Dipl.-Ing. Anja Moldehn, Marketing Communication, Power Supplies Business Unit, Phoenix Contact
Electronics GmbH, Bad Pyrmont, Germany
The high degree of availability of machines and highly detrimental effect. For a device with
systems installed across the world is a key a rated current of 20 A, this means, for examp-
prerequisite for business success in any indus- le, that two power supplies, each with 20 A on
trial sector. Only continuously supplied control the output side, are connected in parallel. If
cabinet components increase the profitability one of the power supply units develops an inter-
of the application. For this reason, users are nal fault or if the primary power supply fails, the
increasingly implementing redundant power second unit automatically takes over and sup-
supply concepts, which are often combined plies the load. This means that the power supply
with redundancy modules (lead figure). units must be dimensioned so that one power
supply unit can cover the complete power de-
Power supplies are configured redundantly mand of the connected devices in all operating
everywhere where downtimes would have a states.
Considering all possible fault sources to supply the required power to the load and
does not feed into the short circuit. Without de-
To minimize the risk of a failure, all potential coupling, the load demand would no longer be
fault sources have to be considered. For this satisfied, because the current from the redun-
purpose, potential reasons for failure in a dant power supply feeds into the short circuit.
redundant power supply configuration are
described below, including suitable solutions • Break in the cable between the power
(Figure 1): supply unit and the redundancy module (5)
If the input voltage of the redundancy module is
• Fault in one phase of the primary monitored, a fault in the wiring will be detected
power supply (1) immediately. After removing it, the power sup-
Power supply units connected in parallel are plies function redundantly again.
operated on separate phases. In this way, if one
phase fails or malfunctions, the supply of power • Internal defect in the redundancy module (6)
is not affected. A self-monitoring function reports internal faults
so that the faulty unit can be replaced without
• Short circuit or break in the cable to the any delay.
power supply (2) or failure of one power
supply unit (3) • Break in the cable between the redundancy
Neither problem will impair the supply of power. module and the load (7)
The system is redundant as the second power To increase the availability of the connected
supply can still satisfy the entire load demand load, the wiring to the load should also be re-
even if the other unit no longer provides an out- dundant. If all modules have two plus output
put voltage. terminal blocks, easy and quick installation is
ensured.
• Short circuit between the power supply
and the redundancy module (4) • Excessive load current caused either
In this case, parallel operation of two power sup- by a faulty load or subsequent increase
ply units is not sufficient. What is needed here is through other devices (8)
a diode or redundancy module that decouples The solution for this scenario is to monitor the
the two power supplies from each other. In this load current and issue a warning as soon as a
setup, the second power supply unit continues predefined value is exceeded.
Supply
network
Redundancy module
I1 I2 to are
Load ΣLoad current=I1+I2 possible error sources
Monitoring the load current redundancy modules includes Oring devices
with a function which informs users of an over-
The following example illustrates the advan- load. The function operates with a delay of
tage of combining load current monitoring with four minutes to prevent operators from misin-
an alert (Figure 2). Redundancy can be lost if terpreting high currents caused, for instance,
auser connects additional loads to a redundant by starting motors, with a permanent overload
power supply when expanding the system. situation.
TRIO DIODE
Load Decoupling with redundancy module + monitoring
of the power supply voltages and the wiring
QUINT ORING
Load Decoupling with active redundancy module + monitoring
of the power supply voltages, the wiring,
the decoupling and the load current