1. All kinds of Yun-Yang Addressable
Fire Alarm Control Panel
Price
Service
2. Addressable Fire Alarm System
Framework Chart Network
Broadcast Connection Addressable Fire Other Addressable capability of
up to 8
Point Module Alarm Control Control Panels panels for
Connect to a maximum of Panel (FACP) Addressable FACP total of16384
points
16 Annunciators with touch screen
Communication
Module (LOOP2) (LOOP3) (LOOP4) (LOOP5) (LOOP6) (LOOP7) (LOOP8)
(LOOP1)
Possible for
branch wiring
◎ Annunciator Functions
a. Fire indicator, power indicator, communication error
indicator, error indicator, line indicator, local telephone
indicator, voltmeter, main voice buttons, operation
YFR-S1
buttons, reset button.
b. LCD backlight protection function
c. Sound synthesis alarm function
d. Modules’ status chart
Quality
Price
Service
4. High-rise Building Control Panel
YFR-CCM
◎Cost saving fire prevention center control module
Modularity design, easy to install and maintain , no
need for additional wiring and addressable
equipments, saving user’s cost and time.
YFR-CCM Quality
Price
Service
High-rise Building Control Panel
FACP
D Module
twisted pair
C.Activation
Light
B.Key-pressed
設備動作確認燈 設備動作確認燈
開關確認燈 開關確認燈
Light
Loop indicator
A.Activation
設備啟動開關 設備啟動開關
Button
Price
Service
5. Broadcast Reporting Module (YFR-OP40/OP80)
Item Specification
Product
Broadcast Reporting Module
name
80 connection points,
Function
40 connection points expandable to 2040 connection
explanation
points
Compatible
Yun-Yang YFR-1 R-Type Control Panel Series
system
Applicable Emergency Broadcast Host, Monitoring/Controlling
equipment System, LED panel
Power
DC24V/ by Addressable Control Panel supplies
Supply
Transmission
RS-485 bus to connect to panels
Method
Output 500mA/DC30V
Quality
Price
Service
7. Addressable Communication Module / Module
and Detector Introduction
Quality
Price
Service
7.a. Communication Module YSC-05
Functions Explanation
Communication Module Segment - Isolation Function
S+ S- Base to
connect to modules
and addressable
detectors
Able to isolate
addressable
equipments based on
groups of 50 points,
make it easy for wire-
checking
7.b. Monitor/ Control (Voltage Output) Module
Functions:
YRR-02 (YRR-0602 Short-circuit Isolation Function)
On-board status indicators for “Monitoring,” Activate,” “Error”DC24V
and “Isolating.” Input DC24V Output :
Address coding by binary coded dip switch for easier setting COM: (No Voltage
Two-wires multi-transmission Contact)
24V 0V COM NO NC
Stable communication with rejection to noise and NO: ( Close on Action /
disturbances
Module Base Normally Open
Self-test functions for circuit disconnection and activation S+ S- A L C M+ Contact)
Expandable to connect with photoelectric smoke, rate of NC: (Open on Action/
rise heat and fixed temperature heat detectors, and no need Normally Close
for external power supply Contact)
DC24V voltage control output, can connect directly to C , M: Confirmation Function
equipments, action confirmation, communication functions Addressable
Loop Signal, Ex: Return Signal that Confirm
Light indication pattern ( fire: red light constantly on, Gate is in Open Position
disconnection: red light flashing, monitoring: red light cannot reverse
positive and L ,C monitor equipments or connect to
flashing once per 2.5s)
negative pole conventional detector, relay function
Alumina rail lock structure, easy to install setting, must use R-type EOL resistor
When short-circuit happens, auto-isolate the error part with
the main communication line (only YRR-0602 series have
this function)
Function Circuit Input and Voltage Control Output Binary
Dip
EOL Resistor Below 10 Ω / master line Switch
Ambient Temperature -10℃ ~ 50℃ Relative Humidity below 95 %
Monitored Current 420μA/DC24V
Output Voltage DC24V
Operating Voltage DC16~30V
Material Fire-proof plastic
Dimension 80(L)×60(M)×30(H)mm
Note Addressable professional EOL resistor
7.c. Monitor Module
YRR-01 / YRR-0601(Short Circuit Isolation Function)
Functions:
Status indicators for “Monitoring,” Activate,” “Error” and
“Isolating.”
