Operation
Maintenance
Series R™ Air-Cooled Helical Rotary
Liquid Chiller
Models
RTAD 85 - 125 (50Hz)
RTAD-SVX01A-E4
©American Standard Inc. 2001 RTAD-SVX01A-E4
Contents
General Information 7
Literature History 7
Unit Inspection 7
Inspection Checklist 7
Loose Parts Inventory 7
General Data 8
Unit Dimensions 9
Installation - Mechanical 10
Warnings and Cautions 10
Installation Responsibilities 10
Nameplates 10
Storage 10
Location Requirements 10
Setting the Unit 10
Isolation and Sound Emission 11
Noise Considerations 11
Foundation 11
Clearances 11
Unit Isolation and Leveling 11
Neoprene Isolator Installation 11
Drainage 12
Evaporator Water Piping 12
Evaporator Piping 12
Entering Chilled Water Piping 12
Leaving Chilled Water Piping 12
Evaporator Drain 12
Evaporator Flow Switch 12
Water Treatment 12
Water Pressure Gauges 13
Water Pressure Relief Valves 14
Freeze Protection 14
RTAD-SVX01A-E4 3
Contents
Installation - Electrical 15
General Recommendations 15
Installer-Supplied Components 16
Power Supply Wiring 16
Control Power Supply 17
Heater Power Supply 17
Water Pump Power Supply 17
Interconnecting Wiring 17
Chilled Water Flow (Pump) Interlock 17
Chilled Water Pump Control 17
Alarm and Status Relay Outputs (Programmable Relays) 17
Low Voltage Wiring 19
External Emergency Stop 19
External Auto/Stop 19
External Circuit Lockout - Circuit 1 and Circuit 2 19
Ice Making Option 19
External Chilled Water Setpoint (CWS) 20
External Current Limit Setpoint (CLS) 20
Outdoor Air Temperature Sensor 20
Communication Card CSR 21
Communication link connection procedure 21
Operating Principles 22
System schematic 22
Pre-Start Checkout 23
Installation Checklist 23
Receiving 23
Unit Location and Mounting 23
Unit Piping 23
Electrical Wiring 23
General 23
Unit Voltage Power Supply 24
Unit Voltage Imbalance 24
Unit Voltage Phasing 24
Water System Flow Rates 25
Water System Pressure Drop 25
4 RTAD-SVX01A-E4
Contents
Maintenance 29
General 29
Weekly Maintenance 29
Monthly Maintenance 29
Annual Maintenance 29
Maintenance Procedures 30
Refrigerant Emission Control 30
Refrigerant and Oil Charge Management 30
R134a Field Charging Procedure 31
Refrigerant Charging 31
Isolating the Refrigerant in the High Pressure Side 31
Isolating the Refrigerant in the Low Pressure Side 32
Adding Refrigerant 32
Refrigerant Filter Changing Procedure 32
Lubrication System 33
Oil Charging Procedure 33
Factory (initial) Oil Charging Procedure 34
Field Oil Charging Procedure 34
Evaporator Heat Tape Checkout Procedure 35
Safety Recommendations 35
Maintenance Contract 35
Training 35
RTAD-SVX01A-E4 5
List of Figures
List of Tables
Table 1 - General Data Standard RTAD units 8
Table 2 - General Data High Efficiency and High Ambient RTAD units 8
6 RTAD-SVX01A-E4
General Information
RTAD-SVX01A-E4 7
General Information
General Data
Table 1 - General Data RTAD 085 - 125 Standard
Size 85 100 115 125
Compressor
Quantity 2 2 2 2
Nominal Size (1) (Tons) 40/40 50/50 60/60 70/70
Evaporator
Evp. Model EG 120 EG 140 EG 170 EG 200
Water Storage (l) 106 270 222 204
Min. Flow (l/s) 5.7 6.9 8.2 9.5
Max. Flow (l/s) 17.3 20.8 24.6 28.4
Condenser
Qty of Coils 2 2 2 2
Coil Length (mm) 2743 3658 3658 3658
Coil Height (mm) 1575 1575 1575 1575
Fin series (fins/ft) 192 192 192 192
Number of Rows 3/3 2/2 3/3 3/3
Condenser Fans
Quantity (1) 6 6 6 6
Diameter (mm) 762 762 762 762
Total Air Flow (m3/s) 23.43 28.59 27.04 27.07
Nominal RPM 915 915 915 915
Tip Speed (m/s) 36.48 36.48 34.48 34.48
Motor kW (kW) 1.9 1.9 1.9 1.9
Min Starting/Oper Ambient (2)
Std Unit (°C) 7 7 7 7
Low Ambient Unit (°C) -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2
% Min. Load (3) 17 17 17 17
Refrigerant Charge (1) (kg) 51 50 69 71
Oil Charge (1) (l) 10 12 16 18
Operating Weight (kg) 2660 3100 3560 3570
Shipping Weight (kg) 2550 2835 3335 3570
Table 2- General Data RTAD 085 - 125 High Efficiency and High Ambient
Size 85 100 115 125
Compressor
Quantity 2 2 2 2
Nominal Size (1) (Tons) 40/40 50/50 60/60 70/70
Evaporator
Evp. Model EG 140 EG 170 EG 200 EG 200
Water Storage (l) 270 222 204 204
Min. Flow (l/s) 5.7 6.9 8.2 9.5
Max. Flow (l/s) 17.3 20.8 24.6 28.4
Condenser
Qty of Coils 2 2 2 2
Coil Length (mm) 3658 3658 4572 4572
Coil Height (mm) 1575 1575 1575 1575
Fin series (fins/ft) 192 192 192 192
Number of Rows 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 6 8 8 10
Diameter (mm) 762 762 762 762
Total Air Flow (m3/s) 27.0 31.2 35.0 39.1
Nominal RPM 915 915 915 915
Tip Speed (m/s) 36.48 36.48 36.48 36.48
Motor kW (kW) 1.9 1.9 1.9 1.9
Min Starting/Oper Ambient (2)
Std Unit (°C) 7 7 7 7
Low Ambient Unit (°C) -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2
% Min. Load (3) 17 17 17 17
Refrigerant Charge (1) (kg) 50 69 87 87
Oil Charge (1) (l) 10 12 18 18
Operating Weight (kg) 3240 3370 3905 4000
Shipping Weight (kg) 2975 3145 3700 3800
8 RTAD-SVX01A-E4
General Information
Table 3 - General Data RTAD 085 - 125 High Efficiency Low Noise
Size 85 100 115 125
Compressor
Quantity 2 2 2 2
Nominal Size (1) (Tons) 40/40 50/50 60/60 70/70
Evaporator
Evp. Model EG 140 EG 170 EG 200 EG 200
Water Storage (l) 270 222 204 204
Min. Flow (l/s) 5.7 6.9 8.2 9.5
Max. Flow (l/s) 17.3 20.8 24.6 28.4
Condenser
Qty of Coils 2 2 2 2
Coil Length (mm) 3658 3658 4572 4572
Coil Height (mm) 1575 1575 1575 1575
Fin series (fins/ft) 192 192 192 192
Number of Rows 3/3 3/3 3/3 3/3
Condenser Fans
Quantity (1) 6 8 8 10
Diameter (mm) 762 762 762 762
Total Air Flow (m3/s) 19.25 22.23 24.99 27.83
Nominal RPM 730 730 730 730
Tip Speed (m/s) 29.1 29.1 29.1 29.1
Motor kW (kW) 1.05 1.05 1.05 1.05
Min Starting/Oper Ambient (2)
Std Unit (°C) 7 7 7 7
Low Ambient Unit (°C) -18 -18 -18 -18
General Unit
Refrigerant HFC 134a HFC 134a HFC 134a HFC 134a
No. Of independent
Refrigerant Circuits 2 2 2 2
% Min. Load (3) 17 17 17 17
Refrigerant Charge (1) (kg) 50 69 87 87
Oil Charge (1) (l) 10 12 18 18
Operating Weight (kg) 3340 3470 4005 4100
Shipping Weight (kg) 3075 3245 3800
(1) Data containing information for two circuits
(2) Minimum start-up/operation ambient based on a 2.22 m/s (5mph) wind across the condenser.
