Hz 63 125 250 500 1000 2000 4000 8000

L1 L2 L3 L4 L5 L6 L7 L8
0 1 2 3 3 3 3 3 APS 195 2d
10L/10 1 1.2589 1.5849 1.9953 1.9953 1.9953 1.9953 1.9953

Σ10L/10 13.82
3.5
10logΣ10L/10 11.4 dB
3 4 5 6 7 8

2.5
Hz dB 2 3
Column
1 63 0 1.5
D

2 125 1
1 2
3 250 2
0.5
4 500 3
5 1000 3 0 1
0 1 2 3 4 5 6 7 8
6 2000 3
7 4000 3
8 8000 3
Chiller R1

If manufacturer provide sound power leve Lw then subtract 21.5 dB to have sound
pressure level Lp at 3 m .
Lp1=Lp2+10.log10(X/R1)2

Manufacturer Lw = 90.000 dB Power


Manufacturer Lp(3m) = 68.500 dB Pressure

x Reduction Lp(x)
3 0 69
10 10 58 Note the reduction is very effective for the first 10 m
15 14 55
20 16 52
25 18 50
30 20 49
35 21 47 Note the reduction after 35 m starts to reduce slowly
40 22 46
45 24 45
50 24 44
55 25 43
60 26 42
65 27 42
70 27 41
75 28 41
80 29 40
85 29 39
90 30 39
95 30 38
100 30 38
105 31 38
110 31 37
Chiller sound Power level 100 dB

R1

85.0
80.0
75.0
70.0
65.0
60.0
55.0
50.0
45.0
Sound Pressue dB depression in outside space 40.0
35.0
30.0
25.0
20.0
15.0
10.0
5.0
0.0
0 10 2 0 30 40 5 0 60 7 0 80 9 0 0 0
1 1
Distance from ch

If manufacturer provide sound power leve Lw then subtract 21.5 dB to have sound pre
Lp1=Lp2+10.log10(R2/R1)2

R1 3 m
R2 100 m
R2/R1 33.333333
Attenuation 30.5
R1 R2 Chiller Lw Chiller Lp(3m) Chiller Lp at R2
m
3 3 0.0 100 80 80.0
8 8.5 71.5 Wall
13 12.7 67.3
18 15.6 64.4
23 17.7 62.3
28 19.4 60.6
33 20.8 59.2
38 22.1 57.9
43 23.1 56.9
48 24.1 55.9
53 24.9 55.1
58 25.7 54.3
63 26.4 53.6
68 27.1 52.9
73 27.7 52.3
78 28.3 51.7
83 28.8 51.2
88 29.3 50.7
93 29.8 50.2
98 30.3 49.7 Wall
103 30.7 49.3
108 31.1 48.9
113 31.5 48.5
118 31.9 48.1
123 32.3 47.7
128 32.6 47.4
133 32.9 47.1
138 33.3 46.7
143 33.6 46.4
148 33.9 46.1
153 34.2 45.8
158 34.4 45.6
163 34.7 45.3
168 35.0 45.0
173 35.2 44.8
178 35.5 44.5
183 35.7 44.3
188 35.9 44.1
193 36.2 43.8
198 36.4 43.6
203 36.6 43.4
208 36.8 43.2
Chiller sound Pressure @3m level
79 dB
( subtract 21 from power level to obtain pressure level )

Column F

0 2 0 30 40 5 0 60 7 0 80 9 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 0 0 1 0 2 0
1 1 1 1 1 1 1 1 1 1 2 2 2
Distance from chiller in meters

.5 dB to have sound pressure level Lp at 3 m .


3m or less

subtract 3 dB from the result

30.5 - 3= 27.46

3m or less

3m or less

subtract 3 dB from the result

30.5 - 6= 24.46
R1
AHU

R2

If manufacturer provide sound power leve Lw then subtract 21.5 dB to have sound pre

