Best Practices:

Installing New Radar


Tank Gauging
for level and overfilling on all type
of tanks with all type of products

Hans Manner
Nicolas Odru

Rosemount Tank Radar AB Confidential


Best Practices Installing New Radar Tank Gauging

 Industry Trends
 Engineering standards and guidelines
 What equipment do I need?
 How do I get it installed on my tank?
 How do I get the readings in the control
room?
 Safety & Overfill Prevention

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 2
27-Jun-01, Slide 2
Complience to Standards
 API standards
– 3.1B Automatic Tank Gauging
– 7 Temperature Measurements
– 3.3 LPG measurements
– 3.6 Hybrid Measurements
– 2350 Overfill Protection

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 3
27-Jun-01, Slide 3
Accuracy Performance
 Pattern approvals for Custody Transfer Accuracy
 OIML R85:2008

International Organization of Legal Metrology

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 4
27-Jun-01, Slide 4
Industry Trends

Radar
Continuous
Redundancy
Safety Mechanical
IEC 61508
Point Switch
API 2350
Closed systems
Wireless
Openness
Internet
[File Name or Event]
Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 5
Tank Equipment

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 6
27-Jun-01, Slide 6
Tank Equipment

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 7
27-Jun-01, Slide 7
Tank Equipment – Fixed Roof Tank

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 8
27-Jun-01, Slide 8
Tank Equipment – Floating Roof Tank

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 9
27-Jun-01, Slide 9
Tank Equipment

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 10
27-Jun-01, Slide 10
Tank Equipment

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 11
27-Jun-01, Slide 11
Where to install the equipment on the tank?

 Look for
– Man ways
– Other nozzles
– Gauge hatches
– Still Pipes

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 12
27-Jun-01, Slide 12
Where to install the Tank Equipment?

Gauge hatch Nozzles 2”, 4”, 8”

Nozzle 8” Manway 20”

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 13
27-Jun-01, Slide 13
Where to install the Tank Equipment?

 Radar
 Temp Sensor

 On a 24” Man Way

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 14
27-Jun-01, Slide 14
Use existing still pipes

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 15
27-Jun-01, Slide 15
Use the existing Still Pipe

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 16
27-Jun-01, Slide 16
Don’t worry about dirty and slotted pipes

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 17
27-Jun-01, Slide 17
Where to install the Tank Equipment?

 Still Pipes
fitted in
existing
access
hatch

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 18
27-Jun-01, Slide 18
Where to install the Tank Equipment?

 Still Pipe
fitted in
existing
access
hatch

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 19
27-Jun-01, Slide 19
Where to install the Tank Gauge

 What does API Ch 3.1B say?

– Roof mounting
• Close to the tank wall to avoid roof flexing influence

– Still pipe
• Slotted
• Fixed at the bottom end

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 20
27-Jun-01, Slide 20
Where to install the Temperature Sensor?

 Same location as the


Transmitter
Radar
 Separate nozzle
 Still pipe arrangements
 Floating Roof
penetration options Temp sensor

 The Temp Sensor can


be combined with a
Water bottom sensor

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 21
27-Jun-01, Slide 21
Temperature Measurement

 What does Standards say?

– Use RTD type of sensor (Pt100)


– Use at least 6 sensors on tanks > 50 ft

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 22
27-Jun-01, Slide 22
Where to install the Temperature Sensor?

 Same location
as the Radar
 Fixed Roof tank

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 23
27-Jun-01, Slide 23
Where to install the Temperature Sensor?

 Same location
as the Radar
 Floating Roof
Tank

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 24
27-Jun-01, Slide 24
Where to install the Temperature Sensor?

 Floating Roof
Tank
Roof
penetration
thru a rubber
gasket

Support and
cabling at the
platform level

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 25
27-Jun-01, Slide 25
Where to install the Pressure Sensor (Density) ?

 Lower end of the tank


 Existing nozzles

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 26
27-Jun-01, Slide 26
Where to install the Local Readout?

 At the gauge hatch


 At grade level
 By the road side
 Or at all of the above

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 27
27-Jun-01, Slide 27
Local Readout

 At Grade Level

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 28
27-Jun-01, Slide 28
Local Readout

 Back lit

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 29
27-Jun-01, Slide 29
Where to install the Local Readout?

 By the road side


 Drive-thru readings
 Day and night

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 30
27-Jun-01, Slide 30
How to connect a new system to the Control Room

 Use existing cabling


 Emulation
 Minimized conduit free new cabling
 Wireless

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 31
27-Jun-01, Slide 31
Emulation: Remove Old, Install New
Plug n´ Play

Disconnect the old cabling Remove the old Gauge

Done!

