test conditions:
DC voltage: 880 V operation mode: MPP AC power: L1: 49876,59 W L2: 49914,63 W L3: 49843,33 W
AC frequency: 50 Hz AC voltage: 346,410161513776 VAC current: L1: 144,11 A L2: 144,14 A L3: 143,99 A
network configuration:
Sinus Rsce: < 33 THD of the line voltage: 0,100%
SMA inverters SHP 150-20 fulfill the limits for harmonic current emission according to IEC/EN 61000-3-12:2005.
49 0,0350 0,0330 0,0330 0,02% 0,02% 0,02% 1,441 1,0% 2,4% 2,3% 2,3%
50 0,0100 0,0070 0,0080 0,01% 0,00% 0,01% 1,441 1,0% 0,7% 0,5% 0,6%