(3) Percent minimum load is for total machine at 10°C (50F) ambient and 7°C (44F) lealing chilled water temp. Not each individual circuit.
Unit Dimensions
Figure 2 - Unit Dimensions and Minimum Recommended Clearances
RTAD-SVX01A-E4 9
Installation - Mechanical
10 RTAD-SVX01A-E4
Installation - Mechanical
CAUTION: Refer to nameplate for Trane is not responsible for Condenser coils and fan discharge
unit weight and additional equipment problems resulting from must be kept free of snow or other
installation instructions contained an improperly designed or obstructions to permit adequate
inside the control panel. Other lifting constructed foundation. airflow for satisfactory unit
arrangements may cause equipment Note: To allow for cleaning under the operation.
damage or serious personal injury. condensing coil, it is recommended In situations where equipment must
that an opening be left between the be installed with less clearance than
Isolation and Sound Emission unit base and the concrete pad. recommended, such as frequently
The most effective form of isolation occurs in retrofit and rooftop
is to locate the unit away from any Clearances applications, restricted airflow is
sound sensitive area. Structurally Refer to Figure 2 for minimum common. The Main Processor will
transmitted sound can be reduced by clearances. Provide enough space direct the unit to make as much
elastomeric vibration eliminators. around the outdoor unit to allow the chilled water as possible given the
Spring isolators are not installation and maintenance actual installed conditions. Consult
recommended. Consult an acoustical personnel unrestricted access to all your Trane sales engineer for more
engineer in critical sound service points. Refer to submittal details.
applications. For maximum isolation drawings for the unit dimensions. A Note: If the outdoor unit
effect, isolate water lines and minimum of four feet is configuration requires a variance to
electrical conduit. Wall sleeves and recommended for compressor the clearance dimensions, contact
rubber isolated piping hangers can service. Provide sufficient clearance your Trane Sales Office
be used to reduce the sound for the opening of control panel Representative. Also refer to Trane
transmitted through water piping. To doors. In all cases, local codes which Engineering Bulletins for application
reduce the sound transmitted require additional clearances will information on RTAD chillers.
through electrical conduit, use take precedence over these
flexible electrical conduit. State and recommendations. Unit Isolation and Leveling
local codes on sound emissions For additional reduction of sound
should always be considered. Since Unobstructed flow of condenser air and vibration, install the optional
the environment in which a sound is essential to maintain chiller neoprene isolators. Construct an
source is located affects sound capacity and operating efficiency. isolated concrete pad for the unit or
pressure, unit placement must be When determining unit placement, provide concrete footings at the unit
carefully evaluated. Sound power give careful consideration to mounting points. Mount the unit
levels for Trane air-cooled RTAD assuring a sufficient flow of air directly to the concrete pads or
chillers are available on request. across the condenser heat transfer footings. Level the unit using the
surface. Two detrimental conditions base rail as a reference. The unit
Noise Considerations are possible and must be avoided if must be level within 1/4-in (6 mm)
Locate the outdoor unit away from optimum performance is to be over the entire length. Use shims as
sound sensitive areas. If required, achieved: warm air recirculation and necessary to level the unit.
install rubber vibration isolators in coil starvation. Warm air recirculation
all water piping and use flexible occurs when discharge air from the Neoprene Isolator (optional)
electrical conduit. Consult an condenser fans is recycled back to he Installation
acoustical engineer for critical condenser coil inlet. Coil starvation Refer to submittals for diagrams.
applications. Also refer to Trane occurs when free airflow to (or from) 1 Secure the isolators to the
Engineering Bulletins for application the condenser is restricted. Both mounting surface using the
information on RTAD chillers. warm air recirculation and coil mounting slots in the isolator base
starvation cause reduction in unit plate. DO NOT fully tighten the
Foundation
efficiency and capacity due to the isolator mounting bolts at this
Provide rigid, non-warping mounting
increased head pressures. Debris, time.
pads or a concrete foundation of
trash, supplies etc. should not be 2 Align the mounting holes in the
sufficient strength and mass to
allowed to accumulate in the vicinity base of the unit with the threaded
support the outdoor unit operating
of the unit. Supply air movement positioning pins on the top of the
weight (i.e., including completed
may draw debris into the condenser isolators.
piping, and full operating charges of
coil, blocking spaces between coil 3 Lower the unit onto the isolators
refrigerant, oil and water). Refer to
fins and causing coil starvation. and secure the isolator to the unit
Tables 1, 2 and 3 for unit operating
Special consideration should be with a nut. Maximum isolator
weights. Once in place, the outdoor
given to low ambient units. deflection should be 1/4 inch
unit must be level within 1/ 4"
(6 mm).
(6 mm) over its length and width.