Lp1=Lp2+10.log10(R2/R1)2

R1 3 m
R2 100 m
R2/R1 33.333333
Attenuation 30.5
R1 R2 Chiller Lw Chiller Lp(3m) Chiller Lp at R2
m
3 3 0.0 80 60 60.0
8 8.5 51.5 Wall
13 12.7 47.3
18 15.6 44.4
23 17.7 42.3
28 19.4 40.6
33 20.8 39.2
38 22.1 37.9
43 23.1 36.9
48 24.1 35.9
53 24.9 35.1
58 25.7 34.3
63 26.4 33.6
68 27.1 32.9
73 27.7 32.3
78 28.3 31.7
83 28.8 31.2
88 29.3 30.7
93 29.8 30.2
98 30.3 29.7 Wall
103 30.7 29.3
108 31.1 28.9
113 31.5 28.5
118 31.9 28.1
123 32.3 27.7
128 32.6 27.4
133 32.9 27.1
138 33.3 26.7
143 33.6 26.4
148 33.9 26.1
153 34.2 25.8
158 34.4 25.6
163 34.7 25.3
168 35.0 25.0
173 35.2 24.8
178 35.5 24.5
183 35.7 24.3
188 35.9 24.1
193 36.2 23.8
198 36.4 23.6
203 36.6 23.4
208 36.8 23.2
.5 dB to have sound pressure level Lp at 3 m .

3m or less

subtract 3 dB from the result

30.5 - 3= 27.46

3m or less

3m or less

subtract 3 dB from the result

30.5 - 6= 24.46
63 125 250 500 1k 2k 4k

80.00 80.00 80.00 88.00 84.00 78.00 65.00 Chiller sound


Chiller Pressure dB @ 3m

200 mm CMU*
35 35 41 44 50 57 64

150 mm solid concrete floor with 100 mm isolated concrete slab and fiberglass insulation in cavity
44 52 58 73 87 97 100

No selection
0 0 0 0 0 0 0
Space

1.00 -7.00 -19.00 -29.00 -53.00 -76.00 -99.00 Pressure dB


i
100.00
SOURCE
NC-65
NC-60
50.00
NC-55
NC-50
0.00 NC-45
63 125 250 500 1000 2000 4000 NC-408000
NC-35
-50.00 NC-30
NC-25

-100.00

-150.00

STC 63 125 250 500 1000 2000 4000


No selection 0 0 0 0 0 0 0

200 mm CMU*
50 35 35 41 44 50 57 64
200 mm CMU with 16 mm GWB* on furring strips
53 33 32 44 50 56 59 65
16 mm GWB on both sides of 92 mm metal studs
38 18 16 33 47 55 43 47
16 mm GWB on both sides of 92 mm metal studs with
fiberglass insulation in cavity 49 16 23 44 58 64 52 53
2 layers of 16 mm GWB on both sides of 92 mm metal studs
with fiberglass insulation in cavity 56 19 32 50 62 67 58 63
Double row of 92 mm metal studs, 25 mm apart, each with 2
layers of 16 mm GWB and fiberglass insulation in cavity 64 23 40 54 62 71 69 74
150 mm solid concrete floor/ceiling
53 40 40 40 49 58 67 76
150 mm solid concrete floor with 100 mm isolated concrete
slab and fiberglass insulation in cavity 72 44 52 58 73 87 97 100
150 mm solid concrete floor with two layers of 16 mm GWB
hung on spring isolators with fiberglass insulation in cavity 84 53 63 70 84 93 104 105

GWB : gypsum wall board

tile thickness
kg/m2 mm 63 125 250 500 1k 2k 4k
No selection 0 0 0 0 0 0 0
Mineral fiber 4.9kg/m2 16 mm thickness 4.9 16 -13 -16 -18 -20 -26 -31 -36
Mineral fiber 2.4kg/m2 16 mm thickness 2.4 16 -13 -15 -17 -19 -25 -30 -33
Glass fiber 4.9 kg/m2 16 mm thickness 4.9 16 -13 -16 -15 -17 -17 -18 -19
Glass fiber 2.9 kg/m2 50 mm thickness 2.9 50 -14 -17 -18 -21 -25 -29 -35
Glass fiber with TL backing 2.9 kg/m2 50 mm thickness 2.9 50 -14 -17 -18 -22 -27 -32 -39
Gypsum board tiles 8.8 kg/m2 13 mm thickness 8.8 13 -14 -16 -18 -18 -21 -22 -22
Solid gypsum board ceiling 8.8 kg/m2 13 mm thickness 8.8 13 -18 -21 -25 -25 -27 -27 -28
Solid gypsum board ceiling 11.2 kg/m2 16 mm thickness 11.2 16 -20 -23 -27 -27 -29 -29 -30
Double layer of gypsum board 18.1 kg/m2 25 mm thickness 18.1 25 -24 -27 -31 -31 -33 -33 -34
Double layer of gypsum board 22 kg/m2 32 mm thickness 22 32 -26 -29 -33 -33 -35 -35 -36
Mineral fiber tiles, concealed spline mount 2.4-4.9 kg/m2 16 mm thicknes 2.4 to 4.9 16
NC-25 -20 -23 -21 -24 -29 -33 -34
60

