONTROLLER
STATUS ALARM HISTORY

3
Code Description
02 Sensor Failure 2APT
03 Sensor Failure 3APT
04 Sensor Failure 4APT
05 Sensor Failure 5OPT (Warn)
06 Sensor Failure 6OPT
07 Sensor Failure P7 (Spare)
08 Sensor Failure P8 (Spare)
10 Sensor Failure 3ATT (Warn)
11 Sensor Failure 4ATT
12 Sensor Failure 5OTT
13 Sensor Failure 7ATT (Warn)
14 Sensor Failure T6 (Spare)
15 Sensor Failure T7 (Spare)
16 Sensor Failure T8 (Spare)
17 Starter Fault
18 Motor Overload (Main)
19 Fan Motor Overload
21 High Airend Discharge Temp.
22 High Bearing Oil Temp.
23 High I/C Air Temp.
24 Control Power Loss
25 Remote Stop Failure
26 Remote Start Failure
29 High Discharge Air Pressure
30 Low Bearing Oil Pressure
31 High I/C Pressure (Loaded)
32 Emergency Stop
33 Change Inlet Filter
34 High I/C Pressure (Unloaded)
35 Change Oil Filter (Warn)
36 Airend Stage Pressure
37 Memory Fault
38 Low Water Flow
39 High Condensate
FIGURE 4-44 INTELLISYS SIERRA SINGLE STAGE BOOSTER125-200HP CONTROLLER
ALARM/WARNING CODES

4
RECIP SG CONTROLLER

Register Variable Read/ Range Notes


(40XXX) Write
001 Status/Control R/W See FIGURE 4-46
003 Oil Pressure R
004 Water In Pressure R
005 Water Out Pressure R
006 Package Discharge Pressure R
007 1st Stage Discharge Pressure R
008 2nd Stage Discharge Pressure R 3 Stage Units Only
009 Suction Pressure R Booster Units Only
010 Inlet Vacuum R Air Filter Press Drop Option
011 Oil Temperature R
012 Water In Temperature R
013 2nd Stage Inlet Temperature R
014 3rd Stage Inlet Temperature R 3 Stage Units Only
015 Package Discharge Temperature R
016 1st Stage Discharge Temperature R
017 2nd Stage Discharge Temperature R
018 3rd Stage Discharge Temperature R 3 Stage Units Only
064 Total Hours (hours) R 0 – 9999 Less Than 10000
065 Ten Thousand Total Hours R Multiply by 10000
066 100% Loaded Hours (hours) R 0 – 9999 Less Than 10000
067 Ten Thousand 100% Loaded Hours R Multiply by 10000
068 50% Loaded Hours (hours) R 0 – 9999 Less Than 10000
069 Ten Thousand 50% Loaded Hours R Multiply by 10000
070 25% Loaded Hours (hours) R 0 – 9999 Less Than 10000
071 Ten Thousand 25% Loaded Hours R Multiply by 10000
072 75% Loaded Hours (hours) R 0 – 9999 Less Than 10000
073 Ten Thousand 75% Loaded Hours R Multiply by 10000
096 Language Selection R 0–2 See FIGURE 4-47
097 Units of Measure R 0–4 See FIGURE 4-47
098 Recip Type R 0–5 See FIGURE 4-47
099 Rated Pressure R
100 Sensor 2APT R 0–2 0=225, 1=500, 2=1000
101 Sensor 1APT R 0–2 0=225, 1=500, 2=1000
102 Sensor 7APT R 0–2 0=225, 1=500, 2=1000
103 Sensor 3APT R 0–2 0=225, 1=500, 2=1000
104 Regulation R 0–4 See FIGURE 4-47
105 Starter Type R 0–3 See FIGURE 4-47
112 Offline Pressure R/W 30 - rated rated = rated pressure
113 Online Pressure R/W 20-(offline-2) offline = offline pressure
114 Mode of Operation R/W 0–1 See FIGURE 4-47
115 Load Delay Time (seconds) R/W 15 – 60
116 Star-Delta Time (seconds) R 10 – 20
117 Auto Start/Stop (AS/S) Time (minutes) R/W 2 – 20
118 Condensate Time (seconds) R/W 3 – 60
119 Contrast R 0 – 10
120 Condensate Interval (seconds) R/W 60 – 300
121 Inlet Regulation Time (10ths of seconds) R/W 0 – 5.0
122 Minimum 1st Stage Discharge Pressure R/W 50 – 300
123 Auto Start Delay Time (seconds) R/W 0 – 60