Address coding by binary coded dip switch for easier setting
Two-wires multi-transmission Module Base C , M: Confirmation
Stable communication with rejection to noise and S+ S- A L C M+ Function
disturbances Ex: Return Signal
Self-test functions for circuit disconnection and activation that Confirm Gate is
Expandable to connect with photoelectric smoke, rate of in Open Position
rise heat and fixed temperature heat detectors, and no need
for external power supply Addressable Loop L ,C monitor equipments or connect
Light indication pattern ( fire: red light constantly on, Signal, cannot to conventional detector, relay
disconnection: red light flashing, monitoring: red light reverse positive and
function setting, must use R-type EOL
flashing once per 2.5s) negative pole resistor
Alumina rail lock structure, easy to install
When short-circuit happens, auto-isolate the error part with
the main communication line (only YRR-0601 series have
this function)
Quality
Price
Service
7.f. Isolation Module YRR-21 Wiring
24V 0V COM NO NC COM NO NC
Module Base
(OUT) Module Base Module Base Module Base
Terminal Base (IN)
S+ S- S+ S- S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+
S-
Indicating Lamp +
L Indicating Lamp
L1 L2 S+
L1 L2 S+
L1 L2 S+
S-
S-
S-
Indicating Lamp -
C1 C2
C1 C2
C1 C2
Telephone T
Addressable Detector
Addressable Detector Addressable Detector
Telephone TC
Buzzer)
{
(Local Bell,
DC 0 V - Module Base
(IN)
S+ S-
(OUT)
S+ S- S+ S- A
COM NO NC
Module Base
L C M+ S+ S-
Module Base
A L C M+
Price
Service
8.a. Monitor/Control Module (YRR-02) + Bell
Monitor/Control Module
4
5
(YRR-02 A1)
24V 0V COM NO NC Simple, Easy
Module Base Wiring
S+ S- A L C M+
Terminal Base 1
Local Bell
DC24V
S+
Bell
S- 2
Indicating lamp +
L Indicating lamp
Indicating lamp - 3 T
A
L
Telephone T TC LC EOF
EOL Equipment
TelephoneTC
S
Power Supply DC 24V +
Buzzer)
{
( Local Bell,
DC 0 V -
Wiring Notes:
1. S+, S- Communication Contacts
Power DC 24V + 2. L , C connect to conventional detector and manual call point contacts. A
Supply
(Gate) { DC 0 V - professional EOL equipment is needed in the terminal, not a normal
Pumper 10KΩ one
AC 220V
Light {
Start-up
AC 220V
RL Pumper Start-up Light (If Bell’s A contact connects to Module’s A contact, there will be no
accumulation)
AC 110V 3. Fire Manual Call Point’s TC contact cannot connect to Module’s C
Power
Supply
(Gate)
{ AC 110V contact
4. On-board DC24V input, control voltage output, can directly
connect to the bell
5. Wiring bells is simple and easy
8.b. Monitor Module (YRR-01)
Monitor Module
(YRR-01 A3) Wiring Notes:
Module Base
S+ S- A L C M+
1. S+, S- Communication Contacts
Terminal Base 1
2. L , C connect to conventional
S+
detector and manual call point
S- 2 contacts. A professional EOL
Indicating Lamp +
equipment is needed in the
L terminal, not a normal 10KΩ one
Indicating Lamp - Indicating Lamp
Telephone T 3. Fire Manual Call Point’s TC contact
cannot connect to Module’s C
A
T L
Telephone TC EOF
TC LC
EOL Device
contact (If Bell’s A contact
Load DC 24V + connects to Module’s A contact,
Power
(bells,
{
DC 0 V -
S
there will be no accumulation)
buzzers)
DC 24V +
Load
Power
(Gate)
{
DC 0 V -
4. When there is no bell, use monitor
module for fire alarm complex
AC 220V
Pump
Activated
Light
{AC 220V
RL
Pump Activated Light
AC 110V
Load
Power
(Gate)
{AC 110V Quality
Price
Service
8.c. Addressable Manual Call Point (YRR-04)
Terminal Block 1
S+ S- S+
C T
S-
4 3
TC
Indicating Lamp +
NO A Build-in A Contact
L
Indicating Lamp - Indicating Lamp L+ LC
Telephone T
2
Telephone TC
Bell
Load DC 24V + DC24V
Power
(bells,
{
DC 0 V -
Bell
buzzers) EOF
DC 24V +
Load
Power
(Gate)
{
DC 0 V - S
EOL Device
Pump AC 220V
Activated
Light {AC 220V
RL
Pump Activated Light
AC 110V
Load
Power
(Gate)
{AC 110V
Wiring Notes:
1. S+, S- Communication Contacts
2. Connect to conventional detectors, L+ to L+, LC to LC. A professional EOL equipment is needed in the terminal, not a