[File Name or Event] Mount the radar antenna Mount the new Gauge 32

Emerson Confidential
27-Jun-01, Slide 32
and connect the wiring
Rosemount Tank Radar AB Confidential
How to connect a new system to the Control Room

OLD NEW

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 33
27-Jun-01, Slide 33
How to connect a new system to the Control Room
 Minimized new cabling
 Intrinsically Safe
 Conduit Free

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 34
27-Jun-01, Slide 34
How to connect a new system to the Control Room
 Minimized new cabling
One pair
cable

Intrinsically
Safe

LAX Airport
[File Name or Event]
Emerson Confidential
Rosemount Tank Radar AB Confidential 35
27-Jun-01, Slide 35
How to connect a new system to the Control Room

 Wireless

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 36
27-Jun-01, Slide 36
How to connect a new system to the Control Room
 Wireless

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 37
27-Jun-01, Slide 37
How to connect a new system to the Control Room

 Wireless

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 38
27-Jun-01, Slide 38
How to connect a new system to the Control Room

 Wireless
 Well proven
 On 2500+ tanks
 Robust
 Safe
 IEC 62591 standard

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 39
27-Jun-01, Slide 39
Overfill Protection with Rosemount 2160
Wireless Vibrating Forks LeveL Switch
No moving parts No wires

No re-calibration Long power module life

9 years at 1 minute
update rate
Min update rate of
1s for control

Virtually unaffected by Self Checking


process conditions condition monitoring

Steam, Density Temperature


[File Name or Event]
vapors,
Emerson dust changes
Confidential changes
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 40
Instrument Advanced Diagnostics-
Health/Self Check Diagnostics
 The 2160 continuously performs instrument health diagnostics to self-
check the condition of the fork and sensor
 Control room can be alerted to emerging issues allowing preventative
maintenance to be scheduled- avoid process down-time
 2160 Frequency Monitoring : interface detection between oil/water,
wet sand/liquid...

Fault conditions detected Standard Enhanced


Process memory failure  
External damage to fork  
Internal wire disconnect or break  
Internal damage to sensor  
[File Name or Event]
Excessive corrosion to fork
Emerson Confidential  
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 41
Overfill Protection with Rosemount
3308 Wireless Guided Wave Radar
No moving parts No wires

No re-calibration Long power module life

9 years at 1 minute
update rate

Virtually unaffected by Single probe handles


process conditions coating better

Steam, Density Temperature


[File Name or Event]
vapors,
Emerson dust changes
Confidential changes
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 42
Proactive Maintenance with
Advanced Diagnostics
 Signal Quality Metrics alerts potential measurement
problems, e.g. caused by probe coating
Field Control room

High
Signal Quality

Low
Time

Level PV
Signal quality
[File Name or Event]
Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 43
Rosemount Level Wireless
2160 Fork Switch & 3308 Guided Wave Radar
 Inaccessible or uneconomic alarms:
– Fast installation of additional instruments

 Gain access to advanced diagnostics:


– Self Check Diagnostics
– Signal Quality Metrics

 Integrate more information into any control


room host without new I/O:
– Eliminate costly cable runs
– System integration

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 44
Readout

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 45
27-Jun-01, Slide 45
Readout

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 46
27-Jun-01, Slide 46
Extended Readout

 Intranet
 Internet
 Portable
devices

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 47
27-Jun-01, Slide 47
Get Tank info distributed

 Open protocols
 OPC
 Modbus
 WebServer

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 48
27-Jun-01, Slide 48
Overfill Safety –
Tank Gauging plays an important part

Time In Use

Emergency response layer

Passive protection layer

Active protection layer

Emergency
Safety layer
Shut Down

Process
Process control layer
Shutdown

Process Process control layer


Value

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 49
27-Jun-01, Slide 49
Why overfill prevention
is important for Industry ?
 EU Safety and Environmental directives
are more and more restrictive :
– Member States are obliged to transpose it
into a national law within the set deadline
– Directive 96/61/EC on integrated pollution
prevention and control
– Directive 96/82/EC on the control of major
accident hazards involving dangerous
substance

 Tank overfill is an important concern :