5
Register Variable Read/ Range Notes
(40XXX) Write
128 Remote Start/Stop On/Off R 0 or 1 0=Off, 1=On
129 Sequence Control On/Off R 0 or 1 0=Off, 1=On
130 Power Out Restart Option (PORO)On/Off R 0 or 1 0=Off, 1=On
131 PORO Time (seconds) R 10 - 120
132 Air Filter Pressure Drop On/Off R 0 or 1 0=Off, 1=On
133 Air Filter Pressure Drop Value (10th of psi) R .2 – 1.0
134 Closed Loop Water System R 0 or 1 0=Off, 1=On
144 High 1st Stage Discharge Temperature R/W 150 – 500
145 High 2nd Stage Discharge Temperature R/W 150 – 500
146 High 3rd Stage Discharge Temperature R/W 150 – 500
147 High Oil Temperature R/W 120 – 210
148 Low Water In Temperature R/W 30 – 50
149 High Water In Temperature R/W 50 – 150
150 High 2nd Stage In Temperature R/W 80 – 160
151 High 3rd Stage In Temperature R/W 80 – 160
152 High Package Discharge Temperature R/W 80 – 500
153 High 1st Stage Discharge Pressure R/W 100 – 400
154 High 2nd Stage Discharge Pressure R/W 100 – 400
155 Low Suction Pressure R/W 30 – 400
156 High Suction Pressure R/W 35 – 405
157 Low Oil Pressure R/W 8 – 60
158 Low Water In Pressure R/W 25 – 45
159 High Water In Pressure R/W 50 – 76
160 Low Water Pressure Drop R/W 0 – 40
252 Software Part Number – Most Significant R High Digits
253 Software Part Number – Least Significant R Low Digits
254 Software Version Number R
255 Warning Code R See FIGURE 4-49
256-270 Alarm Code History R See FIGURE 4-49
272-286 Oil Pressure Alarm History R
288-302 Water In Pressure Alarm History R
304-318 Water Out Pressure Alarm History R
320-334 Package Discharge Press Alarm History R
336-350 1st Stage Discharge Press Alarm History R
352-366 2nd Stage Discharge Press Alarm History R
368-382 Suction Pressure Alarm History R
384-398 Inlet Vacuum Alarm History R
400-414 Oil Temperature Alarm History R
416-430 Water In Temperature Alarm History R
432-446 2nd Stage In Temperature Alarm History R
448-462 3rd Stage In Temperature Alarm History R
464-478 Package Discharge Temp Alarm History R
480-494 1st Stage Discharge Temp Alarm History R
496-510 2nd Stage Discharge Temp Alarm History R
512-526 3rd Stage Discharge Temp Alarm History R
528-542 Run Hours Alarm History R Less Than 10000 Hours
544-558 10000 Run Hours Alarm History R Multiply by 10000
560-574 100% Loaded Hours Alarm History R Less Than 10000 Hours
576-590 10000 100% Loaded Hours Alarm History R Multiply by 10000
592-606 50% Loaded Hours Alarm History R Less Than 10000 Hours
608-622 10000 50% Loaded Hours Alarm History R Multiply by 10000
624-638 Status Alarm History R See FIGURE 4-48
640-654 Real Time Clock Alarm History – Hours R
656-670 Real Time Clock Alarm History – Minutes R
672-686 Real Time Clock Alarm History – Month R

6
Register Variable Read/ Range Notes
(40XXX) Write
688-702 Real Time Clock Alarm History – Date R
704-718 Real Time Clock Alarm History – Year R
720-734 25% Loaded Hours Alarm History R Less Than 10000 Hours
736-750 10000 25% Loaded Hours Alarm History R Multiply by 10000
752-766 75% Loaded Hours Alarm History R Less Than 10000 Hours
768-782 10000 75% Loaded Hours Alarm History R Multiply by 10000
999 IRI Version Number R Reads from IRI only

FIGURE 4-45 INTELLISYS RECIP SG CONTROLLER REGISTER STRUCTURE

7
Bit 0: Host/Local (R/W) Bit 6: Alarm (R)
0 = Local 0 = No Alarms
1 = Host 1 = Alarms
Bit 1: Run/Stop (R/W) Bit 7: Warning (R)
0 = Stop 0 = No Warnings
1 = Run 1 = Warnings
Bit 2: Load/Unload (R/W) Bit 8: Constant Speed Mode (R)
0 = Unload 0 = Not in Const. Speed Mode
1 = Load 1 = Constant Speed Mode
Bits 3-4: Load Level (R/W) Bit 9: Auto/Dual Mode (R)
00 = 25% 0 = Not in Auto/Dual Mode
01 = 50% 1 = Auto/Dual Mode
10 = 75%
11 = 100%
Bit 5: Stopped in Auto Restart (R) Bits 10-12: Unused
0 = Not Stopped in Auto Restart Bits 13-15: Unit Type (R)
1 = Stopped in Auto Restart 111 = Recip controller
FIGURE 4-46 INTELLISYS RECIP SG CONTROLLER REGISTER 01-STATUS/CONTROL