RTAD-SVX01A-E4 11
Installation - Mechanical
4 Level the unit carefully. Fully Caution: A pipe strainer must be Evaporator Flow Switch
tighten the isolator mounting bolts. installed in the entering water line. Specific connection and schematic
Failure to do so can allow wiring diagrams are shipped with
Drainage waterborne debris to enter the the unit. Some piping and control
Provide a large capacity drain for evaporator. schemes, particularly those using a
water vessel drain-down during "Piping components" include all single water pump for both chilled
shutdown or repair. The evaporator devices and controls used to provide and hot water must be analyzed to
is provided with a drain connection. proper water system operation and determine how and or if a flow-
All local and national codes apply. unit operating safety. These sensing device will provide desired
The vent on the top of the components and their general operation.
evaporator shell is provided to locations are given below. Follow the manufacturer's
prevent a vacuum by allowing air
recommendations for selection and
into the evaporator for complete
drainage. Entering Chilled Water installation procedures. General
guidelines for flow switch installation
Piping are outlined below
Evaporator Water Piping ❏ Air vents (to bleed air from 1. Mount the switch upright, with a
system). minimum of 5 pipe diameters of
Thoroughly flush all water piping to
❏ Water pressure gauges with straight horizontal run on each
the unit before making the final
shutoff valves. side. Do not install close to
piping connections to the unit.
❏ Vibration eliminators. elbows, orifices or valves.
Caution: If using an acidic
❏ Shutoff (isolation) valves. Note: The arrow on the switch must
commercial flushing solution,
Thermometers (if desired). point in the direction of flow.
construct a temporary bypass
❏ Clean-out tees. 2. To prevent switch fluttering,
around the unit to prevent damage
❏ Pipe strainer. remove all air from the water
to internal components of the
Caution: Install strainer in system.
evaporator. To avoid possible
evaporator water inlet piping. Failure Note: The UCM-CLD provides a 6-
equipment damage, do not use
to do so can result in evaporator second time delay after a "loss-of-
untreated or improperly treated
tube damage. flow" diagnostic before shutting the
system water.
unit down. Contact a qualified
Evaporator Piping Leaving Chilled Water service representative if nuisance
machine shutdowns persist.
Components and layout will vary Piping 3. Adjust the switch to open when
slightly, depending on the location of ❏ Air vents (to bleed air from water flow falls below nominal.
connections and the water source. system). Evaporator data is given in Tables 1,
Caution: The chilled water ❏ Water pressure gauges with 2 and 3. Flow switch contacts are
connections to the evaporator are to shutoff valves. Vibration closed on proof of water flow.
be flange type connections. eliminators. 4. Install a pipe strainer in the
To prevent damage to chilled water ❏ Shutoff (isolation) valves. entering evaporator water line to
components, do not allow ❏Thermometers. protect components from
evaporator pressure (maximum ❏ Clean-out tees. waterborne debris.
working pressure) to exceed 150 psig ❏ Balancing valve.
(10.5 bar). ❏ Flow Switch
Provide shutoff valves in lines to the Caution: To prevent evaporator Water Treatment
gauges to isolate them from the damage, do not exceed 150 psig CAUTION: If calcium chloride is used
system when they are not in use. (10.5 bar) evaporator water pressure. for water treatment, an applicable
Use rubber vibration eliminators to corrosion inhibitor must also be
prevent vibration transmission used. Failure to do so may result in
Evaporator Drain damage to system components.
through the water lines. If desired,
A 3/4" drain connection is located
install thermometers in the lines to
under the evaporator shell. This may Dirt, scale, products of corrosion and
monitor entering and leaving water
be connected to a suitable drain to other foreign material will adversely
temperatures. Install a balancing
permit evaporator drainage during affect heat transfer between the
valve in the leaving water line to
unit servicing. A shutoff valve must water and system components.
control water flow balance. Install
be installed on the drain line. Foreign matter in the chilled water
shutoff valves on both the entering
and leaving water lines so that the system can also increase pressure
evaporator can be isolated for drop and, consequently, reduce
service. water flow. Proper water treatment
must be determined locally,
12 RTAD-SVX01A-E4
Installation - Mechanical
Figure 4: Evaporator Water Pressure Drop RTAD depending on the type of system and
local water characteristics. Neither
Evaporator Water Pressure Drops (SI units) salt nor brackish water is
recommended for use in Trane air-
1000
cooled Series R™ chillers. Use of
either will lead to a shortened life to
an indeterminable degree. The Trane
Company encourages the
3 employment of a reputable water
100
1 4 treatment specialist, familiar with
2 local water conditions, to assist in
this determination and in the
WPD kPa
RTAD-SVX01A-E4 13
Installation - Mechanical
Freeze Protection
If the unit will remain operational at
subfreezing ambient temperatures,
the chilled water system must be
protected from freezing, following
the steps listed below
1 Heaters are factory-installed on the
packaged unit evaporator and will
protect it from freezing in ambient
temperatures down to -18°C (0°F).
2 Install heat tape on all water
piping, pumps, and other
components that may be damaged
if exposed to freezing
temperatures. Heat tape must be
designed for low ambient
temperature applications. Heat
tape selection should be based on
the lowest expected ambient
temperature.
3 Add a non-freezing, low
temperature, corrosion inhibiting,
heat transfer fluid to the chilled
water system. The solution must be
strong enough to provide
protection against ice formation at
the lowest anticipated ambient
temperature. Refer to Table 1
through Table 3 in Section 1 for
evaporator water storage
capacities.
Note: Use of glycol type antifreeze
reduces the cooling capacity of the
unit and must be considered in the
design of the system specifications.
14 RTAD-SVX01A-E4
Installation - Electrical
RTAD-SVX01A-E4 15
Installation - Electrical
1. As standard, all units have single diagrams that are shipped with the sources before completing wiring
point power connection. unit. The installer must provide the connections to the unit.
2. LRA (Locked Rotor Amps) - based following components if not ordered All wiring must comply with local
on full winding (x-line) start units. with the unit: electrical codes. The installing (or
LRA for wye-delta starters is 1/3 of ❏ Power supply wiring (in conduit) electrical) contractor must provide
LRA of x-line units. for all field-wired connections. and install the system
3. VOLTAGE UTILIZATION RANGE: ❏ All control (interconnecting) wiring interconnecting wiring and the
(in conduit) for field supplied power supply wiring. It must be
Rated Voltage Utilization Range devices. properly sized and equipped with the
400/50/3 340-460
❏ Fused-disconnect switches or appropriate fused disconnect
circuit breakers. switches. The type and installation
For the RTAD 100 only, the Utilization ❏ Power factor correction capacitors. location(s) of the fused disconnects
Range is 360 - 460 Volts must comply with all applicable
codes.
