REPORT TO DEPARTMENT OF CHEMICAL ENGINEERING

MIDDLE EAST TECHNICAL UNIVERSITY

FOR COURSE: CHE-327 HEAT AND MASS TRANSFER


OPERATIONS
PLATE TYPE HEAT EXCHANGER DESIGN
GROUP MEMBERS:

ALARA MELISA AYDIN


COŞKU MOLER
RESKY SAPUTRA

METU

(25.05.2016)

Ankara, TURKEY

1
ABSTRACT

This design project aims to propose a plate type heat exchanger that can meet given heat
duty and find the number of plates required. Plate type heat exchanger uses metal plates to transfer
heat between two fluids. Starting point of this design is to define given properties. It is asked us to
cool the inlet fluid which is waste stream from 65 o C to 40 o C using cooling water at 15 o C. Several
information of the inlet and outlet streams are given such as the inlet and outlet temperature of
waste stream, mass flow rate of inlet stream, physical properties of waste and other constructio na l
data for the similar heat exchanger; vertical, horizontal distances, plate thickness, length, effective
channel width, enlargement factor, chevron angle etc. Several calculations are done in 2 parts. The
first one is geometry analysis used in order to find the required number of plates. The second one
is heat transfer analysis in order to find the required heat duty for both streams and actual heat
duties for clean and fouled involving trial-error solution. Some correlations is needed such as heat
transfer coefficient calculation, correlation of Nusselt number and Reynold number in which the
empirical equation needed. Assumptions are regarded at the beginning of the design. Finally, the
required heat duty for cold and hot streams are found 1.47 x 107 W and the actual heat duties for
clean and fouled are 2.62 x 107 W and 2.32 x 107 W, respectively. The total required number of
plates are also found as 105 plates.

2
TABLE OF CONTENT

TABLE OF CONTENTS

NOMENCLATURE…………………………………………………………………………1

1. INTRODUCTION …………………………………………………………………..3

1.1. Problem Statement……………………………………………………………...4

1.2. The Calculation Method………………………………………………………..5

1.3. Assumptions……………………………………………………………………..8

2. SAMPLE CALCULATIONS…………………………………………………………10

2.1. Geometry Analysis………………………………………………………………10

2.2. Heat Transfer Analysis………………………………………………………….11

3. RESULT AND DISCUSSIONS……………………………………………………….14

4. CONCLUSIONS……………………………………………………………………….16

5. REFERENCES…………………………………………………………………………17

3
NOMENCLATURE

Thi : inlet hot stream temperature 0c

Tho : outlet hot stream temperature 0c

Tci : inlet cold stream temperature 0c

Tco : outlet cold stream temperature 0c

mc : cold stream mass flow rate kg/s

mh : hot stream mass flow rate kg/s

Gc : The cold channel mass velocity kg/m2 s

Gh : The hot channel mass velocity kg/m2 s

Ch : steam heat capacity J/kg.K

Cc : ipa-water mixture heat capacity J/kg.K

Qc : Amount of heat transfer under clean condition W

Qf : Amount of heat transfer under fouled condition W

Uf : Fouled overall heat transfer coefficient W/m2 K

Uc : overall heat transfer coefficient W/m2 K

Ae : Actual effective area m2

A1 : Single plate efective area m2

A1p : Single plate projected area m2

Nt : total number of plates

Ne : The effective number of plates

Np : Number of passes

Ncp : the total number of channels per pass

Lv : Vertical distance m

4
Lh : Horizontal distance m

t : Plate thickness m

Lc : Plate pack length m

Lw : Effective channel width m

p : The plate pitch m

b : the mean channel spacing m

Dh : The hydraulic diameter of the channel m

∅ : The enlargement factor

𝛽 : Chevron angle o

µh : viscocity of hot fluid N.s/m2

µc : viscocity of cold fluid N.s/m2

Pr : prandalt number

Re : reynolds number

Nu : nusselt number

hc : convective heat transfer coefficient on clod fluid W.m2 /K

hh : convective heat transfer coefficient on hot fluid W.m2 /K

𝑅𝑓ℎ : fouling factor for hot fluid m2 .K/W

𝑅𝑓𝑐 : fouling factor for cold fluid m2 .K/W

kw : thermal conductivity of the plate material W/m.K

5
1. INTRODUCTION

Plate heat exchanger is a type of Heat Exchanger which consists of many corrugated
stainless-steel sheets separated by polymer gaskets and clamped into a steel frame. It transfers heat
by placing thin, corrugated metal sheets side by side and connecting them by gaskets. Flow of the
substances to be heated and cooled takes place between alternating sheets allowing heat to transfer
through the metal sheets.