Register 096: Language Register 097: Units of Measure


0 = English 0 = °F and PSI
1 = Spanish 1 = °C and PSI
2 = Portuguese 2 = °C and Bar
3 = °C and kPa
4 = °C and kg/cm2

Register 098: Recip Type Register 104: Regulation


0 = ESV 0 = 2 Step
1 = ESV Booster 1 = 3 Step
2 = PHE, LLE, XLE 2 Stage 2 = 5 Step 1
3 = PHE, DXE 3 Stage 3 = 5 Step 2
4 = PHE 2 A/E Booster 4 = Inlet Regulation
5 = PHE 2 Stage Booster

Register 105: Starter Type Register 114: Mode of Operation


0 = Star-Delta 0 = Constant Speed
1 = Full Voltage 1 = Auto/Dual
2 = Remote Star-Delta
3 = Remote Full Voltage
FIGURE 4-47 INTELLISYS RECIP SG CONTROLLER REGISTER CODES

Bit 0: Run/Stop (R) Bit 4: Stopped Auto Restart (R)


0 = Stop 0 = Not Stopped in Auto Restart
1 = Run 1 = Stopped in Auto Restart
Bit 1: Constant Speed Mode (R) Bits 5-6: Load Level
0 = Not in Constant Speed Mode 00 = 25% Load
1 = Constant Speed Mode 01 = 50% Load
Bit 2: Auto Dual Mode (R) 10 = 75% Load
0 = Not in Auto Dual Mode 11 = 100% Load
1 = Auto Dual Mode
Bit 3: Load/Unload (R) Bit 7: Unused
0 = Unload
1 = Load
FIGURE 4-48 INTELLISYS RECIP SG CONTROLLER STATUS ALARM HISTORY

8
Code Description
01 Sensor Failure 1APT
02 Sensor Failure 2APT
03 Sensor Failure 3APT
04 Sensor Failure 4OPT
05 Sensor Failure 5WPT
06 Sensor Failure 6WPT
07 Sensor Failure 7APT
08 Sensor Failure 3AVPT
09 Sensor Failure 30TT
10 Sensor Failure 7WTT
11 Sensor Failure 5ATT
12 Sensor Failure 6ATT
13 Sensor Failure 4ATT
14 Sensor Failure 1ATT
15 Sensor Failure 2ATT
16 Sensor Failure 8ATT
17 Starter Fault
18 Motor Overload
19 High Vibration
20 Control Power Loss
21 Lubricator Line Alert
22 Low Lubricator Oil Level
23 Low Frame Oil Level
24 Intercooler Condensate
25 Remote Stop Failure
26 Remote Start Failure
27 Aftercooler Condensate
28 High Package Inlet Temperature
29 High Water Out Temperature
30 High Frame Oil Temperature
31 Low Water In Temperature
32 Emergency Stop
33 High 2nd Stage In Temperature
34 High 3rd Stage In Temperature
35 High Package Discharge Temp
36 High 1st Stage Discharge Temp
37 High 2nd Stage Discharge Temp
38 High 3rd Stage Discharge Temp
39 High Water In Temp
40 Low Frame Oil Pressure
41 Low Water In Pressure
42 High Water In Pressure
43 Low Water Pressure Loss
44 High Package Discharge Pressure
45 High 1st Stage Discharge Pressure
46 High 2nd Stage Discharge Pressure

9
Code Description
47 Low Suction Pressure
48 High Suction Pressure
49 Air Filter Pressure Drop
50 High Discharge Pressure by Host
51 Motor Not Synchronized
52 Memory Fault
53 Invalid Calibration
FIGURE 4-49 INTELLISYS RECIP SG CONTROLLER ALARM & WARNING CODES