Power Supply Wiring Caution: Use only copper conductors
Installer-Supplied All power supply wiring must be for terminal connections to avoid
Components sized and selected accordingly by the corrosion or overheating.
project engineer in accordance with Cut holes into the sides of the
Caution: Customer wiring interface
EN 60204. control panel for the appropriately
connections are shown in the
WARNING: To prevent injury or sized power wiring conduits.
electrical schematics and connection
death, disconnect all electrical power
16 RTAD-SVX01A-E4
Installation - Electrical
The wiring is passed through these Interconnecting Wiring -4 would be a time clock, ambient
conduits and connected to the Chilled Water Flow (Pump) Interlock thermostat, building automation
terminal blocks, optional unit- The model RTAD chiller requires a system, etc.
mounted disconnects, or circuit field-supplied control voltage contact 2. UCM-CLD Pump Control Contacts
breakers. input through a flow proving switch (Terminals A1 TB4-8 and -9)
To provide proper phasing of 3- 6S56 and an auxilary contact 6K51 of This output is a set of contacts that
phase input, make connections as the chilled water pump contactor. will close, starting the chilled-water
shown in field wiring diagrams and IMPORTANT: Do not turn the chiller pump when the external Auto/Stop
as stated on the Warning label in the on or off using the chilled-water contacts are closed. When the
starter panel. For additional interlocks. contacts are opened, 1 to 30 minutes
information on proper phasing, refer When making field connections, later (adjustable through the Clear
to "Unit Voltage Phasing." Proper refer to the appropriate field layout, Language Display), the UCM-CLD
equipment ground must be provided wiring schematics, and control pump control contacts open.
to each ground connection in the diagrams that ship with the unit. 3. Proof-of-Chilled-Water-Flow
panel (one for each customer- Interlock (Terminals A1 TB3-1
supplied conductor per phase). Chilled-water pump control and -2)
CAUTION: The chilled-water pump This terminal must be field-installed.
Control Power Supply must operate for a minimum of one Contact closure between the
The unit is equipped with a control minute after the UCM-CLD receives a terminals indicates proof of chilled-
power transformer; it is not command, through the external water flow. Examples of this are a
necessary to provide additional Auto/Stop input, to shut down the pump starter auxiliary contact, flow
control power voltage to the unit. The chilled-water system. switch, differential pressure switch,
RTAD units are factory-connected for or a contact from a building
400V/3/50 with a factory-installed On the RTAD units, the controller will automation system. Opening of this
control power transformer. initiate the "Run:Unload" mode to contact will immediately shut down
terminate a cycle from any of the the chiller and initiate an automatic
Heater Power Supply following: reset diagnostic, indicating loss of
The evaporator shell is insulated • Stop key pressed chilled-water flow.
from ambient air and protected from • Loss of load
freezing temperatures by electric
heaters. Whenever the water
• External Auto/Stop input opened Alarm and Status Relay
The "Run:Unload" operating mode
temperature drops to approximately commands the compressor to
Output (Programmable
37°F (2.8°C), the thermostat completely unload, which takes Relays)
energizes the heaters. The heaters about ½ minute. This will allow the Alarm/Running/Maximum Capacity
will provide protection from ambient compressors to be totally unloaded Outputs
temperatures down to -18°C (0°F). for the next start-up. If only the Terminals 1 to 7 on terminal strip TB4
The heaters are factory-wired back to proof-of-chilled-water-flow interlock of the A1 board provide a variety of
the unit control panel. is used, the chiller will shut down contact outputs on the RTAD. These
with an immediate (non-friendly) are dependent on the setting of
CAUTION: Control panel main shutdown and initiate an automatic Programmable Relay Setup (Service
processor does not check for loss of reset diagnostic. Setting Menu) and its relationship to
power to the heat tape nor does it 1. External Auto/Stop (terminals A1 diagnostics, compressors operating,
verify thermostat operation. A TB3-3 and -4). This input is and the system operating at full
qualified technician must verify supplied by the field. A contact capacity.
power to the heat tape and confirm closure will start the chiller water As shown in Figure 7, there are three
operation of the heat tape pump and chiller, via the UCM-CLD relays.
thermostat to avoid catastrophic pump control contacts. Opening
damage to the evaporator. the contact will put the operating
compressors into "Run:Unload"
Water Pump Power Supply mode and initiate a timing period
Provide power supply wiring with (1 to 30 minutes, adjustable
fused disconnect for the chilled through the Clear Language
water pump(s). Display). This will delay
termination of the chilled-water
pump operation via the UCM
pump control contacts. Examples
of the input terminals 1UTB3-3 and
RTAD-SVX01A-E4 17
Installation - Electrical
Figure 7 - Alarm / Running / Maximum capacity relay output for the RTAD unit.
1 Relay 1 Alarm
Relay 2 Compressor running
Relay 3 Maximum capacity
3 Relay 1 Alarm
Relay 2 Circuit 1 running
Relay 3 Circuit 2 running
Notes:
MMR: Machine Manual Reset
CMR: Circuit Manual Reset
MAR: Machine Auto Reset
CAR: Circuit Auto Reset
IFW: Informational Warnings
18 RTAD-SVX01A-E4
Installation - Electrical
RTAD-SVX01A-E4 19
Installation - Electrical
If, while in ice-building mode, the External current limit Outdoor air-temperature
unit gets down to the freezestat
setting (water or refrigerant), the unit
setpoint: voltage source sensor
will shut down on a manually 2-10 V (dc)or current source This sensor is used for low ambient
resettable diagnostic, just as in lockout and chilled-water reset by
4- 20 mA. outdoor air temperature. This sensor
normal operation. This option allows the external is optional on the RTAD units.
setting of the current limit setpoint Remove the sensor from its shipping
External chilled-water (CLS), independent of the front panel location in the control panel and
setpoint: voltage source current-limit setpoint, by one of the install it in the fresh-air intake on the
two means:
2-10 V (dc), or Current 1 - an isolated voltage input 2-10 V
north wall of the building. Protect the
sensor from direct sunlight and
source 4-20 mA (dc) shelter it from the elements. Connect
This option allows the external 2 - an isolated voltage input 4-20 mA leads to terminals 1 and 2 from
setting of the chilled-water setpoint To enable external current-limit module A9 TB1. All wiring to and
(CWS), independent of the front setpoint operation, external current- from the remote sensor must be
panel chilled-water setpoint, by one limit setpoint (operator setting made with shielded, twisted-pair
of two means: menu) should be set to "E" using the conductors.