– Industry have to improve the Safety of their
sites to reduce pollution risks

Industrial requests for overfill


prevention device applications
[File Name or Event] have risen in recent years
Emerson Confidential
27-Jun-01, Slide 50
Buncefield oil storage, UK
Dec. 2005
 Overfill of fuel storage tank
 Bad configuration and faulty
independent high level switch
on floating roof
 20 large storage fuel tanks
took fire
 Over 40 people injured
 UK Health and safety
Executive investigation
resulted in 25
recommendations on fuel
storage sites

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 51
Tank Overfill Prevention :
Key Points
 Detection should be
independant of the primary
level measurement device and
separate failure alarm is
preferable

 Proof testing is required :


manual test or internal
diagnostics can be used

 Redundancy with different


technologies is a common
strategy for critical level
detection

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 52
Tank Overfill Prevention :
Customer challenge

 Customers need to increase the


Safety of their existing
installation :
– More information needed for
continual supervision in the
control room (less operators
round)
– Additional independent high
level alarm on your primary
level measurement
– Remote tank locations / No
local power supply

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 53
Single Point for Overfill Protection
Vibrating Forks is one of the most common
technology used in process industry

 Advantages :  To be considered :
 Independent safety system ≈ One device for each level
 Not affected by process alarm
changes ≈ Power supply needed for
 Different types of on/off alarm electronics
output available ≈ No separate fault signal
 Functionality is less dependant output
on configuration, mechanical
installation and start up

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 54
Rosemount Vibrating Forks Portfolio
OEM Core Premier

-70 +260°C

-40 +180°C -70 +260°C


PlantWeb alerts
-40 +150°C SIL 2 High & Low Level

-40 +150°C Diagnostic Advanced Health Diagnostic

Diagnostic Direct load, Direct load,


PNP, 12V PNP,
Wireless HART
Direct Load, Relay, 8/16 DPDT Relay, 8/16
PNP/PLC
[File Name or Event] IS NAMUR IS NAMUR
Emerson Confidential
27-Jun-01, Slide 55
Basic or Advanced :
What is the difference ?
Output Circuit
Output Circuit
Self Check Diagnostics
Frequency Circuit
Frequency Circuit
Forks
Forks

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 56
2130/2160 Sensor States
 The frequency band below show the six sensors states of the 2130
switching bands divided into three groups :
 Valid sensor frequency : Wet or Dry
 Fault Sensor frequency :
Too Wet : broken wire to the cassette, over-temperature, build-up
Too Dry : sensor body lost mass due to damage to sensor, corrosion
 Zero Frequency
Frequency Switching Bands

Too Wet Wet Dry Too Dry

0HZ DFF – 28% DFF + 4.5%

DFF* 1400 Hz
[File Name or Event] *DFF : Dry Forks Frequency
Emerson Confidential Sensor switching limits are percentage of the calibrated frequency
27-Jun-01, Slide 57
2130 – Self Check available on all
Cassettes :
 Direct Load

 PNP

 Relay

 Fault Relay*

 Namur

 8-16mA*

[File Name or*Provide


Event]
Emerson Confidential
Separate fault signal output
27-Jun-01, Slide 58
Electrical Installation of the 2130
8-16mA – High Level Alarm
U = 24 Vdc Nominal
PE
(Ground)

+ -
ION = 15...17 mA
PSU- +

Heartbeat LED On

Drives 4-20 mA Analog Intput


Compatible with NAMUR NE43

Dry = On

Safe Area Hazardous Area

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 59
Electrical Installation of the 2130
8-16mA – High Level Alarm
U = 24 Vdc Nominal
PE
(Ground)

+ -
IOFF = 7.5...8.5 mA
PSU- +

Heartbeat LED Flashing


1Hz
Drives 4-20 mA Analog Intput
Compatible with NAMUR NE43

Dry = On

Safe Area Hazardous Area

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 60
Electrical Installation of the 2130
8-16mA – Fault Conditions
U = 24 Vdc Nominal
PE
(Ground)

+ -
IFAULT < 3.7 mA
PSU- +

Heartbeat LED Pulsed

Drives 4-20 mA Analog Intput


Compatible with NAMUR NE43

Dry = On

Safe Area Hazardous Area

[File Name or Event]


Emerson Confidential
27-Jun-01, Slide 61
Overfill Safety – Tank Gauge Redundancy

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 62
Overfill Safety – Tank Gauge Redundancy

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 63
Overfill Safety – Tank Gauge Redundancy

Level & Roof Gauging

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 64
Overfill Safety

Level & Roof Gauging

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 65
Common Situation:
Only One Tank Opening
 Need for two
Radars but only one
opening available I want two Radars
on one nozzle!
 What to do?