Figure 1: Plate type heat exchanger

Some advantages using plate heat exchanger are high heat transfer area, high heat transfer
coefficient, having lower floor space requirements, multiple duties can be performed by a single
unit, most suitable type heat exchanger for lower flow rates and heat sensitive substances.
Moreover, area of heat transfer of plate heat exchanger can be increased by increasing the number
of the plates.

6
1.1. Problem Statement

In this problem, a plate heat exchanger is needed to be designed for a specific purpose. This heat
exchanger should be able to cool a waste from 65°C to 40°C using cooling water which enters the
heat exchanger at 15°C. The mass flow rate of the waste stream is 140 kg/s and its properties may
be approximated as follows:

ρ = 985 kg/m3

μ = 510 x 10-6 kg/m.s

k = 0.650 W/m.K

Pr = 3.3

Cp = 4200 J/kg.K

Fouling resistance ≡ Fouling resistance of water= 0.0000069 m2 .K/W (taken from Heat
Exchanger: Selection, Rating and Thermal Design, table 10.4)

Moreover, we are going to propose a plate type heat exchanger that can meet this heat duty and
find the number of plats required for the heat exchanger.

Some constructional data for a similar heat exchanger are given as follows:

Total effective area (Ae)= 110 m2

Vertical distance (Lv ) = 1.55 m

Horizontal distance (Lh )= 0.43 m

Plate thickness (t)= 0.6 mm

Plate pack length (Lc)= 0.38 m

Effective channel width (Lw)= 0.63 m

Enlargement factor (∅)= 1.25

Chevron angle (𝛽 )= 45°

7
Plates are stainless steel (kw = 16.5 W/m.K, taken from heat exchangers selection, Rating and
thermal design, table 10.1)

Figure 2: Main dimensions of a chevron plate and and developed and projected dimensions of a
chevron plate cross section normal to to the direction troughs.

1.2. The Calculation Method;

Calculation of this problem design are separated by 2 analysis.

The first one is geometry analysis. The channels increase the surface area of the plate as
compared to the original flat area. To express the increase of the developed length in relation to
the projected length, a surface enlargement factor,∅, is the defined as the ratio of the developed
length to the flat or projected length

𝐷𝑒𝑣𝑒𝑙𝑜𝑝𝑒𝑑 𝑙𝑒𝑛𝑔𝑡ℎ 𝐴𝑐𝑡𝑢𝑎𝑙 𝑒𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑎𝑟𝑒𝑎


∅= = 𝑝𝑟𝑜𝑗𝑒𝑐𝑡𝑒𝑑 𝑝𝑙𝑎𝑡𝑒 𝑎𝑟𝑒𝑎 =A1 /A1p
𝑃𝑟𝑜𝑗𝑒𝑐𝑡𝑒𝑑 𝑙𝑒𝑛𝑔𝑡ℎ

(1.1)

8
Where Actual effective area can be calculated as (1.2)

Actual effective area (Ae) = Lp * Lw (1.2)

Or actual effective area can be calculated as Ae = A1 * Ne

Where the effective number of plates. N e, can be estimated as N e = Nt – 2

Also Lp and Lw can be estimated from the port distance Lv and Lh and port diameter Dp as

Lp ≈ Lv - Dp (1.3)

Lw ≈ Lh + Dp (1.4)

The value of enlargement factor is calculated the effective flow path.

From (1.3 and 1.4) we can make a new equation to find Lp.

Lp = Lv – Lw + Lh (1.5)

Flow channel is the conduit formed by two adjacent plates between the gaskets. The cross section
of a corrugated surface being very complex, the mean channel spacing, b, is defined as (1.6)

b = p –t (1.6)

The plate pitch (p) can be determined from the compressed plate pack length (Lc), which usually
specified.

p = Lc / N t (1.7)

Where N t is the total number of plates.