1 - An isolated voltage input 2-10 V clear language display. Be sure to ground the shielding only
(dc) 1- 2-10 V (dc) voltage source input at the UCM-CLD. Apply tape to the
2 - An isolated current loop input Set dipswitch SW1-2 of the option sensor end of the shielding to
4-20 mA module A9 to "OFF." prevent it from contacting the
Connect the voltage source to surface.
Isolated 2-10 V (dc) voltage terminals 7 (+) and 8 (-) of the option WARNING: To prevent injury or
module A9. CLS is now based on the
source input following equation:
death, disconnect the electrical
Set dipswitch SW1-1 of the option power source before completing
CLS % = (V (dc)*10) + 20 wiring connections to the unit.
module A9 to "OFF." Connect the Sample values for CLS vs.
voltage source to terminals 4 (+) and V(dc)signals are shown in Table 8.
5 (-) on option module A9 TB1. CWS Minimum setpoint: 40% (2.0 V
is now based on the following (dc)input)
equation: Maximum setpoint: 120% (10.0 V
CWS °C = (V (dc) * 4.88) - 27.56 (dc)input)
Sample values for CWS vs. V (dc) 4-20 mA Current source input
signals are shown in Table 7 Set dipswitch SW1-2 of the option
Table 7: Input values vs. External chilled- module A9 to "ON." Connect the
water setpoint current source to terminal 7 (+) and 8
Voltage Current Resulting (-) of option module A9. CLS is now
(V (dc)) (mA) chilled-water
setpoint (°C)
based on the following equation:
3.6 7.2 -10 CLS % = (mA * 5) + 20
4.6 9.2 -5 Sample values for CLS versus mA
5.6 11.3 0 signals are shown in Table 8.
6.7 13.3 5
7. 7 1 5.4 10
Minimum setpoint = 40% (4.0 mA)
Maximum setpoint = 120% (20.0 mA)
Table 8: Input values vs. external current-
Isolated 4-20 mA current limit setpoint
Voltage Current Resulting
source input (V (dc)) (mA) chilled-water
Set dipswitch SW1-1 of the option setpoint (°C)
module A9 to "ON."
2.0 4.0 40
Connect the current source terminals 3.0 6.0 50
4 (+) and 5 (-). 4.0 8.0 60
CWS is now based on the following 5.0 10.0 70
6.0 12.0 80
equation: 7. 0 1 4.0 90
Setpoint (°C) = (mA * 2.44) - 27.56 8.0 16.0 100
9.0 18.0 110
10.0 20.0 120
RTAD-SVX01A-E4 20
Installation - Electrical
Communication-link
connection procedure
1. Refer to the Tracer installation
literature to determine proper
communication-link termination
connections at the Tracer module.
2. Connect the shield of the
communication-link wiring to the
designated shield terminal at the
Tracer module.
3. Connect leads to terminals 1 to 4
of TB2 of the module A9 of the
UCM-CLD to the Tracer. There is no
polarity requirement for the
connection.
RTAD-SVX01A-E4 21
Operating Principles
22 RTAD-SVX01A-E4
Pre-Start Checkout
Installation Checklist ❏ Install a water strainer in the ❏ If the ice making-option is used,
Complete this checklist as the unit is entering chilled water line. install leads on terminals TB1-1
installed and verify that all ❏ Install a balancing valve and flow and 2 on module A9.
recommended procedures are switch (recommended) in the
accomplished before the unit is leaving chilled water line. General
started. This checklist does not ❏ Install a drain with shutoff valve or When installation is complete, but
replace the detailed Instructions a drain plug on the evaporator prior to putting the unit into service,
given in the "Installation - waterbox. the following pre-start
Mechanical" and "Installation - ❏ Vent the chilled water system at procedures must be reviewed and
Electrical" sections of this manual. high points in the system piping. verified correct:
Read both sections completely, to ❏ Apply heat tape and insulation, as Disconnect all electric power
become familiar with the installation necessary, to protect all exposed including remote disconnects before
procedures, prior to beginning the piping from freeze-up. servicing. Failure to disconnect
work. power before servicing can cause
Electrical Wiring severe personal injury or death.
Receiving WARNING: To prevent injury or 1 Inspect all wiring connections in
❏ Verify that the unit nameplate data death, disconnect electrical power the compressor power circuits
corresponds to the ordering source before completing wiring (disconnects, terminal block,
information. connections to the unit. contactors, compressor junction
❏ Inspect the unit for shipping CAUTION: To avoid corrosion and box terminals, etc.). to be sure they
damage and any shortages of overheating at terminal connections, are clean and tight.
materials. Report any damage or use copper conductors only. CAUTION: Verify all connections are
shortage to the carrier. ❏ Connect the unit power supply made. Loose connections can cause
wiring with fused-disconnect to overheating and undervoltage
the terminal block or lugs (or unit- conditions at the compressor motor.
Unit Location and mounted disconnect) in the power 2 Open all refrigerant valves in the
Mounting section of the control panel. discharge, liquid, oil and oil return
❏ Inspect the location desired for ❏ Connect power supply wiring to lines.
installation and verify adequate the evaporator heater. CAUTION: Do not operate the unit
service access clearances. ❏ Connect power supply wiring to with the compressor, oil discharge,
❏ Provide drainage for evaporator the chilled water pump. liquid line service valves and the
water. ❏ Connect power supply wiring to manual shutoff on the refrigerant
❏ Remove and discard all shipping any auxiliary heat tapes. supply to the coolers "CLOSED".
materials (cartons, etc.) ❏ Connect the auxiliary contact of Failure to have these "OPEN" may
❏ Install optional rubber isolators, if the chilled water pump (6K51) in cause serious compressor damage.
required. series with the flow switch, if 3 Check the power supply voltage to
❏ Level the unit and secure it to the installed, and then connect to the the unit at the main power fused-
mounting surface. proper terminals. disconnect switch. Voltage must be
❏ For the External Auto/Stop within the voltage utilization range
Unit Piping function, install wiring from and also stamped on the unit
❏ Flush all unit water piping before remote contact (6S1) to the proper nameplate. Voltage imbalance
making final connections to the terminals on the circuit board. must not exceed 3%.
unit. CAUTION: Information in 4 Check the unit power phasing L1-
CAUTION: If using an acidic Interconnecting Wiring: Chilled Water L2-L3 in the starter to be sure that
commercial flushing solution, Pump Interlock and External it has been installed in an "ABC"
construct a temporary bypass Auto/Stop must be adhered to or phase sequence.
around the unit to prevent damage equipment damage may occur. CAUTION: Improper power phasing
to internal components of the ❏ If alarm and status relay outputs can result in equipment damage due
evaporator. To avoid possible are used, install leads from the to reverse rotation.
equipment damage, do not use panel to the proper terminals on CAUTION: Do not use untreated or
untreated or improperly treated circuit board. improperly treated water.
system water. ❏ If the emergency stop function is Equipment damage may occur.
