Medicion de Hidrogeno en El Aceite
2. History of gas in oil 7KH ̨UVW SDSHU WKDW PHQWLRQV K\GURJHQ DV
measurements
the most distinctive indicator of electrical
The first observation in transformer
history that correlates faulty condition discharge in the oil – the famous D2 fault
to evolved gasses from the mineral oil is
documented in a paper from 1919 [1].
type – dates back to 1919
Figure 1. Ampules for sampling gas and oil, the U.S. and European versions
w w w . t ra n s fo r m e r s - m a g a z i n e . co m 43
COLUMN
Figure 2. Sampling in duplicate helps reveal incorrect sampling Figure 3. Special sealing between the piston and glass body made to
avoid hydrogen escaping from the syringe
For Gas Chromatography Head Space, there are at least four manufacturers of [11]. Since hydrogen cannot be detected
according to ASTM D3612 the uncertain- these portable and online devices. by PAS, for some version of instruments
ty for punched vials is between 22 % and this measurement is not accurate and
40 %. For non-punched vials, according to Although most studies have found that repeatable. So, the users have to be very
IEC60567 the uncertainty is between 15 % the accuracy of PAS is acceptable for careful when taking into consideration
and 30 %. most of the gases, one study showed a any diagnosis based on hydrogen values
40 % difference between the hydrogen obtained by PAS devices, Fig. 6.
Non-chromatographic DGA was in- concentration when measured by PAS
troduced in 2003 by implementing method and when measured in the
photoacoustic spectroscopy (PAS) in the laboratory [10]. Also, Cigre report 409
3. Online monitors
portable or online device [9]. In the early [11] displays the same magnitude of Most DGA measurements today are per-
years, the PAS sensor was manufactured inaccuracy for this measurement, 38 %, formed either by the fuel cell online mo-
only by one company, Kelman, but today recorded by seven utilities, see Table 8 in nitors or in the laboratories. The fuel cell
Table 1. 90th percentile for the fleet with non-free breathing transformers designed and manufactured in the last 25 years
Calculated 90 %
of the Hydran C 2H 2 CH4 C 2H 6 C 2H 4 CO CO2 H2 TG %
value
w w w . t ra n s fo r m e r s - m a g a z i n e . co m 45
COLUMN
7DEOH7UDQVIRUPHUIDXOWW\SHSUREDELOLW\FODVVLͤHGE\>@
No. of
Type of fault Ratio %
faults
bution to the overall (un)certainty of the In a fleet of more than 200 monito- of continuous monitoring by offline and
diagnosis based on the concentration of red transformers, in 70 % of the cases online devices, with a high but fluctuated
dissolved hydrogen. It seems that hydro- where faulty condition was discovered concentration of hydrogen, between 500
gen concentrations could be problema- by DGA, there was not a significant and 1200 ppm. The failure occurred at 800
tic, and one of the main concerns is that concentration of hydrogen. In the rest ppm hydrogen and 55 ppm methane, but
the liquid and solid insulation existing in of the cases where there was a signifi- the recorded fluctuation of the concentra-
the 1970s when most of the diagnostics cant hydrogen concentration, other hy- tion made it difficult to decide if the fault
was developed is not the same as what we drocarbons or carbon oxides were also was active or not. Finally, the fault was de-
have today. present in such concentrations that they tected on the basis of ethylene, and not on
allowed predicting the failure. However, the basis of abnormal hydrogen value.
The most significant differences in ther- in at least five cases, the hydrogen devel-
modynamics of gases vs. temperature are opment was confirmed as stray gas, and According to different studies, the most
illustrated in Figure 7 and Figure 8. the hydrogen alarm and trigger was in- popular and successful diagnostic meth-
deed a false alarm. Stray gassing produ- od, the classic Duval Triangle [18], is able
In the past, hydrogen was attributed to ces high concentration of gases, which to reveal the fault in more than 90 % of
thermal issues or partial discharge issues. leads to a false alarm. So, stray gassing cases if applied correctly, and it achieves
Based on this, many online device manu- is a very tricky issue in diagnostics. Not these performances without using hy-
facturers claim, even today, that the majo- all transformers filled with potentially drogen. It seems that the undisputable
rity of faulty conditions are characterized stray gassing oil actually develop stray success of this method lies in the fact
by appearance of hydrogen in significant gassing. that it is not affected by the uncertainty
amounts. However, a more recent study of hydrogen evaluation. The used hydro-
observes that in a big majority of failures, Figures 9, 10 and 11 illustrate some of carbons are much less sensitive to usual
hydrogen is not an important gas. Most of the issues related to diagnosing a failure stray gassing.
the failures are overheating or thermal- based on hydrogen.