The hydraulic diameter of the channel (Dh ) can be estimated as (1.8)

Dh ≈ 2b / ∅ (1.8)

Finding the total number of channels per pass (Ncp) is obtained from (1.9)

Ncp = (Nt – 1) / 2 *Np (1.9)

Where Nt is total number of plates and Np is the number of passes.

9
From those correlations we can find total number of plates required. With plate type heat
exchangers, heat transfer is enhanced. The heat transfer enhancement will strongly depend on the
chevron inclination angle (𝛽) relative to flow direction. Moreover, the performance of a chevron
plate will also depend upon the surface enlargement factor (∅), the channel profile, the mean
channel spacing (b), the temperature dependent physical properties, and especially the variable
viscosity effects.

The second one is heat transfer analysis. In order to find heat transfer coefficient (h),
correlation of Nusselt number (Nu) and Reynold number (Re) is needed. The Reynolds number
based on channel mass velocity and the hydraulic diameter of the channel is defined as (1.10)

Re = Gc * Dh / 𝜇 (1.10)

Where the channel mass velocity is given by (1.11)

Gc = mch / Ncp * b * Lw (1.11)

Correlation empirical equation is needed. The correlation in the form of (1.12) are proposed by
Kumar and the values of constants C h and n are given in table 1.1 (Heat exchangers:Selection,
Rating and Thermal design 2nd ed, p. 395)

𝜇
Nu = Ch * Ren * Pr * (𝜇 )0.17 (1.12)
𝑤

Table 1.1. Constants for single-phase heat transfer and pressure loss calculation in gasketed-plate
heat exchanger (Heat exchangers:Selection, Rating and Thermal design 2 nd ed, p. 394).

10
Overall heat transfer coefficient under fouling conditions is calculated as (1.13)

1 1 1 𝑡
= + + + 𝑅𝑓ℎ + 𝑅𝑓𝑐 (1.13)
𝑈𝑓 ℎℎ ℎ𝑐 𝑘𝑤

The required heat duty (Q r) for cold and hot streams is defined as (1.14)

Qr = (𝑚̇ ∗ 𝐶𝑝)c *(Tc2 – Tc1 ) = (𝑚̇ ∗ 𝐶𝑝)h * (Th1 – Th2 ) (1.14)

On the other hand, the actually obtained heat duty (Q f) for fouled conditions is defined as (1.15)

Qf = U*Ae*F*∆𝑇𝑙𝑚 (1.15)

In order to find ∆𝑇𝑙𝑚 , equation (1.16) is defined as

(𝑇ℎ ,𝑖𝑛 −𝑇𝑐,𝑜𝑢𝑡 ) −(𝑇ℎ ,𝑜𝑢𝑡 −𝑇𝐶 ,𝑖𝑛 )


∆𝑇𝑙𝑚 = (𝑇ℎ ,𝑖𝑛 −𝑇𝑐,𝑜𝑢𝑡 )
(1.16)
ln (
(𝑇ℎ,𝑜𝑢𝑡 −𝑇𝐶 ,𝑖𝑛 )

For heat transfer analysis we are not given 𝑇𝑐,𝑜𝑢𝑡 . So that physical properties of water cannot be
decided. Hereby trial-error solution is needed to find the correct 𝑇𝑐,𝑜𝑢𝑡 . To determine the correct
one we need to check both the required heat of hot and cold fluid. From energy balance analysis,
the required heat of hot and cold fluid must be same. The calculation for trial-error solution stops
until it reaches the equality of the required heat of hot and cold fluid.

1.3. Assumptions;
 Physical properties are constant at 1 atm
 Heat loses to or from the surrounding are negligible.
 The kinetic and potential energy changes are negligible.
 The heat exchanger operates at steady-state conditions.
 No phase changes in the fluid streams.
 Wall thermal resistances are distributed uniformly.
 The velocity and temperature at the inlet of the heat exchanger on each fluid side are
uniform.
 The heat transfer area (A) is distributed uniformly on each fluid side.

