Professional Documents
Culture Documents
MMLG e MMLB (En)
MMLG e MMLB (En)
MMLG 04 –
Horizontal version of MMLG 02
MMLB 01 –
Multi-finger test plug
MMLB 02 –
Single-finger test plug
2
Application MMLG 01
3
P2 P1 Equipment side
A injection/monitoring sockets Live side sockets
S2 S1 (white background) (orange background)
B 1 2
2 1
Trip and
C 3 4 4
alarm 3
contacts 5 6
6 5
as
7 8
required 8 7
9 10 10 9
11 12 Fit external links
12 11 if station
Relay 13 14 aux. supply
(See Note 1) 14 13
scheme is required to
15 16
aux. 16 15 energise scheme.
supply 17 18 (For use with
18 17
19 20 MMLG 01 only).
20 19
21 22
22 21
23 24 A
Current 24 23 See Note 2
25 26 injection
26 25
sockets
27 28 B
as reqd. 28 27
See Note 2
MMLG 01 test block MMLB 01 test plug Note 2.
C
(rear view (front view) To avoid lethal electric shock
Note 1. representation) hazard external CT terminals
Terminals 13 and 14 are shorted together E/F must NOT be open circuited.
by the cover contacts when the cover Shorting links must be fitted
is in place. BEFORE plug insertion.
Protection scheme
Equipment side
Feeder Breaker Module injection/monitoring sockets Live side sockets
MBCZ 12 (white background) (orange background)
1 2
A 17 2 1
3 4 18 See Note 1
B 19 See Note 1 Main 4 3
Main zone CT's 5 6 20 zone
C 21 6 5
7 8 CT's
N 22 8 7
9 10 5 10 9
11 12 7
Note: 12 11
DC isolation is not 13 14 6 Trip A
14 13
available between Trip 15 16 8
terminals 13 and 14 16 15
17 18 10 9 18 17
19 20 12 11
20 19
21 22 23 Trip B
A 24 22 21
23 24 25 See Note 1
B 26 See Note 1 Current 24 23
Check zone CT's 25 26 injection
C 27 26 25
27 sockets
28 28
N 28 as reqd. 27
4
Current measurements This ensures that current transformer
secondary windings are short-
This single-finger test plug
circuited before they are
allows the current in any of the
disconnected from the protection
circuits routed through the test block
relay or scheme, thereby avoiding
to be monitored. When using the
dangerously high voltages. This is
single-finger test plug to monitor
illustrated in Figures 2 and 4.
secondary CT current, the leads
from this must never be open If it is desired to use the dc auxiliary
circuited, otherwise lethal voltages supply during testing, then it can be
may be generated. Before the linked across using the sockets in
single-finger test plug is inserted into the test plug. Test equipment can be
the test block, the connected connected to the relay or scheme
ammeter must be on the correct using the sockets in the white area
range. With this plug in the test of the test plug, and operation of
block, the ammeter range must not contacts can be monitored.
be changed. This avoids potentially Where more than one MMLG 01
lethal voltages being generated. test block is used in the connections
Voltage measurements to a relay, it may be advisable to
route the dc supply through each of
Hazardous live voltages will them as a safeguard against
be accessible via the single-finger inadvertent operation.
test plug leads when using this for
voltage measurements. Single-finger Test Plug
Connections to other equipment,
This test plug consists of two contact Figure 6: Type MMLB 02
eg., CTs, VTs and dc supplies,
strips which are insulated from each single-finger test plug.
should be made to odd numbered
other, and each of which is
terminals on the test block. This
connected to a lead, as shown in
ensures that when the test plug
Figure 6.
MMLB is used, the sockets in the
white half of the plug are the The test plug can be inserted into
isolated relay circuits, and the individual test positions in the test
sockets in the orange half are module as an alternative to the
connected to the potentially live multi-finger test plug, as shown in
supplies as shown in Figure 4. Figure 7. This single-finger test plug
allows the current in any of the
Note: It is important that
circuits routed through the test
the sockets in the
module to be monitored.
MMLB 01 test plug which
correspond to current Note: An ammeter on the correct
transformer secondary range should be connected to the
windings are shorted using two leads before the plug is
external links before the test inserted, especially if a CT
plug is inserted into the secondary circuit is being
MMLG test block. For a typical monitored.
example, refer to Figure 2.
5
Technical Data
Current withstand
MMLG 01/02, MMLB 01 All contact circuits rated at 20A
continuously or 400A for 1s.
MMLB 02 Rated at 10A continuously.
Atmospheric environment
Temperature
IEC 60255-6: 1988 Storage and transit –25°C to +70°C
Operating –25°C to +55°C
IEC 60068-2-1: 1990 Cold
IEC 60068-2-2: 1974 Dry Heat
Humidity
IEC 60068-2-3: 1969 56 days at 93% RH and +40°C
Enclosure Protection
IEC 60529: 1989
MMLG with cover fitted IP50 (dust protected)
MMLG (without cover) and MMLB 01 IP20
6
Mechanical environment
Vibration
IEC 60255-21-1: 1988 Response Class 2
EMC compliance
89/336/EEC These products have been classified
as electromagnetically benign and
are therefore excluded from the
European Community EMC Directive
(89/336/EEC).
Product safety
73/23/EEC Compliance with the European
Commission Low Voltage Directive.
EN61010-1: 1993/A2: 1995 Compliance is demonstrated by
EN60950: 1992/A11: 1997 reference to generic safety
standards.
7
ALSTOM T&D Protection & Control Ltd St Leonards Works, Stafford, ST17 4LX England
Tel: 44 (0) 1785 223251 Fax: 44 (0) 1785 212232 Email: enquiries@pcs.alstom.co.uk Internet: www.gecalsthomgpc.co.uk
©1998 ALSTOM T&D Protection & Control Ltd
Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should
only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it.
ALSTOM T&D Protection & Control Ltd cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.