You are on page 1of 2

Technical Bulletin : DO-5 module causing hardware fault in DI-10

Technical Bulletin:
DO-5 module when working with 4.3
Hardware DI-10

Servelec-Technologies Pty Ltd P +61 (03) 8544 8544 Servelec-group.com/technologies


Unit 8 / 3-5 Gilda Crt F +61 (03) 8544 8555
Mulgrave, Victoria 3170 E
Australia
Technical Bulletin : DO-5 module causing hardware fault in DI-10

Release Information

Product
Affected: DO-5 Module Date: 22/02/2018

Type of
Hardware Software Firmware Documentation
change:

Other

Reason for change

Feature Enhancements Update Product Recall

Other:

Details

Servelec technologies have identified an issue where using new hardware DI-10 modules with the obsolete
DO-5 module can damage the DI-10 modules.

The old DO-5 module (now obsolete) have the 24V and the 12V inputs shorted together by inductors. In the
DI-10 module (Hardware version 4.3 onwards) the 24v bus is used to synchronize time between a DI-10 GPS
and slave module. Connecting DO-5 and DI-10 4.3 hardware together on the backplane introduces 12V to the
time synchronization bus and thus damages the time sync circuitry on the DI-10.

Please note that this issue is caused only when DI-10(4.3) hardware is introduced on the backplane along with
a DO-5 module

Recommended Action

The DO-5 hardware must be upgraded to resolve this issue. This cannot be done in the field so the affected
DO-5 modules must be returned to the Semaphore factory for upgrade, under warranty. Please contact your
local Semaphore office to arrange the return of the modules to our factory for upgrade.

If you do not use the DI-10 4.3 hardware then you can of course choose to ignore this issue.

Servelec-Technologies Pty Ltd P +61 (03) 8544 8544 Servelec-group.com/technologies


Unit 8 / 3-5 Gilda Crt F +61 (03) 8544 8555
Mulgrave, Victoria 3170 E
Australia