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 66
27-Jun-01, Slide 66
Put 2 Radar in 1
On-Tank Redundancy Made Easy
 2 Radar in 1
 Only one tank
opening
 Easy installation
 Total electric
separation
 Operates in parallel

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 67
27-Jun-01, Slide 67
2-in-1 Radar
On-Tank Redundancy Made Easy
 Redundancy

 Dual operation
 Gauging

 Overfill Alarm

 Separated

 ”Built in Spare”

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 68
27-Jun-01, Slide 68
Safety Standard Compliant

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 69
27-Jun-01, Slide 69
Safety Standard Compliant
 API 2350 compliant

 IEC 61508 certified


 Certified SIL2
 Certified SIL3

 TÜV, (WHG) certified

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 70
27-Jun-01, Slide 70
Summary
 Its easy to install new
Tank Gauging
 Minimum Wiring
 Wireless
 Use existing tank
opening
 Use exisiting Still Pipes
 Easy to connect to
other systems
 Get Overfil Protection
at the same time

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 71
27-Jun-01, Slide 71
Rosemount Raptor System
THUM 5900S
2240S 5400
2240S 5400 5900S
5900S
2410 Smart Wireless
644 Gateway
3051S
5300
644
2160/65/75 Field
Communication Unit
2230 2410 2410 2410

2180 Field Bus


Modem
2240S Multi-input
Temperature 375 /475 Field
5900S Radar 5300/5400
Transmitter Communicator
Level Gauge Radar Level
TankMater PC
Transmitter
Workstation in
2410 Tank Hub Network TankMaster.net

2230 Graphical Smart Wireless


Field Display THUM Adapter

644 Temperature
3051S Pressure 2120/2160 Transmitter with Single
Transmitter Liquid Level switch Point Temperature Sensor

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 72
Typical instruments on LNG storage tanks

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 73
27-Jun-01, Slide 73
Raptor 5900S radar for LNG
 Radar replacing servo in almost all
applications
 Primary, secondary and HLA
measurement using only radar
 Highest accuracy over full range
 Advanced signal processing
– FMCW @ 10 GHz
– High sensitivity for long range
 Digital accuracy reference
– No aging or temperature effects
 Verification during operation
 SIL 2 and SIL 3 certified
 Unique 2-in-1 redundancy

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 74
27-Jun-01, Slide 74
Antenna – 5900S LPG/LNG
 Designed for
– Liquefied gas in LPG/LNG tanks
Seal & ball
– 4 in still-pipes sch 10 or 40 New Adapter
valve
– 100 mm still-pipes
 Quartz/Ceramic window as pressure sealing
 Verification pin function
 Optional
– Ball valve, fire-proof
– Rosemount 2051 Pressure sensor
 Flange available in six versions
– 4 in. class 150, class 300
– 6 in. class 150, class 300
– 8 in. class 150, class 300

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 75
27-Jun-01, Slide 75
Level Accuracy: 5900S
exceeds OIML R85:2008
4
Old (R85:1998)

0.001 New (R85:2008)


1 Downwards manual log
(mm)

Upwards manual log


0
0 0 5 10 15 20 25 30 Downwards autolog
Upwards autolog
-1
-0.001
New (R85:2008)
-2

-3
Old (R85:1998)

-4

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 76
27-Jun-01, Slide 76
Verification of Level measurement
 On-line verification during
normal operation
 Verification is made inside the
tank
 Tank remains closed and no
valves need to be
maneuvered
 A reference pin is mounted
inside the still-pipe for level
verification
 A bottom reflection ring
mounted at the end of the
pipe is used for zero
verification
 Photos

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 77
27-Jun-01, Slide 77
Raptor –
SIL 2 and 3 Certified

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 78
27-Jun-01, Slide 78
Built In Proof Testing
 The two Radars
will constantly
”safety-check”
each other Avoid Manual Proof Testing
 Long time between
manual Proof
Testing
 ”No man on the
tank”
 Saves $$$

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 79
27-Jun-01, Slide 79
Online proof-testing

-check

Blue and Red lines separated for visibility.


An alarm is given if the  exceeds a defined limit

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 80
27-Jun-01, Slide 80
2-in-1 Radar
Radar #1
 High Level of Safety Radar #2
 SIL3 Rated
 Low Cost Installation
 On Tank Redundancy
 High Availability
 Less Proof Testing
 Less Verification

 Saves $$$ in many ways


[File Name or Event]
Emerson Confidential
Rosemount Tank Radar AB Confidential 81
27-Jun-01, Slide 81
2x Radars on the same tank - well proven

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential
27-Jun-01, Slide 82
Some LNG sites using radar from Emerson:
 Radar gauges have been used for more than 10 years to measure level at several LNG
import terminals in Japan. So far 15+ tanks.