normal 10KΩ one
3. Fire Manual Call Point’s TC contact cannot connect to Module’s C contact (A contact is built-in with no accumulation)
4. On-board control output (COM,NO) that can connect to bells
8.d. Solenoid Valve (DC 24V) +
Monitor/Control Module YRR-02
DC24V Output
DC24V Input
Terminal Block
S+
S-
24V 0V COM NO NC
Indicating Lamp + Module Base
L S+ S- A L C M+ To Solenoid Valve Contacts
Indicating Lamp -
Indicating Lamp Solenoid Valve
Telephone T DC24V
TelephoneTC
AC 110V
Load
Power
(Gate)
{AC 110V Wiring Notes:
1. DC24V Input provides DC24V for Control Output
2. Voltage Control Output, when action, provides power to activate
Solenoid Valve (COM, NO contacts, DC24V)
8.e. Solenoid Valve (DC 110V) + Monitor/Control
Module YRR-02 + Relay Module RY-01
DC110V
EOL Device
Solenoid Valve
NO
Activated Power Output
Load Power DC 24V + S
(Bells, { 2
NC
Buzzers) DC 0 V - H2 H1 - - + +
DC24V IN/OUT To Module
3
COM COM
DC 24V +
Load
Power
(Gate)
{
DC 0 V -
1 RY-01
Pump
Power Input
AC 220V
Activated
Activated
Light {AC 220V
RL
4
IN
Pump Activated Light
AC 110V
Load
Power
(Gate)
{AC 110V
8.f. Magnetic Lock (DC 24V ) +
Monitor/Control Module YRR-02
DC24V Output
DC24V Input
Terminal Block
S+
S-
24V 0V COM NO NC
To Lock Contacts
Indicating Lamp + Module Base
L S+ S- A L C M+
Indicating Lamp - To Lock Close Confirmation
Indicating Lamp
(Optional Function)
Telephone T
Telephone TC
AC 110V
Load
Power
(Gate)
{AC 110V
Wiring Notes:
1. DC24V Input provides DC24V for Control Output
2. Voltage Control Output, when action, provides power to activate Magnetic
Lock (COM, NO contacts, DC24V)
3. To Lock Close Confirmation: C, M to Lock Close Contact for
returning confirmation signal
8.g. Magnetic Lock (DC 110V) + Monitor/Control
Module YRR-02 + Relay Module RY-01
Wiring Notes:
1.To Module: Fire
Monitor/Control Module reporting signal
come to Relay
(YRR-02)
Module and
COM NO NC activate the
Module Base 5 Output Voltage
S+ S- A L C M+
Terminal Block To Magnetic Lock Close Confirmation 2. Provide DC24V:
(Optional Function) for Relay
S+
Module to
S- activate
Indicating Lamp + operating
L
Indicating Lamp - Indicating Lamp Lock (Fire-proof Gate)
must provide A No-Voltage Contact
3. Activated Power
Telephone T Input: AC110V
Relay Module (AC110V)
Telephone TC
EOF Input
EOL Device 3
To Lock Contacts
NO
Activated Power Output
Load Power DC 24V + S 4. Activated Power
(Bells, { 2 Output: provide
NC
Buzzers) DC 0 V - H2 H1 - - + +
DC24V IN/OUT To Module AC110V for
COM COM
DC 24V +
Load
Power
(Gate)
{
DC 0 V -
1 RY-01
Magnetic Lock
when action
Power Input
Pump AC 220V
{ 5. To Lock Close
Activated
Activated RL 4
Light AC 220V Confirmation: C,
IN
Pump Activated Light
AC 110V M to Lock Close
Load
Power
(Gate)
{AC 110V Contact for
returning
confirmation
signal
8.h. Pressure Switch for Water-Based Fire Protection
System (Mist, Foam, Sprinkler ) + Buzzer +
Monitor/Control Module YRR-02
DC24V Input DC24V Output, easy
and simple wiring
Terminal Block
S+
S- 24V 0V COM NO NC
Module Base
Indicating Lamp +
S+ S- A L C M+
L
Indicating Lamp -
Indicating Lamp
Buzzer
Telephone T DC24V
Telephone TC
DC 24V +
Load
Power
(Gate)
{
DC 0 V -
AC 220V
Pump
Activated
Light
{AC 220V
RL
Pump Activated Light
C/NO contacts
AC 110V
Load
Power
(Gate)
{AC 110V
To non polarized pressure switch, a
professional EOL device is needed, not a
normal 10KΩ one
8.i. Smoke Extraction System – Shutter (DC24V) +
Monitor/Control Module YRR-02
Terminal Block DC24V Input To Shutter Switch
S+
S-
NO
need a professional
2 DC24V IN/OUT
To Module
3 EOL device
Pump AC 220V
{
C
AC 110V Activation
Load
Power
(Gate)
{ AC 110V
Relay Module for Windmill Confirmation Contact
for returning
confirmation signal
9. Addressable Detector Wiring Instruction
Quality
Price
Service
9.1.a. Addressable Detector Base YRR-03
Functions:
Status indicators for “Monitoring,” Activate,”
“Error” and “Isolating.”
