Professional Documents
Culture Documents
Practical Implementation of Facts On A Model Transmission Line For Performance Improvement
Practical Implementation of Facts On A Model Transmission Line For Performance Improvement
Supervised By:
Prof. Dr. Muhammad Fayyaz Khan
United International University (UIU)
CONTENTS
What is FACTs?
Objectives of FACTs
Types of FACTS Controllers
Transmission line Parameters & Design of FACTS
Controllers
Advantages of FACTS Controllers
Conclusion
Reference
What is FACTs?
Series Shunt
Compen Compens
Source sation ation 4
1 Source
1 2 Transmission Line
3 FACTS Intelligence System (i) (ii)
(i) Series Compensation L
(ii) Shunt compensation O
A
4 Load D
Basic Types Of FACTS
Compensation
FACTS compensation are classified as
Series Compensation
Shunt Compensation
Combined series-series compensation
Combined series-shunt compensation
TALA
Thyristor Controlled Series
Capacitor in New Delhi, India
Beauly Substation , UK
Basic Types Of FACTS
Compensation
Series Compensation
It could be a variable impedance, such as capacitor, reactor, or a
power electronic based variable source of main frequency,
subsynchonous and harmonic frequencies to serve the desired
need.
Inject a voltage in series with the line .
If the voltage is in phase quadrature with the current, controller
supplies or consumes reactive power.
Any other phase, involves control of both active and reactive
power.
Thyristor Controlled Series
Compensation (TCSC)
TCSC : TCSC is a capacitive reactance compensator ,which consists
of a series capacitor bank shunted by a thyristor – controlled reactor in
order to provide a smoothly variable series capacitive reactance.
The equivalent
impedance, Zeq, of
this LC combination
is expressed as
Current control
Damping Oscillations
Transient and Dynamic stability
Voltage stability
Fault current limiting
Basic Types Of FACTS
Compensation
Shunt compensation
It could be a variable impedance (capacitor ,reactor , etc.) or a
power electronic based variable source or combination of both .
Inject a current in the system.
If the current is in phase quadrature with the voltage ,controller
supplies or consumes reactive power.
Any other phase ,involves control of both active and reactive
power.
Types Of Shunt Compensation
Shunt compensation are of 2 types :
1) inductive shunt compensation
2) capacitive shunt compensation
inductive shunt compensation :
If Vr > Vs ; usually happens due to no load or less load or leading load
25MW 238.8 KV 183.3 A 65.65 MW 0 65.65 MVA 45MW 255.1 KV 125.3 A 47.95 MW 0 47.95 MVA
145M 238.8KV 450.2A 161.3MW 0 161.3MVA 145M 239.8KV 379.5A 136.5MW 0 136.5MVA
W W
Performance of Uncompensated 370
km line with R-L Load
Results Of Uncompensated line
Uncompensated Sending End Side (lagging pf) Uncompensated Receiving End Side (lagging pf)
Load Voltage( Current(I) Active Reactive Appare Load Voltage Current Active Reactiv Appare
V) Power(P) Power(Q nt (V) (I) Power( e nt
) Power(S PF Pf
P) Power(
) Q) Power(S
50MW 195 KV 159.33 A 36.09 MW 29.5MVar 46.6 MVA 0.7744 )
50MW 151.66 KV 327.77 A 32.62 67.06MV 74.57 0.4375
MW ar MVA
75MW 195 KV 210.38 A 51.5MW 33.66MVa 61.53 0.837
r MVA 75MW 148.51 KV 357.234 46.92 64.3MVar 79.59 0.5895
A MW MVA
100MW 195 KV 261.8 A 65.61 MW 39.48MVa 76.57 0.8568
r MVA 100MW 144.9KV 392.9 A 59.57 61.22MV 85.42 0.6973
MW ar MVA
125MW 195 KV 311.29 A 78.24 MW 46.58MVa 91.05 0.8593
r MVA 125MW 140.99 KV 431.4 A 70.48 57.95MV 91.25 0.7724
MW ar MVA
150MW 195KV 357.9 A 89.33MW 54.59MVa 104.7 0.8533
150MW 136.85 KV 470.5 A 79.67 54.59MV 96.58 0.8249
r MVA
MW ar MVA
200MW 195 KV 441.2 A 107 MW 72.11MVa 129 MVA 0.8293 200MW 128.3 KV 545.1 A 93.27 47.93MV 104.9 0.8894
r MW ar MVA
Performance of Compensated 370 km
line with R-L Load
Results of Compensated lines
Compensated Sending End Side (lagging pf) Compensated Receiving End Side (lagging pf)
Load Voltage( Current(I) Active Reactive Appare Load Voltage Current Active Reactiv Appare
V) Power(P) Power(Q nt (V) (I) Power( e nt
) Power(S PF Pf
P) Power(
) Q) Power(S
50MW 195 KV 267.6 A 66.04 MW 42MVar 78.26 0.8434 )
MVA 50MW 205.3 KV 400.20 A 59.7 MW 107.8MV 123.2 0.4848
ar MVA
75MW 195 KV 353.8 A 95.32 MW 40.3 MVar 103.5 0.921
MVA 75MW 201.5 KV 446.9 A 86.37 103.9MV 135.1 0.6393
MW ar MVA
100MW 195 KV 443.15 A 123.6 MW 39.09MVa 129.6 0.9534
r MVA 100MW 197.9 KV 503.8 A 111.1 100.2MV 149.6 0.7426
MW ar MVA
125MW 195 KV 532.05 A 150.8 MW 38.3 MVar 155.6 0.9693
MVA 125MW 194.4 KV 431.4 A 133.9 96.6MVar 165.2 0.8109
MW MVA
150MW 195KV 619.4 A 177.1 MW 37.86MVa 181.1 0.9779
150MW 191.9 KV 632.03 A 155.2 93.3 181.1 0.857
r MVA
MW MVar MVA
200MW 195 KV 787.3 A 227.1 MW 37.99MVa 230.3 0.9863 200MW 184.5 KV 765.36 A 193.1 87.1MVar 211.9 0.8894
r MW MVA
MVA
FACTs Implemented On a Model
Transmission Line (practical)
A single phase 2 Km line was taken for FACTs application and
implementation in the lab.
Line parameters are calculated
Line performance was simulated under different load conditions
FACTs controller was designed to improve the line performance
Model Transmission Line Parameters
Calculation
Line specification:
Line= 2 km Short = less than about 80 km (50 mile) long
Medium = 80 km to 240 km (150 mile) long
Load Specification: Long = longer than 240 km long
P = 500 W
V = 220 V
Conductor name = “Turky”
P.F(Power Factor) = 100%
𝑟𝑎𝑐 = 0.750 Ω / 1000 ft = 5.4 Ω 𝑋𝐿 = 0.1390 Ω / 1000 ft.
= 0.182Ω
Now
𝑋𝐿 = 2𝜋𝑓L
L =2.42 mH
Block Diagram of Shunt Compensation
POWER SUPPLY
LCD
Schematic Diagram Of Shunt
Compensation
Hardware Design Of Shunt
Compensation
Source Load
Transmission Line
Hardware Design Of Shunt
Compensation
Hardware Design Of Shunt
Compensation
Capacitor Bank
DC Source
Receiving
END Voltage
Intelligent Circuit
Results Of practical Uncompensated
line
Uncompensated Sending End side Uncompensated Receiving End side
S L
O O
220 V
U A
50 Hz
R D
C
E Back to Back Inductor
Thyristor Driver
Block Diagram of Series
Compensation in the Matlab
Simulink
Series Compensation Output Curve
From Matlab Simulink
Future Work