11
 The cold and hot stream mass flow rate are same
 Number of passes is one pass

12
2. SAMPLE CALCULATIONS
2.1 Geometry Analysis

2
Ae  110m Lv  1.55m Lh  0.43m t  0.0006m Lc  0.38m Lw  0.63m
W
kw  16.5 Np  1
m K

The projected plate area

Lp  Lv  Lw  Lh  1.35m

2
A1 p  Lp Lw  0.851m

Single plate heat transfer area


2
A1    A1p  1.063m

The effective number of plates


Ae
Ne   103.469
A1

Total number of plates


Nt  Ne  2  105.469

The plate pitch

Lc 3
p   3.603 10 m
Nt

the mean channel flow gap


3
b  p  t  3.003 10 m

The one channel flow area


3 2
Ach  b  Lw  1.892 10 m

The channel hydraulic

2 b 3
Dh   4.805 10 m

13
Total number pf channel per pass

Nt  1
Ncp   52.234
2 Np

2.2 Heat Transfer Analysis

(Trial-error method)
assume Tco  40  273  313 K

Tci  15  273  288 K Thi  65  273  338 K Tho  40  273  313 K

water properties at 313/288 = 300.5 K


J 4 W kg
Cpc  4185.847   8.4 10 Pa s k  0.611 mc  140
kg  K m K s
2
Cpc  m K
Pr   5.748 Rfwat er  0.0000069
k W
waste properties
J
W Cpwast e  4200
kwast e  0.650 6 Prwast e  3.3 kg K
m K wast e  510 10 Pa s
3
 6 s K kg
Rfwast e  Rfwat er  6.9 10 mh  mc  140
kg s

The mass flow rate per channel


mc kg
mch   2.68
Ncp s
mch 3 kg
Gch   1.417 10 3 kg
Ach 2 Gcc  Gch  1.417 10
sm 2
sm

for hot fluid for cold fluid


Gch  Dh 4 Gcc Dh 3
Reh   1.335 10 Rec   8.103 10
wast e 

14
0
Table 10.6   45 Reh  100 Rec  100
ch  0.3 n  0.663
1
kwast e n 3 4 kg
hhot   ch  Reh  Prwast e  3.283 10 or hhot= 3.283x104 W/m2K
Dh 3
s K
1
k n 3 4 kg or hcold=2.669x104 W/m2K
hcold   ch  Rec  Pr  2.668 10
Dh 3
s K

The clean overall heat transfer coefficient

3
1 3 kg or 9.587 10 W/m2K
Uc   9.587 10
1 1 t 3
  s K
hcold hhot kw
The fouled overall heat transfer coefficient
1 3 kg
Uf   8.467 10
1 3
 Rfwast e  Rfwat er s K
Uc

T2  Th o  Tci  25K T1  Th i  Tco  25K

for counter current flow


LMT D  25K

the actual heat duties for clean and fouled surfaces

7
Qc  Uc Ae  LMT D  2.636 10 W

7
Qf  Uf  Ae  LMT D  2.328 10 W

The required heat


7
Qrh  mh Cpwaste  ( Thi  Tho)  1.47 10 W
7
Qrc  mc Cpc ( Tco  Tci)  1.465  10 W

Since Qrh and Qrc is almost same, then Tco assumption is acceptable

15
The safety factor
Qf
Cs   1.584
Qrh
The precent over surface design
OS  100 Uc ( Rfwast e  Rfwat er)  13.23

The cleanliness factor


Uf
CF   0.883
Uc

16
3 RESULTS AND DISCUSSONS

Objective of this project was to design a proper plate type heat exchanger. Several assumptions
were made while making the calculations. These assumptions are constant physical properties at
1 atm, negligible heat losses through the surroundings, negligible kinetic and potential energy
changes, operating at steady state, no phase changes, same mass flow rates and, uniform
temperature and velocity at the inlet of the heat exchanger. Calculation of this problem design
are separated by 2 analysis. The first one is geometry analysis and the second one is heat transfer
analysis. Geometry is analyzed by the given datas and calculations were made according to these
given datas. First of all projected length was calculated as 1.35 m and then projected area was
determined as 0.851 𝑚2 , by using this value single plate heat transfer area was calculated by
enlargement factor times projected area, enlargement factor,∅, is the defined as the ratio of the
developed length to the flat or projected length and found as 1.25. Up to here effective area and
single plate heat transfer area was calculated number of effective plates was found as 103.469 by
dividing effective area by single plate heat transfer area. Then total number of plates were found
as 105.469. After that plate pitch was determined as 3.603 ∗ 10−3 𝑚 and mean flow channel gap
was found by using that one as 3.003 ∗ 10−3 𝑚. The one channel flow area was determined by
using mean flow channel gap and found as 1.892 ∗ 10−3 𝑚2 hydraulic diameter was calculated
by 2 mean flow channel gap divided by enlargement factor and found as 4.805 ∗ 10−3 𝑚. Lastly
total number pf channel per pass was found as 52.234 and the geometry calculations were done.
In the heat transfer analyses in order to find heat transfer coefficient (h), correlation of Nusselt
number (Nu) and Reynold number (Re) is needed. The Reynolds number based on channel mass
velocity and the hydraulic diameter of the channel is defined as Re for hot fluid was determined
as 1.335 ∗ 104and 8.303 ∗ 103 for the cold fluid. Where the channel mass velocity is given by
𝑘𝑔
Gc 1.417 ∗ 103 𝑚2 ∗𝑠 for both hot and cold fluid. In calculation of Nusselt number Correlation