Address coding by binary coded dip switch for
easier setting
Two-wires multi-transmission
Stable communication with rejection to noise
and disturbances
Self-test functions for circuit disconnection and
activation
Expandable to connect with photoelectric
smoke, rate of rise heat and fixed temperature
heat detectors, and no need for external
power supply
Function Circuit Input
EOL Resistor Below 10 Ω / master line
Ambient Temperature -10℃ ~ 50℃ Relative Humidity below 95 %
Monitored Current 420μA/DC24V
Operating Voltage DC16~30V
Material Fire-proof plastic
Dimension 108 x 22.6 mm
Note Addressable professional EOL resistor
Quality
Price
Service
9.1.b. Addressable Detector Base (YRR-03)
Wiring Instruction
To
Conventional L+
Detector’s L2
S+
Contacts LC To Addressable
Connect a Detectors, Module, or
professional Communication
10KΩ at the Module, S+ to S+
terminal S- to S-
C2 S-
Binary
Code Dip
Quality
Price
Service
9.1.c. Addressable Detector Base YRR-03
Wiring Application
Wiring Notes:
1. Addressable Detector Base’s L+ LC connect to Conventional Detectors’
L+ LC, polarized.
2. Provided current is not over 1.3mA/DC24V
3. A professional terminal device is needed, cannot use a normal 10KΩ
A
Professional
EOL Device
To Addressable FACP
S+ S- Conventional ROR Heat Fixed Heat
Smoke Detector Detector Detector
Telephone TC
(Cut-off when connect to conventional detectors)
Load Power DC 24V +
(Bells,
Buzzers)
{
DC 0 V -
L1 L2 S+ L+ L+ L+ L+ L+ L+
DC 24V +
Load
Power
(Gate)
{
DC 0 V - C1 C2 S-
LC LC LC LC LC LC
EOF
EOL Device
AC 220V
Pump
Activated
Light
{AC 220V
RL
Pump Activated Light
Add. Detector Conventional Detectors
AC 110V
Load
Power
(Gate)
{AC 110V Modules/ Add. Detectors provide a current of 1.3mA/DC24V per
loop, please calculate the number of conventional detectors that
can be connected by the real total of current consumption. No
limit for non-electric detectors.
9.3. Addressable Rate of Rise Heat
Detector YRR-11
Functions:
Address coding by binary coded dip switch for easier setting
Two-wires multi-transmission
Expandable to connect with photoelectric smoke, rate of rise heat and fixed temperature heat
detectors, and no need for external power supply
It reacts sensitively with rapidly temperature rises
Employ mechanical operating principle for long-term durability
Auto reset to original status after activated for reusing
High-quality parts are used to ensure the functional reliability
The detector is made of flameproof and high temperature-resistant plastic with elegance design
Price
Service
9.4. Addressable Fixed Temperature
Functions:
Heat Detector YRR-12
Address coding by binary coded dip switch for easier setting
Two-wires multi-transmission
Expandable to connect with conventional detectors
Adopt UL-certified temperature sensor with better quality and durable maintenance
Auto reset to original status after activated for reusing
Sealed sensor is to avoid moisture and dust entering and affecting the performance
The electric contacts made of pure silver can respond sensitively
The detector is made of flameproof and high temperature-resistant plastic with elegance design
Price
Service
9.5. Addressable Photoelectric
Smoke Detector YRR-13
Functions:
Address coding by binary coded dip switch for easier setting
Two-wires multi-transmission
Expandable to connect with conventional detectors
With the function of photoelectric sensor, it can act rapidly and accurately with high stability.