10
SIERRA 125-200 HP SG CONTROLLER

Register Variable Read/ Range Notes


(40XXX) Write
001 Status/Control R/W See FIGURE 4-51
003 Discharge Pressure R
004 2nd Stage Inlet Pressure R
005 2nd Stage Discharge Pressure R
006 Inlet Vacuum R
007 Oil Filter In Pressure R
008 Bearing Oil Pressure R
009 2nd Stage Inlet Temp R
010 1st Stage Discharge Temp. R
011 2nd Stage Discharge Temp. R
012 Bearing Oil Temp. R
013 Package Discharge Temp. R
014 P6 Spare Pressure Input R 0 - 1023 0 volts = 0, 5 volts = 1023
064 Running Hours (<10,000 hours) R
065 Ten Thousand Running Hours R Multiply value by 10,000
066 Load Hours (<10,000 hours) R
067 Ten Thousand Load Hours R Multiply value by 10,000
093 Service Level R 0 or 1 0=Level 1, 1=Level 1
094 Service Type R 0 or 1 0=Hours, 1=Months
095 Service Interval R 0-3 3, 6, 9, or 12 months
096 Language Selection R See FIGURE 4-52
097 Units of Measure R See FIGURE 4-52
098 Rating Pressure R
099 Starter Type R 0 -3 See FIGURE 4-52
100 Power Type R 0-1 0=50 Hz, 1=60 Hz
112 Offline Pressure R/W 75 - (rated+3) rated = rated pressure
113 Online Pressure R/W 65-(offline-10) offline = offline pressure
114 Condensate Release Time (seconds) R/W 2-10
115 Condensate Inteval Time (seconds) R/W 90-270
116 Start-Delta Time (seconds) R 10-20
117 Auto Start/Stop Time (minutes) R/W 2-60 No Write if AS/S is off
118 Max. 1st Stage Temperature R/W 310-410
119 Max. 2nd Stage Temperature R/W Variable Refer to Sierra's Manual
120 PORO Time (seconds) R/W 10-120 No Write if PORO is off
121 Auto Start/Stop On/Off R 0 or 1 0=Off, 1=On
122 PORO On/Off R 0 or 1 0=Off, 1=On
123 Remote Start/Stop On/Off R 0 or 1 0=Off, 1=On
124 Sequence Control On/Off R 0 or 1 0=Off, 1=On
125 Condensate Level On/Off R 0 or 1 0=Off, 1=On
126 Load Delay Time (seconds) R/W 0 - 60
127 Lead/Lag R/W 0 or 1 0=Lead, 1=Lag
128 Lag Offset R/W 0 - 45 psi
129 Contrast R 0 - 10
130 Lead/Lag Cycle Length (Hours) R/W 0 - 750
131 Scheduled Start (Hours) R/W 0 - 23
132 Scheduled Start (Minutes) R/W 0 - 59
133 Scheduled Stop (Hours) R/W 0 - 23
134 Scheduled Stop (Minutes) R/W 0 -59
135 Real Time Hours R 0 - 23
136 Real Time Minutes R 0 - 59
137 Month of Year R 1 - 12
138 Day of Month R 1 - 31
139 Year R 0 - 99

11
Register Variable Read/ Range Notes
(40XXX Write
140 Integral Sequencing Lead R/W 0–3 0=Off, 1=On, 2=Always,
3=Never
141 Integral Sequencing Total R/W 2–4
142 Integral Sequencing Address R/W 1–4
143 Integral Sequencing Load Delay R/W 10 – 60
144 Integral Sequencing Lead Change (Hours) R/W 0 – 750
145 Integral Sequencing Lead Change – Day R/W 0–9 See FIGURE 4-52
146 Integral Sequencing Lead Change - Hour R/W 0 – 23
147 Integral Sequencing Lead Change – Min R/W 0 – 45 Steps of 0, 15, 30, 45
252 Part Number R High 16-bits
253 Part Number R Lower 16-bits
254 Software Version R
255 Warning Code R See FIGURE 4-54
256-270 Alarm Code History R See FIGURE 4-54
272-286 Inlet Vacuum Alarm History R
288-302 2nd Stage Inlet Pressure Alarm History R
304-318 2nd Stage Discharge Press. Alarm History R
320-334 Package Discharge Press. Alarm History R
336-350 Oil Filter In Pressure Alarm History R
352-366 Bearing Oil Pressure Alarm History R
368-382 1st Stage Discharge Temp Alarm History R
384-398 2nd Stage Inlet Temp Alarm History R
400-414 2nd Stage Discharge Temp Alarm History R
512-526 Bearing Oil Temp Alarm History R
528-542 Package Discharge Air Temp Alarm History R
544-558 Run Hours Alarm History R
560-574 Run Hours, Ten Thosand, Alarm History R
576-590 Load Hours Alarm History R
592-606 Load Hours, Ten Thousand, Alarm History R
608-622 Status Alarm History R See 4-53
999 IRI Version Number R Reads from IRI only