empirical equation is needed. The correlation in the form of (1.12) are proposed by Kumar and
the values of constants C h and n are given in table 1.1. This correlation gave us the heat transfer
𝑊 𝑊
coefficients directly by using Nusselt number as 3.283 ∗ 104 𝑚2 ∗𝐾 for hot 2.668 ∗ 104 𝑚2 ∗𝐾 for

cold fluid. By using these heat transfer coefficients, the overall heat transfer coefficient for hot
𝑊 𝑊
clean and fouled heat exchangers were found 9.587 ∗ 103 𝑚2 ∗𝐾 , 8.467 ∗ 103 𝑚2 ∗𝐾 respectively.

17
In the determination of Qr and Qf ∆𝑇𝑙𝑚 is required and for heat transfer analysis we are not
given 𝑇𝑐,𝑜𝑢𝑡 . So that physical properties of water cannot be decided. Therefore trial-error solution
is needed to find the correct 𝑇𝑐,𝑜𝑢𝑡 . To determine the correct one we need to check both the
required heat of hot and cold fluid. From energy balance analysis, the required heat of hot and
cold fluid must be same. The calculation for trial-error solution goes until it reaches the equality
of the required heat of hot and cold fluid. To be sure of the 𝑇𝑐,𝑜𝑢𝑡 value was acceptable Qrh and
Qrc was determined and found as 1.47 ∗ 107 𝑊 and 1.465 ∗ 107 𝑊 which is really close to each
other so that Tcout value that choosen is acceptable. After calculation of ∆𝑇𝑙𝑚 Qr and Qf was
calculated as 2.637 ∗ 107 𝑊, 2.328 ∗ 107 𝑊 respectively. Lastly the safety factor was calculated
by dividing Qf to Qrh and found as 1.584 and cleanless factor as 0.883. According to the
literature Process heat transfer, 1950, typical design are based on safety factor of 1.6 which is
closer to 1.58. Moreover, based on Heat Exchanger: Selection, Rating, and Thermal Design, 2 nd ,
Typical designs are based upon a cleanliness factor of 0.85 which is quite closer with our value.

18
4 CONCLUSION

After performing the required equations which are given in calculation part, it is seen that
each plate is corrugated to increase the surface area and maximize heat transfer. Within a plate
heat exchanger, the fluid paths alternate between plates allowing the two fluids to interact, but not
mix, several times in a small area. The data from the similar heat exchanger is used in order to
define the heat exchanger that is used in the project. The goal of the project is to understand the
characteristics and design of a plate heat exchanger. By geometry and heat transfer analysis, the
total number of plates, the actual with fouled surface and required heat duty are found as 105
plates, 2.63 x 107 W and 2.32 x 107 W, respectively. It is considered that no heat loss to
surroundings however in reality there should be heat loss, therefore, error due to this assumptio n
must be considered in real life applications.

19
5 REFERENCES
 Incropera, F. (2012). Principles of heat and mass transfer (7th ed.). Singapore: John
Wiley & Sons Singapore Pte.
 Leib, T., & Pereira, C. (2008). Perry's chemical engineers' handbook (8th ed.). New York:
McGraw-Hill.
 Kakaç. S. (Sadik). Heal exchangers : selection, rating. and thermal design / Sadik Kakaç,
Hongtan Liu.-. 2nd ed
 Kern, “Process heat transfer”, McGraw Hill, 1950

20