❏ Connect the chilled water piping to used, install low voltage leads to 5 Fill the evaporator chilled water
the evaporator. terminals on circuit board. circuit. Vent the system while it is
❏ Install pressure gauges and shutoff ❏ Connect separate power for the being filled. Open the vents on the
valves on the chilled water inlet External Emergency Stop option, if top of the evaporator shell while
and outlet to the evaporator. applicable. filling and close when filling is
completed.
RTAD-SVX01A-E4 23
Pre-Start Checkout
Important: The use of improperly CAUTION: Provide adequate voltage three-phase system succeed one
treated or untreated water in this to the unit. Failure to do so can another is called phase sequence or
equipment may result in scaling, cause control components to phase rotation. This is determined by
erosion, corrosion, algae or slime. malfunction and shorten the life of the direction of rotation of the
The services of a qualified water relay contact, compressor motors alternator. When rotation is
treatment specialist should be and contactors. clockwise, phase sequence is usually
engaged to determine what called "ABC," when counter-
treatment, if any, is advisable. The Unit Voltage Imbalance clockwise, "CBA."
Trane Company warranty specifically Excessive voltage imbalance This direction may be reversed
excludes liability of corrosion, between the phases of three-phase outside the alternator by
erosion or deterioration of Trane system can cause motors to interchanging any two of the line
equipment. Trane assumes no overheat and eventually fail. The wires. It is this possible interchange
responsibilities for the results of the maximum allowable imbalance is 3 of wiring that makes a phase
use of untreated or improperly percent. Voltage imbalance is sequence indicator necessary if the
treated water or saline or brackish determined using the following operator is to quickly determine the
water. calculations: phase rotation of the motor.
6 Close the fused-disconnect Proper compressor motor electrical
switch(es) that supplies power to % Imbalance = [(Vx - V ave) x phasing can be quickly determined
the chilled water pump starter. 100]/Vave and corrected before starting the
7 Start the chilled water pump to V ave = (V1 + V2 + V3)/3 unit. Use a quality instrument, such
begin circulation of the water. as the Associated Research Model 45
Inspect all piping for leakage and Vx = phase with the greatest Phase Sequence Indicator, and
make any necessary repairs. difference from V ave (without follow this procedure.
8 With water circulating through the regard to the sign) 1 Press the STOP key on the UCM-
system, adjust water flow and For example, if the three measured CLD.
check water pressure drop through voltages are 221, 230, and 227 volts, 2 Open the electrical disconnect or
the evaporator. the average would be: circuit protection switch that
9 Adjust the chilled water flow switch (221+230+227)/3 = 226 provides line power to the line
for proper operation. power terminal block(s) in the
Warning: Use extreme caution when The percentage of the imbalance is starter panel (or to the unit-
performing the following procedure then: mounted disconnect).
with power applied. Failure to do so [100(221-226)]/226 = 2.2% 3 Connect the phase sequence
can result in personal injury or This exceeds the maximum indicator leads to the line Power
death. allowable (2%) by 0.2 percent. terminal block, as follows:
10 Reapply power to complete 4 Turn power on by closing the unit
procedures. supply power fused-disconnect
11 Prove all Interlock and
Unit Voltage Phasing switch.
Interconnecting Wiring Interlock Warning: It is imperative that L1, L2, 5 Read the phase sequence on the
and External as described in the L3 in the starter be connected in the indicator. The "ABC" LED on the
Electrical Installation section. A-B-C phase sequence to prevent face of the phase indicator will
12 Check and set, as required, all equipment damage due to reverse glow if phase is "ABC."
UCM-CLD menu items. rotation. WARNING: To prevent injury or death
13 Stop the chilled water pump. It is important that proper rotation of due to electrocution, take extreme
14 Energize compressor and oil the compressors be established care when performing service
separators 24 hours prior to unit before the unit is started. procedures with electrical power
start-up. Proper motor rotation requires energized.
confirmation of the electrical phase 6 If the "CBA" indicator glows
sequence of the power supply. The
Unit Voltage Power Supply motor is internally connected for
instead, open the unit main power
Voltage to the unit must meet the disconnect and switch two line
clockwise rotation with the incoming leads on the line power terminal
criteria given in the Installation- power supply phased A, B, C.
Electrical Section. Measure each leg block(s) (or the unit mounted
Basically, voltages generated in each disconnect). Reclose the main
of the supply voltage at the unit's phase of a polyphase alternator or
main power fused- disconnect. If the power disconnect and recheck the
circuit are called phase voltages. In phasing.
measured voltage on any leg is not a three-phase circuit, three sine wave
within specified range, notify the voltages are generated, differing in
supplier of the power and correct the phase by 120 electrical degrees. The
situation before operating the unit. order in which the three voltages of a
24 RTAD-SVX01A-E4
Pre-Start Checkout
RTAD-SVX01A-E4 25
Unit Start-up Procedures
Daily Unit Start-Up safety interlocks are closed, the 4 Open all the valves in the
The time line for sequence of unit will start. The compressor(s) evaporator chilled water circuits.
operation is shown at the end of this will load and unload in response to 5 Open all refrigerant valves to verify
section and depicts the nominal the leaving chilled water they are in the open condition.
delays and sequences that a chiller temperature. 6 If the evaporator was previously
would experience during a typical Once the system has been operating drained, vent and fill the
operational cycle. The time line for approximately 30 minutes and evaporator and chilled water
begins with a power up of the main has become stabilized, complete the circuit. When all air is removed
power to the chiller. The sequence remaining start-up procedures, as from the system , re-install the vent
assumes a RTAD chiller with no follows: plugs on top of the evaporator
diagnostics or 1 Check the evaporator refrigerant shell.