Moreover, there is no false alarm due to chemicals, exhaust gas, wind and exterior light
Stainless steel insect-proof nets of holes' diameter 0.5 mm ensure smooth inflow of smoke but
preventing from insects or dust
The detector is reusable and easy maintenance. Remove the cover to clean the interior
With the compact styling and pretty outlines, the detector can enhance ceilings decoration design
and visual effect
The detector is made of flameproof and high temperature-resistant plastic with elegance design
Dimensions 108*43mm
Quality
Price
Service
10.1. Addressable Fire Alarm Control Panel Inside
Base and Terminal Block Wiring Introduction
S+
S-
Indicating Lamp - L
Indicating Lamp
Telephone T
Telephone TC
K5
K1
T + + +
J4 J3
SW3
J2
SW2
J1 SW1
Load Power
(Gate) { AC 110V
AC 110V
Terminal Block
- - -
TC 0V 24V
Call DC 24V Load Indicating
Phone Point Resettable Power Lamp Reporting BATT AC-OUT AC-IN
~
Standby Battery AC Input
DC24V
To Pump Activation Panel
10.2. Addressable Fire Alarm Control
Panel Terminal Block Wiring Instruction
COM NO NC
C1 C2
Module Base Module Base
Terminal Block Terminal Block
L1 L2 S+
S+ S- A L C M+ S+ S- A L C M+
S-
EOF EOF
S+ EOL Device EOL Device S+
S- S-
Indicating Lamp + Indicating Lamp +
L Indicating Lamp L
Indicating Lamp - Indicating Lamp -
Indicating Lamp
Telephone T Telephone T
Telephone TC Telephone TC
DC 24V + DC 24V +
Load Power
(Gate)
{ DC 0 V -
Load Power
(Gate) { DC 0 V -
AC 110V AC 110V
Load Power
(Gate) { AC 110V
Load Power
(Gate) { AC 110V
11. Addressable FACP –
Signaling Line Circuit (SLC)
Wiring Introduction
Price
Service
11.1. Signal Line Circuit (SLC)
Standard Wiring Instruction
Standard Wiring uses Parallel Connection Method for easier trouble-
shooting procedure and convenience
a. Class A (style 6 & 7): Dual Direction Power Supply
Note:Should one end breaks off, the other end can supply power, modules and
detectors are active (normal signal)
Communication
Module
24V 0V COM NO NC COM NO NC COM NO NC
s+ s+ s- s- Module Base Module Base Module Base Module Base
S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+
L1 L2 S+
L1 L2 S+
L1 L2 S+
L1 L2 S+
S-
S-
S-
S-
S-
C1 C2
C1 C2
C1 C2
C1 C2
C1 C2
Add. Detector Add. Detector Add. Detector Add Detector Add. Detector
11.1. Signal Line Circuit (SLC)
Standard Wiring Instruction
Standard Wiring uses Parallel Connection Method for easier trouble-shooting
procedure and convenience
b. Class B (style 4): Single Direction Power Supply
Note: Should one end breaks off, every device down stream of the break will be
unavailable (trouble signal)
Communication
Module
24V 0V COM NO NC COM NO NC COM NO NC
s+ s+ s- s- Module Base Module Base Module Base Module Base
S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+
L1 L2 S+
L1 L2 S+
L1 L2 S+
L1 L2 S+
S-
S-
S-
S-
S-
C1 C2
C1 C2
C1 C2
C1 C2
C1 C2
Add. Detector Add. Detector Add. Detector Add. Detector Add. Detector
11.2 . SLC Branch Wiring
Instruction
Note: As requirements at the construction site, branch wiring may be adopted; however, should
not be branched more than 15 areas per loop and should be noted clearly in the block diagram
for easier trouble shooting procedure
Communication
Module 24V 0V COM NO NC COM NO NC COM NO NC
s+ s+ s- s- Module Base Module Base Module Base Module Base
S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+ S+ S- A L C M+
L1 L2 S+
L1 L2 S+
L1 L2 S+
L1 L2 S+
S-
S-
S-
S-
S-
C1 C2
C1 C2
C1 C2
C1 C2
C1 C2
Add. Detector Add. Detector Add. Detector Add. Detector Add. Detector
Price
Service
12. Addressable Fire Alarm
Control Panel Design Notification
9. Fire Manual Call Point’s Telephone contact TC cannot connect to Module’s C
contact
10.Addressable Device’s Terminals need a professional EOL Device, cannot use a
normal 10K resistor.
11.Addressable manual call point’ communication line adopts 2.0mm -1 pr PE
Aluminum Foil Shielded Twisted Pair
12.Control Module COM.NC.NO. contacts’ capacities are DC30V 2A, please use
proper devices. A Relay Module RY-01/02 is needed when connecting to
higher devices
13.Relay Module RY-01’s COM.NC.NO contacts are Voltage contacts, while
RY-02’s H1.H2 are dry contacts, which capacity is AC277V 16A, please
wiring proper devices . Please check Solenoid Valve’s voltage and current
before using. If they are higher than the capacity described above, an external
appropriate control module is needed to ensure a normal operation for the
system