Professional Documents
Culture Documents
N EW
6000 tech. broch. 01347
Function
LEGIOMIX® This particular series of electronic mixing valves is equipped with a special
regulator that controls a set of programs for circuit thermal disinfection.
Electronic mixing valve with programmable thermal disinfection In addition it enables checking the temperature and time for thermal
and check on disinfection. Male threaded connections with union. disinfection are actually reached and undertaking the appropriate corrective
Consisting of: action. All the parameters are updated every day and logged, recording the
- three-way ball valve, temperatures by time.
- actuator,
- regulator,
- flow temperature probe,
- return temperature probe.
With auxiliary microswitches for disinfection management and other devices.
Fitted for remote control connection with RS-485 and MODBUS-RTU protocols.
Electric supply: 24 V - 50/60 Hz - (6,5+6) VA.
Max. working pressure: 10 bar. Spare parts for electronic mixing valve
Max. inlet temperature: 100 °C. with programmable thermal disinfection 6000 series
Adjustment temperature range: 20–85 °C. with threaded connections, 24 V.
Disinfection temperature range: 40–85 °C.
Protection class: IP 65 (actuator).
PATENT.
Code
Code Kv (m3/h)
170
NEW
6000 tech. broch. 01347
Spare parts for electronic mixing valve
with programmable thermal disinfection 6000 series
LEGIOMIX® with flanged connections.
Electronic mixing valve with programmable thermal disinfection
and check on disinfection. Flanged connection PN 16. Consisting of: Codice
- three-way ball valve,
- actuator, F69381 flow temperature probe
- regulator, F69393 three-way valve with flanged connections for codes 6000.6
- flow temperature probe,
F69394 three-way valve with flanged connections for codes 6000.8
- return temperature probe.
With auxiliary microswitches for disinfection management and other devices. F0000995 actuator 24 V (AC) for codes 600016 and 600018
Fitted for remote control connection with RS-485 and MODBUS-RTU protocols. F0000961 regulator with check on disinfection
Electric supply: 24 V - 50/60 Hz - (6,5+10,5) VA. F69591 recirculation probe for check on disinfection
Max. working pressure: 10 bar.
Max. inlet temperature: 100 °C. F69531 contact probe holder for recirculation loop
Adjustment temperature range: 20–85 °C. F69888 spare battery
Disinfection temperature range: 40–85 °C.
To be coupled with counterflanges EN 1092-1.
Protection class: IP 65 (actuator).
PATENT.
7550
MODBUS-RTU/BACnet converter for connection
with BMS systems.
Interface for products with MODBUS-RTU transmission
with systems using BACnet protocol.
Supply:
9–30 V (dc), 12–24 V (AC), 50/60 Hz
2,5 W / a 12 V 150 mA.
Certification: CE, IEC, FCC, RHOS.
Inputs/Outputs:
Ethernet port 10/100
RS-485 port + / - / GND.
Working temperature: -40–75 °C.
Relative humidity: 5–90 % without condensation.
Code Kv (m3/h)
BACnet
BMS
80
60
°C
40
20
LEGIOMIX®
0
Modbus/BACnet Converter
Modbus
BMS
recirculation probe
171