 Trunkline LNG Co. – Terminal, Lake Charles, USA


 Gaz de France – Terminal, Fos Cavaou, France
– Complete Emerson system solution
 CPC Taiwan - Receiving terminal, Northern Taiwan
 Qatargas II - Production site, 5 new tanks,
– Complete Emerson system solution
– Radar for all Level measurements (primary, secondary, HLA)
 Freeport – Quintana Island - Receiving terminal, Texas, USA

Recent projects system solutions, Rex radar gauges combined with Whessoe LTDs
 Cheniere - Sabine Pass – Receiving terminal, Louisiana, US. 5 tanks
 Fluxys - Zeebrügge - Existing receiving terminal, Belgium
 Exxon - Golden Pass LNG – Receiving terminal, Texas US. 5 tanks
 Woodside - Pluto LNG – New export terminal. 2 tanks in Ph I.
 PTT LNG – Map Ta Put – New receiving terminal
 AGA – Nynashamn LNG – New receiving terminal. 1 tk Ph. 1
 Chevron - Gorgon – New tanks at export site, 2 LNG + 4 Condensate tanks. Totally 24
[Fileradars
Name or Event]
Emerson Confidential
Polskie LNG – New receiving terminal, 2 tks.
 27-Jun-01, Slide 83
Rosemount Tank Radar AB Confidential 83
Rosemount LNG Radar Benefits
 No moving parts
 No re-calibration
 No maintenance
 SIL2 / SIL3 safety functions
 Built in High Alarm
 On-Line verification during operation inside the tank
 Custody Transfer Accuracy
 Conformance to API, OIML, ISO and other standards
 Proven Technology
 Many excellent references on LNG and LPG
 Anything for a single gauge to a complete LNG Management System

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 84
27-Jun-01, Slide 84
Emerson and Wärtsilä (Whessoe)
 Combining the skills and experience from two
organizations into an LNG storage management solution
provider
 Rosemount Tank Gauging
– Rosemount is the measurement division within Emerson
– Focus on high accuracy radar level gauges and supporting
instruments for temperature and pressure
– System supplier, incl project management
 Wärtsilä Calais (Whessoe product name)
– Focus on LTD gauges and LNG management software

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 85
27-Jun-01, Slide 85
Total LNG Tank Instrumentation Solution
Level alarms to ESD

Loop 1
Loop 2

5900S LNG + 2410


5900S LNG + 2410
Secondary level
Primary level 5900S + 1146 LTD
2410
Hi-Hi alarm

2240S and 566 2240S and 566


multiple spot multiple spot
temp temp

TANK
N°1

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 86
27-Jun-01, Slide 86
Total LNG Tank Instrumentation Solution

LNG Manager

TANK N°1
Loop 1 Serial link
Loop 2

9510
20 mA loop / RS232C DCS

Serial link Serial link

TANK N°2
Loop 1
Serial link LNG Roll-Over
Predictor
Loop 2
9510
20 mA loop / RS232C
LNG Manager

TRL2 bus for Raptor FCU 2160


/2410 if not using
WM660

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 87
27-Jun-01, Slide 87
Tank detail (Roll-Over)

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 89
27-Jun-01, Slide 89
Sample of project awards
Combined Emerson / Rosemount Tank Radar and Whessoe LTD
- recent projects realized at LNG terminals or production sites :
 Cheniere’s Sabine Pass

 Exxon’s Golden Pass

 Fluxys (Zeebrugge, Belgium)

 Pluto LNG Australia

 Nynashamn Sweden

 PTT LNG Map Ta Put Thailand

 Sonatrach Skikda LNG Algeria

 Gorgon Australia

 Polskie LNG

 Many new projects to be decided shortly

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 90
27-Jun-01, Slide 90
LNG references (continued)
 Golden Pass LNG - new receiving terminal in
Texas; Five tanks. Installation 2008.
– CB&I US is the main EPC for the complete project
– Whessoe LTD + software (Wärtsilä)
– Emerson partner to Wärtsilä and supplied:
• 5 x Radar Rex 3960
• 5 x SDAU
• 5 x MST Cryo
• 2 x FCU 2160

[File Name or Event]


Emerson Confidential
Rosemount Tank Radar AB Confidential 93
27-Jun-01, Slide 93