Developer:
SFA6 Compliant
Layout Foul Surface Comments
2.4.1 - Sewer Location
Other
Y/N Y/N
SFA6 Compliant
Manholes Foul Surface Comments
2.4.2 - Requirement
Manholes are required at all changes in direction, pipe
diameter, gradient and where 2 or more sewers Y/N Y/N
connect. Distance between manholes should not
exceed 100m.
2.9 - Types
Appropriate MH Types have been used and detailed? Y/N Y/N
NB: MH Types’ A, B, C & E permitted. Where manhole
depth >6m a ‘special’ manhole detail will be required.
2.9.3 - Diameters
Manhole diameters (Type A & B only) are in Y/N Y/N
accordance with Table 2.2 of SFA6 and take into
account minimum benching requirements.
2.9.7 - Covers & Frames
Manhole covers and frames are in accordance with Y/N Y/N
Clause 5.2.32 of SFA6 and badged 'FW' or 'SW'.
2.9.11 - Rocker Pipes
Rocker pipes lengths are in accordance with Table 5.14 Y/N Y/N
of SFA6.
2.9.12 - Backdrops
Steeper gradients are preferred to the use of
backdrops. If required then they should be constructed Y/N Y/N
as external ramped backdrops as per Figure 2.10 in
SFA6.
2.9.15 - Access / Fittings
Minimum access opening sizes and fitting requirements Y/N Y/N
are in accordance with Table 2.3 of SFA6.
Other
Y/N Y/N
SFA6 Compliant
Sewers Foul Surface Comments
2.10.1 - Depths
Do the adoptable sewers have 1.2m cover and if
not are the measures taken to protect them in
Y/N Y/N
accordance with Table 2.4 of SFA6.
2.14.2 - Attenuation
Storage for the 1in30 year event is wholly
contained within the adoptable system. Storage Y/N
above the 1in30 year event is private or flood
routing provided.
2.14.3 - Surcharging
All sewers are designed to run pipe full in a 1in30 Y/N
year event.
5.5.2 - Bedding
The appropriate pipe bedding details have been
provided which in most cases would be a Class 'S'
Y/N Y/N
bed and surround.
Other
Y/N Y/N
SFA6 Compliant
General Foul Surface Comments
Colouring
Drawings are coloured as per Appendix VI of SFA6 Y/N Y/N
with highway drains and private laterals
uncoloured.
Inconsistencies
Pipe lengths, gradients and sizes are consistent on Y/N Y/N
layout plans, long sections and design calculations.
Long Sections
Long section drawings also include bedding
details, concrete protection (where applicable),
Y/N Y/N
manhole types and manhole diameters.
2.4.7 - Outfalls/Headwalls
A detail of the outfall/headwall has been provided
and is in accordance with Fig 2.1 and 2.2 of SFA6
Y/N
which includes water levels.
Other
Y/N Y/N