malfunctioning components. pressure and the condenser CAUTION: Ensure that the
External events such as the operator refrigerant pressure under compressor and oil separator
placing the chiller in Auto Refrigerant Report on the CLD heaters have been operating for a
or Stop, chilled water flow through Module. The pressures are minimum of 24 hours before
the evaporator, and application of referenced to sea level (1013 mbar - starting. Failure to do so may result
load to the chilled water 14.7 psia). in equipment damage.
loop causing loop water temperature 2 Measure the system discharge 7 Check the adjustment and
increases are depicted and the superheat. operation of each safety and
chillers responses to those 3 Measure the system subcooling. operating control.
events are shown, with appropriate 4 A shortage of refrigerant is 8 Close all disconnect switches.
delays noted. The effects of indicated if operating pressures are 9 Refer to the sequence for daily unit
diagnostics, and other external low and subcooling is also low. If startup for the remainder of the
interlocks other than evaporator the operating pressures, sight seasonal startup.
water flow proving, are not glass, superheat and subcooling
considered. The response of the readings indicate a refrigerant
CLD Display is also depicted on the shortage, gas-charge refrigerant
time line. into each circuit, as required. With
the unit running, add refrigerant
vapor by connecting the charging
General line to the suction charging service
If the pre-start checkout, as discussed valve port until operating
above, has been completed, the unit conditions become normal.
is ready to start. CAUTION: If both suction and
1 Press the STOP key on the CLD discharge pressures are low but
module. subcooling is normal, a problem
2 As necessary, adjust the setpoint other than refrigerant shortage
values in the UCM-CLD « Operator exists. Do not add refrigerant, as this
Settings » menu. may result in overcharging the
3 Close the fused-disconnect switch circuit. Use only refrigerants
for the chilled water pump. specified on the unit nameplate (HFC
Energize the pump(s) to start water 134a) and Trane Oil 00048. Failure to
circulation. do so may cause compressor
4 Check the service valves on the damage and improper unit
discharge line, oil line and liquid operation.
line for each circuit. These valves
must be open (backseated) before
starting the compressors.
Seasonal Unit Start-Up
CAUTION: To prevent compressor Procedure
damage, do not operate the unit 1 Close all valves and re-install the
until all refrigerant and oil line drain plugs in the evaporator.
service valves are opened. 2 Service the auxiliary equipment
5 Verify that the chilled water pump according to the start-
runs for at least one minute after up/maintenance instructions
the chiller is commanded to stop provided by the respective
(for normal chilled water systems). equipment manufacturers.
6 Press the AUTO key. If the chiller 3 Close the vents in the evaporator
control calls for cooling and all chilled water circuits.
26 RTAD-SVX01A-E4
Unit Start-up Procedures
RTAD-SVX01A-E4 27
Unit Shutdown Procedures
Extended Shutdown
Procedure
The following procedure is to be
followed if the system is to be taken
out of service for an
extended period of time, e.g.
seasonal shutdown:
1 Test the unit for refrigerant leaks
and repair as necessary.
2 Open the electrical disconnect
switches for the chilled water
pump. Lock the switches in the
"OPEN" position.
28 RTAD-SVX01A-E4
Maintenance
Monthly Maintenance
1 Perform all weekly maintenance
procedures.
2 Record the system subcooling.
3 Record the system superheat.
4 Make any repairs necessary.
Annual Maintenance
1 Perform all weekly and monthly
procedures.
2 Check oil sump oil level while unit
is off.
Note: Routine changing of the oil is
not required. Use an oil analysis to
determine the condition of the oil.
RTAD-SVX01A-E4 29
Maintenance Procedures
30 RTAD-SVX01A-E4
Maintenance Procedures
RTAD-SVX01A-E4 31
Maintenance Procedures
10 Open all valves, start the unit and through the liquid line service
verify the refrigerant charge by valve.
measuring the subcooling. 4 Once the unit has been charged
with refrigerant, start the unit.
Isolating the refrigerant Measure the subcooling and verify
that the refrigerant charge is
charge in the low pressure correct.
side for High Side Repairs
If the refrigerant charge needs to be Table 9 Refrigerant Charge per Circuit
in kg.
isolated in the low side of the unit, RTAD Circuit A Circuit B
perform the following procedures : 085 std 26 25
1 Press the STOP key and send the 085 HE 24 26
100 std 24 26
unit to a stopping mode.
100 HE 33 36
2 Close the discharge service valve 115 std 33 36
(optional on RTAD). 115 HE 42 45
3 Before closing the liquid line 125 std 34 37
125 HE 42 45
service valve, attach a manifold
gauge set to the liquid line
backseat port. Refrigerant Filter Changing
4 Close the liquid line service valve.
5 Attach the inlet of a liquid transfer Procedure
pump to the manifold gauge set A dirty filter is indicated by a
and the outlet of the service valve temperature gradient across the
mounted on the suction line. filter, corresponding to a pressure
This will transfer the liquid drop. If the temperature downstream
refrigerant. As the low pressure side of the filter is 4.4°C (8°F) lower than
cannot contain all the charge, the the upstream temperature, the filter
remaining refrigerant will be should be replaced. A temperature
transferred to a separate vessel. drop can also indicate that the unit is
6 Remove all of the vapor from the undercharged. Ensure proper
high side of the system. subcooling before taking
7 Complete all necessary repairs. temperature readings.
8 Evacuate the high side through the 1 With the unit off, verify that the
access port on the liquid line EXV is closed. Close liquid line
service valve. isolation valve. On units with
9 Open all the valves and run the remote evaporators or oil cooling
unit. Verify the refrigerant charge circuits, close ball valve on oil
by measuring the subcooling. cooler liquid line.
2 Attach vacuum hose to service port
on liquid line filter flange.
Adding Refrigerant
3 Evacuate refrigerant from liquid
If the entire charge has been
line and store.
removed, perform the following
4 Remove vacuum hose.
procedures to recharge the unit.
5 Depress schrader valve to equalize
1 Open all service valves
pressure in liquid line with
2 Establish water flow through the
atmospheric pressure.
evaporator. Connect a hose from
6 Remove bolts that retain filter
the refrigerant bottle to the
flange.
backseat port on the liquid line
7 Remove old filter element.
shutoff valve. Midseat the valve.
8 Inspect replacement filter element
Caution : The evaporator water flow
and lubricate o-ring with Trane
needs to be established and
OIL00048.
maintained while adjusting the
Note: do not use mineral oil. It will
charge to avoid freezing and
contaminate the system.
rupturing the tubes.