50

40
63 125 250 500
NC-25 1k 2k 4k 8k
30 NC-25 54 44 34 31 28 25 24 22
NC-30 57 48 42 35 31 30 29 27
20 NC-35 60 52 45 40 36.4 35 34 32
NC-40 64 56 50 45 41 39 38 37
10 NC-45 68 60 54 49 46 44 43 42
NC-50 71 64 58 54 51 49 48 47
0 NC-55 74 67 62 59 56 54 53 52
0 100
NC-60 200 77 300 40071 500 600
68 64 61 59 58 57
NC-65 80 75 71 69 66 64 63 62
Source : kinaticnoise : acoustic inclousure for air cooled screw compressor

63 125 250 500 1k 2k 4k

80 80 80 88 84 78 65 Chiller sound pressure data dB @ 3m

#N/A #N/A #N/A #N/A #N/A #N/A #N/A Roof insertion

0 0 0 0 #N/A #N/A #N/A #N/A #N/A #N/A #N/A Roof insertion

#N/A #N/A #N/A #N/A #N/A #N/A #N/A

#N/A #N/A #N/A #N/A #N/A #N/A #N/A Ceiling insertion

#N/A #N/A #N/A #N/A #N/A #N/A #N/A Space dB


63 125 250 500 1000 2000 4000 8000

Carrier 42CE@ 1200 cfm ,Lw 79 78 75 76 73 68 67 63


1 Enviromental corrction -4 -2 -1 0 0 0 0 0
2 Source Area Effect 1 1 1 0 0 0 0 0
3 Ceiling insertion Solid gypsum board ceiling 8.8 kg/m2 -14 -16 -18 -18 -21 -22 -22 -22
Room Lp ( uniform to 5m) 62 61 57 58 52 46 45 41

NC-25 54 44 34 31 28 25 24 22
NC-30 57 48 42 35 31 30 29 27
NC-35 60 52 45 40 36.4 35 34 32
NC-40 64 56 50 45 41 39 38 37
NC-45 68 60 54 49 46 44 43 42
NC-50 71 64 58 54 51 49 48 47
NC-55 74 67 62 59 56 54 53 52
NC-60 77 71 68 64 61 59 58 57
NC-65 80 75 71 69 66 64 63 62

90
SOURCE
80 NC-65
NC-60
70
NC-55
60 NC-50
NC-45
50
NC-40
40 NC-35

30 NC-30
NC-25
20

10

0
63 125 250 500 1000 2000 4000 8000
NC-25
20

10

0
63 125 250 500 1000 2000 4000 8000
tile thickness
kg/m2 mm
63 125 250 500 1000 2000 4000
Mineral fiber 4.9kg/m2 4.9 16 -13 -16 -18 -20 -26 -31 -36
Mineral fiber 2.4kg/m2 2.4 16 -13 -15 -17 -19 -25 -30 -33
Glass fiber 4.9 kg/m2 4.9 16 -13 -16 -15 -17 -17 -18 -19
Glass fiber 2.9 kg/m2 2.9 50 -14 -17 -18 -21 -25 -29 -35
Glass fiber with TL backing 2.9 kg/m2 2.9 50 -14 -17 -18 -22 -27 -32 -39
Gypsum board tiles 8.8 kg/m2 8.8 13 -14 -16 -18 -18 -21 -22 -22
Solid gypsum board ceiling 8.8 kg/m2 8.8 13 -18 -21 -25 -25 -27 -27 -28
Solid gypsum board ceiling 11.2 kg/m2 11.2 16 -20 -23 -27 -27 -29 -29 -30
Double layer of gypsum board 18.1 kg/m2 18.1 25 -24 -27 -31 -31 -33 -33 -34
Double layer of gypsum board 22 kg/m2 22 32 -26 -29 -33 -33 -35 -35 -36
Mineral fiber tiles, concealed spline mount 2.4-4.9 kg/m2 2.4 to 4.9 16 -20 -23 -21 -24 -29 -33 -34