You are on page 1of 5

GENERATOR CAPABILITY VS AMBIENT TEMPERATURE Rev: 12Apr11

4P10.7-3350 CLASS B RISE 60 HZ ODP DESIGN < 3000 FT. ALT.

6773
6800
6729
6700
6625
6600
6489
6500

6400
6357
6300
6200
6200

6100
6010
6000

5900
KW @ 0.8 P.F.

5806
5800

5700

5600
5569
5500

5400
5306
5300

5200

5100
5065
5000

4900
4813
4800

4700

4600
4545
4500
-18 -12 -7 -1 4 10 16 21 27 32 38 43 49
0 10 20 30 40 50 60 70 80 90 100 110 120

AMB. DEG C/F

4/12/2011 KATO ENGINEERING


EFFICIENCY CURVES
4P10.7-3350 4160 VAC RATED: 6000 KVA 4800 KW @ 40 C AMB. B RISE

96.6

95.6
% EFF.

94.6 0.8 P.F.


1.0 P.F.

93.6

92.6

91.6
25 50 75 100

% KW LOAD

4/12/2011 KATO ENGINEERING


Stator Damage Curve
Class B rise, Class F insulation

1400

1200

1000
Percent of Rated Current

800

600

400

200

0
1 10 100 1000 10000 100000
Time (sec)
REACTIVE CAPABILITY CURVE
4800KW, 6000 KVA, 4160 VOLT, 60 HZ
SN 25472

8000

0.4PF
6000
0.6PF 0.7PF
0.8PF

4000
0.9PF

2000
Leading -- Reactive Load
kVAR -- Lagging

0
0 1000 2000 3000 4000 5000 6000 7000

-2000

--0.9PF

-4000
-0.8PF

-0.6PF
-0.4PF -0.7PF
-6000
Assumptions:
1. System reactance is 0.4 P.U.
2. Regulator stability limit is not included
3. Curve is based on linear reactive loading
-8000 Power (kW)
ESTIMATED SHORT CIRCUIT DECREMENT CURVE
6000 kVA, 4800 kW, 60 HZ, 0.8 PF
SN 25472
3PH, SYM, NL,
MAN, HOT

16.0 3PH, SYM, NL,


REG, HOT

3PH, ASYM, FL,


14.0 REG, COLD

L-L, SYM, NL,


12.0 MAN, HOT
PER UNIT LINE CURRENT

L-L, ASYM, FL,


REG, HOT
10.0
L-N, SYM, NL,
MAN. HOT
8.0
L-N, ASYM, FL,
REG, HOT
6.0

4.0

2.0

0.0
0.001 0.01 0.1 1 10
TIME IN SECONDS

You might also like