9 Install new filter element in filter
3 It may not be possible to put the
housing.
entire amount of refrigerant charge
10 Inspect flange gasket and replace
required using step 2. If so, start
if damaged.
the unit and add liquid refrigerant
32 RTAD-SVX01A-E4
Maintenance Procedures
11 Install flange and torque bolts to • Discharge line with optional service
19-22 mN (14-16 lb-ft). valve
12 Attach vacuum hose and evacuate • Oil line from separator to
liquid line. compressor
13 Remove vacuum hose from liquid • Oil line drain (lowest point in
line and attach charging hose. system)
14 Replace stored charge in liquid • Oil cooler
line. • Oil temperature sensor
15 Remove charging hose. • Oil line shut off valve with flare
16 Open liquid line isolation valve. service connection
On units with remote evaporators • Oil filter (internal to compressor)
or oil cooler circuits, open oil with flare fitting service connection
cooler liquid line ball valve. and schrader valve
• Oil flow control valve (internal to
Lubrication System the compressor after the filter)
The lubrication system has been
designed to keep most of the oil The standard oil charge for each
lines filled with oil as long as there is circuit size is in Table 10.
a proper oil level in the oil sump. Table 10 - Standard oil charge
The total oil charge can be removed Unit size Oil charge (l)
by draining the oil system, oil return RTAD 085 5
line from the evaporator, the RTAD 100 6
RTAD 115 8
evaporator, and the compressor. Very RTAD 115HE 9
small quantities of oil may be found RTAD 125 9
in other components.
Recommendation: check the oil level
in the sump using a sight glass
Oil Charging Procedure attached to charging hoses.
Proper charging of the oil system is
critical to the reliability of the 1 To measure the oil level, use the oil
compressor and chiller. drain valve on the oil line and a
Too little oil can cause the service valve on the discharge line.
compressor to run hot and This measurement can only be
inefficiently. When taken to an made when the circuit is not
extreme, low oil level may result in running.
infant failure of the compressor. Too Note: the bottom plate of the oil
much oil will result in high oil- separator is approximately 25mm
circulation rates, which will foul the (1'') thick.
condenser and evaporator 2 After the unit has run for a while,
performance. This will result in the oil level in the sump can vary
inefficient operation of the chiller. greatly. However, if the unit has
Taken to an extreme, high oil levels run "normal" conditions for a long
may result in erratic expansion valve time the level should be between
control or shut down of the chiller 25 to -100mm (+1" to - 4" )
due to low evaporator-refrigerant The field charging procedure
temperature. Too much oil may depends on the circumstances that
contribute to long-term bearing resulted in the need for oil
wear. Additionally, excessive charge.
compressor wear is probable when 1 Some service procedures may
the compressor is started with the oil result in loss of small quantities of
lines dry. oil that must be replaced (oil
Note: The oil system schematic is analysis, compressor filter
represented in dotted line on the replacement, re-tubing the
refrigerant circuit schematic, Figure 8 evaporator, and so forth.).
The oil system consists of the 2 Additionally, some maintenance
following components: procedures may result in virtually
• Compressor all of the oil being removed
• Oil separator (compressor motor burn or total
RTAD-SVX01A-E4 33
Maintenance Procedures
34 RTAD-SVX01A-E4
Maintenance Procedures
10 Open the oil line shut off valve. the evaporator. This can be copied and air conditioning service school at
Severe damage to the compressor by cutting a small strip of your disposal. The principal aim of
can result if the oil line shut off insulation out and replacing it with this is to give operators and
valve is closed when the tape. maintenance technicians a better
compressor is started. 4 Replace any insulation that was knowledge of the equipment they
WARNING: Catastrophic damage to removed. are using, or that is under their
the compressor will occur if the oil 5 Wire the heaters into the system as charge. Emphasis is particularly
line shut off valve or the isolation per the wiring diagram. given to the importance of periodic
valves are left closed on unit start- 6 Recheck the resistance to verify checks on the unit operating
up. that they are wired correctly. parameters as well as on preventive
11 Open the other compressor maintenance, which reduces the cost
isolation valves. Safety recommendations of owning the unit by avoiding
Note: this procedure assumes that To avoid accidents and damage, the serious and costly breakdowns.
the oil that is put into the filter following recommendations should
housing does not have contaminants be observed during maintenance
such as non-condensable gases. The and service visits:
oil forces these gases out of the filter 1. The maximum allowable pressures
and oil line shut off valve without the for system leak testing on low and
need to pull a vacuum on this small high pressure side are given in the
volume. If the oil has been in an chapter "Installation". Always
open container or is otherwise provide a pressure regulator.
contaminated, then this small 2. Disconnect the main supply before
volume must be subject to vacuum any servicing on the unit.
as well. However, the filter cavity is 3. Service work on the refrigeration
full of oil. Therefore, be sure to use a system and the electrical system
flash tank in line with the vacuum should be carried out only by
pump to make sure that oil, that is qualified and experienced
pulled out of the filter cavity, does personnel.
not slug the vacuum pump.
Maintenance contract
Evaporator Heat Tape It is strongly recommended that you
Checkout Procedure sign a maintenance contract with
CAUTION: If the heat tapes wrapped your local Service Agency. This
around the evaporator barrel fail, the contract provides regular
evaporator will freeze causing maintenance of your installation by a
catastrophic damage to the entire specialist in our equipment. Regular
unit. maintenance ensures that any
To check the heat tapes wrapped malfunction is promptly detected
around the barrel follow the and corrected and minimizes the
procedures below. possibility that serious damage will
1 Locate the connection under the occur. Finally, regular maintenance
evaporator insulation near the ensures the maximum operating life
bottom of the barrel. of your equipment. We remind you
CAUTION: Do not cut past the that failure to respect these
evaporator insulation. Electrical installation and maintenance
damage to the heat tape wires will instructions may result in immediate
occur if cutting of the insulation is cancellation of the warranty.
done improperly.
The resistance can be checked with Training
an ohmmeter to determine if there is The equipment described in this
an open or a short. If a heater has manual is the result of many years of
failed, replace as follows: research and continuous
1 Remove the insulation around the development. To assist you in
heater. obtaining the best use of it, and
2 Remove the old heater. maintaining it in perfect operating
3 The factory installed heaters have condition over a long period of time,
the wire run under the insulation of the constructor has a refrigeration
RTAD-SVX01A-E4 35