FIGURE 4-50 INTELLISYS SIERRA 125-200HP SG CONTROLLER REGISTER STRUCTURE

12
Bit 0: Host/Local (R/W) Bit 6: Alarm (R)
0 = Local 0 = No Alarms
1 = Host 1 = Alarms
Bit 1: Run/Stop (R/W) Bit 7: Warning (R)
0 = Stop 0 = No Warnings
1 = Run 1 = Warnings
Bit 2: Load/Unload (R/W) Bit 8: On/Off Line Mode (R)
0 = Unload 0 = Not in On/Off Line Mode
1 = Load 1 = On/Off Line Mode
Bit 3: Unused Bit 9:Unused
Bit 4: Unused Bits 10-12: Unused
Bit 5: Stopped in Auto Restart (R) Bits 13-15: Unit Type (R)
0 = Not Stopped in Auto Restart 100 = Sierra controller
1 = Stopped in Auto Restart
FIGURE 4-51 INTELLISYS SIERRA 125-200HP SG CONTROLLER REGISTER 01-
STATUS/CONTROL

Register 096: Language Register 097: Units of Measure


0 = English 6 = German 0 = °F and PSI
1 = Spanish 7 = Danish 1 = °C and PSI
2 = Portuguese 8 = Norwegian 2 = °C and Bar
3 = French 9 = Swedish 3 = °C and kPa
4 = Italian 10 = Finnish 4 = °C and kg/cm2
5 = Dutch 11 = Turkish

Register 099: Starter Type Register 145: Integral Seq. Lead Change – Day
0 = Full Voltage 0 = Sunday 4 = Thursday 7 = Daily
1 = Star-Delta 1 = Monday 5 = Friday 8 = Weekdays
2 = Remote Star-Delta 2 = Tuesday 6 = Saturday 9 = Weekends
3 = Remote Full Voltage 3 = Wednesday
4 = Soft Starter
FIGURE 4-52 INTELLISYS SIERRA 125-200HP SG CONTROLLER REGISTER CODES

Bit 0: Run/Stop (R) Bit 4: Stopped Auto Restart (R)


0 = Stop 0 = Not Stopped in Auto Restart
1 = Run 1 = Stopped in Auto Restart
Bit 1: On/Off Line Mode (R) Bit 5: Unused
0 = Not in On/Off Line Mode
1 = On/Off Line Mode
Bit 2: Unused Bit 6: Unused

Bit 3: Load/Unload (R) Bit 7: Unused


0 = Unload
1 = Load
FIGURE 4-53 INTELLISYS SIERRA 125-200HP SG CONTROLLER STATUS ALARM
HISTORY

13
Code Description
01 Sensor Failure 1AVPT
02 Sensor Failure 2APT
03 Sensor Failure 3APT
04 Sensor Failure 4APT
05 Sensor Failure 5OPT
06 Sensor Failure 6OPT
07 Sensor Failure P7 (Spare)
08 Sensor Failure P8 (Spare)
09 Sensor Failure 2ATT
10 Sensor Failure 3ATT
11 Sensor Failure 4ATT
12 Sensor Failure 5OTT
13 Sensor Failure 7ATT
14 Sensor Failure T6 (Spare)
15 Sensor Failure T7 (Spare)
16 Sensor Failure T8 (Spare)
17 Starter Fault
18 Motor Overload (Main)
19 Fan Motor Overload
20 High 1st Stage Discharge Temp.
21 High 2nd Stage Discharge Temp.
22 High Bearing Oil Temp.
23 High I/C Air Temp.
24 2nd Stage Over Ratio
25 Remote Stop Failure
26 Remote Start Failure
27 High Vacuum
28 High Loaded Vacuum
29 High Discharge Air Pressure
30 Low Bearing Oil Pressure
31 High I/C Pressure (Loaded)
32 Emergency Stop
33 Change Inlet Filter/Inlet Restriction
34 High I/C Pressure (Unloaded)
35 Change Coolant Filter
36 High 2nd Stage Pressure
37 Memory Fault
38 Low Water Flow
39 High Condensate
40 Auxiliary 1
41 Auxiliary 2
42 Service Required
43 100 Hours To Service
44 14 Days To Service
45 Alarm – Service Required
46 No Control Power

14
47 Invalid Calibration
48 Communication Failure 1
49 Communication Failure 2
50 Communication Failure 3
51 Communication Failure 4
FIGURE 4-54 INTELLISYS SIERRA 125-200HP SG CONTROLLER ALARM/WARNING
CODES