type failure – 53 % of them [16], and the F. Jacob and J. Dukarm [19] recommend
gas appearing in overheating is ethylene, Figure 11 depicts a real PD fault – an in- not to take into consideration hydrogen
while hydrogen comes only at 2 % [17]. ternal failure that occured after eight years and carbon monoxide concentration val-
ues for fault evaluation. More and more
experts warn about problematic interpre-
A recent study observes that in a big majority tation of those gases. In a recent study [20]
it was established that most of the availa-
RIIDLOXUHVK\GURJHQLVQRWDVLJQL̨FDQWJDV
FDQWJDV ble diagnosing methods suffer from in-
accuracy due to stray gassing, which is at
7DEOH&KDUDFWHULVWLFJDVHVIRUSDUWLFXODUDEQRUPDOFRQGLWLRQV>@
Partial discharge, arc Short circuit between winding layers, winding breakdown; partial discharge
H2
discharge between the tap-changer contacts, arc discharge, short circuit
Overheating, loose
CH4, C2H2 Loose contact of tap-changer, joint becoming loose, insulation is poor
contact
w w w . t ra n s fo r m e r s - m a g a z i n e . co m 47
COLUMN
Conclusion
In the early days of DGA, the most mea-
sured gases were hydrogen, carbon mo-
noxide and acetylene. These gases were
present in a gas cushion above the oil or
the protective relays, in connection to
electrical discharge that mostly involved
cellulose. The early measurements were
performed with low sensitive devices, as
early IR and Mass Spectra. It is time for
a rethink about the necessity and advan-
tages of monitoring hydrogen alone or
with carbon monoxide and their relevan-
Figure 10. Online multi-gas monitor detected a metal hotspot on the connection bolt,
ce to obtaining a reliable health index. In
without an increase of hydrogen concentration
the 21st century, the technology allows
developing new detectors, even based on
old MS principles or on new inventions.
The elevated inaccuracies of low concen-
tration measurements of dissolved hyd-
rogen, together with still unexplainable
phenomenon of stray gassing, impose an
additional concern about using hydro-
gen and, to a lesser degree, carbon dioxi-
de parameters for transformer diagnosis.
Overall
2IÀLQH'*$ Sampling Extraction Measurement 'LDJQRVLV
inaccuracy
Bibliography [11] CIGRE WG D1.01 (TF 15), Report toring and fault diagnosis method, IEEE
on Gas Monitors for Oil-Filled Electrical International Conference, 2012
[1] O. H. Eschholz, Some Characteristics Equipment, Technical Brochure # 409,
of Transformer Oil, The Electric Journal, [17] Z. Etman, D.E Mansour, N. El-Amary,
February 2010
February 1919 Performance evaluation of dissolved gas
[12] Hydran M2-X Brochure, GE Grid analysis technique against measurement
[2] P. Ramachandran, Malfunctioning Solutions, accessed at https://www.ge- errors, IEEE conference on dielectric
of Buchholz Relays-Field Experience and gridsolutions.com/products/brochu- ICDL, 2017
Learnings, India Doble Forum 2014 res/MD/HydranM2-X-Brochure-EN-
[18] M. Duval, Dissolved gas analysis: It
[3] J. T. Madill, Typical Transformer Faults 2018-03-Grid-GA-1644_R003.pdf
can save your transformer, IEEE Electrical
and Gas Detector Relay Protection, AIEE [13] M. Banovic, P. Ramachandran, P. Jus- Insulation Magazine, Vol 6, No.6, pp. 22-
1947 tiz, N. Rego, Significance of CO2/CO ratio 27, 1989
[4] Sloat et al., Gas Evolution from Trans- in dissolved gas analysis, Transformers
[19] F. Jakob, P. Noble, J. J. Dukarm, Ther-
former Oils Under High-Voltage Stress, Magazine, Volume 2, Issue 1, January
modynamic estimation of transformer
IEEE Transactions, March 1967 2015
fault severity, IEEE Trans. on Power Del.,
[5] J.P. Vora, L.C. Aicher, Transformer [14] M. Shirai, S. Shimoji, T. Ishii, Ther- Vol. 30, No. 4, 2015
fault-gas analysis and interpretation, IEEE modynamic study on the thermal decom-
[20] S.Kim et al., Advanced dissolved gas
Trans. on Power Apparatus Systems, vol. position of insulating oil, IEEE Trans. Elec.
analysis method with stray gassing diag-
PAS-84, pp. 172-176, February 1965 Ins., 1977
nosis, 2016 International Conference on
[6] Transformer Fault Detection by Dis- [15] M. Duval, Training track on the best Condition Monitoring and Diagnosis,
solved das Analysis, F.B Waddington & use of Duval Triangles and Pentagons, Xi'an, China
D.J.Allan, electrical Review 1969 TJH2B, 2018, Denver Colorado
[21] W. Lampe, E. Spicar, The oxygen-free
[7] Dissolved Gas Analysis by Gas Chro- [16] Huimin He, Xiaotian Xu, Study on transformer, Reduced ageing by continuous
matography A Modern Tool to detect Inci- transformer oil dissolved gas online moni- degassing, Cigre Paper 12.05, Cigre 1976
pient Faults in Power Transformers, CPRI,
Report No 93, June 1979
Author
[8] Tenbohlen et al., Investigation on Sam-
pling, Measurement and Interpretation of Marius Grisaru received his MSc in Electro-Analytical
Gas-in-Oil Analysis for Power Transfor- Chemistry from Israel Institute of Technology in 1991. The
mers, CIGRE D1-204, 2008 same year he joined Israel Electric Corporation (IE) and
established the insulating oil test policy and methodology
[9] C. Mcllroy, Photo-Acoustic Spectrosco- in Israel. He now performs insulating oil tests and oil
py, A new Technique for DGA in Oil, EPRI treatments in Israel for IE and other local industrial and
2003 private customers, as well as trains and educates electrical
[10] Larry W. Weathington, Compari- staff on insulating oil issues. Marius is an active member
son of two on-line monitoring systems to of IEC and CIGRÉ, and a former member of ASTM. He is the author and co-
laboratory dissolved gas analysis, Doble, author of several papers, CIGRÉ brochures and presentations on insulation
2006 oil tests, focused on DGA and analytical chemistry of insulating oil.
w w w . t ra n s fo r m e r s - m a g a z i n e . co m 49