ABB MOTORS AND GENERATORS, 2020 CHRISTIAN PAYERL
All Q&A´s will be sent out to all participants latest 2 weeks after the webinar
The presentation as well as the webinar recording will be available on the ABB webpage
The link to this page will be sent to all participants together with the Q&A file
Christian Payerl
Area Sales Manager Synchronous Condensers
christian.payerl@se.abb.com
Tel.: +46 21 320475
Mob.: +46 70 2601024
Marketing material:
https://new.abb.com/motors-
generators/synchronous-condensers
3
2 Excitation will be fully connected, the voltage and the power factor
regulator will start to operate, based on the voltage and power factor
reference
Synchronous Condenser supports the grid with instantaneous inertia (rotating mass):
Synchronous
generator f
Frequency
+/- ∆f Demand Supply
stabilization
\\\\\\\\\\\\\\
Grid AC
waveform df
MWs RoCoF =
(60 Hz) dt
Balancing
1
RoCoF ~
Inertia
December 16, 2020 Slide 8 ABB – Solutions for Synchronous Condenser Systems
—
Synchronous Condenser – Why
Fault level contribution
1
Inverter Based Resource:
i(t) 0
Fault current is tightly controlled by IBR control scheme
-1
Ic
-2
1 1.05 1.1 1.15
t(s)
December 16, 2020 Slide 9 ABB – Solutions for Synchronous Condenser Systems
—
Synchronous Condenser – Why
MVAr support (voltage regulation)
Capability diagram
Capability diagram at cooling water temperature of 48 .0° C
AMS 900 LH 14000 kVa 50 Hz 0.01 PF 13800 V 586 A 1500 rpm
0.0
Over-excited 1 0.5
2
1 0.7
0.8
0.6
0.9 Synchronous condenser operating region
0.4
Reactive power [p.u]
Over-excited
0.2
Produces reactive power
Active power [p.u.]
-0.0
Absorbs reactive power
U = 1.00
Under-excited -0.2
5 1
-0.4
0.9
Base apparent power 1 p.u. = 14000 kVa
-0.6 1 Stator heating limit
2 Rotor heating limit
-0.8 0.7 3 Practical stability limit
4
-1.0 0.5 4 Zero field-current limit
Under-excited 0.1 0.3 0.5 0.7 0.9 1.1 1.3 5 Core end heating limit
Implications Increased RoCoF, PLL instability, limitations Decreased SCL (protection Big variation of SCL (day/night), Production problems caused
Duck curve in power infeed (low SCL) problems), PLL instability, deeper voltage dips (reduced by weak grid (dips – process
inertia planning problems, rapid SCL), power quality problems interruptions), PQ emission
changes in power flow, system issues
stability, power system split
(different inertia)
What can Provide Inertia, Increase SCL, comply Increase SCL, Additional Provide controllable SCL, Less impacts from dips
Off-load MVAr’s to SCR requirements, available inertia, MVAr reduce depth of voltage from the grid, stronger
SynCon do Off-load MVAr’s for voltage support, dips, sink for unbalance, industry network,
decentralized system MVAr support Improved pf
strength (inertia/SCL -
multi-units)
Result Less interruptions, More stable grid, reduced Stability improvements, More stable distribution Reduced dip impact (Less
increased profit limitations in power less black-outs, grid, less PQ problems VSD trips), easier to start
transfer, increased profit decentralized grid support big loads, Increased profit
(SCL & inertia & voltage
regulation)
RoCoF – Rate of Change of Frequency | PLL – Phase Lock Loop | SCL – Short Circuit Level | SCR – Short Circuit Ratio | VSD – Variable
December 16, 2020 Slide 11
Speed Drives
—
Synchronous condensers – Where
Energy
intensive
Industry
Offshore Wind parks Synchronous Synchronous
or HVDC links condenser condenser
Synchronous
condenser
Industry/
Renewable generation large
commercial
Synchronous
condenser Synchronous
MV condenser
Distr.
grid
Mining industry
Installation from site Musselroe, Tasmania with two synchronous condensers 14000 kVAr
Synchronous condenser unit Fin fan cooler Main terminal box Pony motor Lube oil tank unit
REFERENCE #1
Installation from an Energy Park, Queensland first synchronous condenser with CAWA cooling
REFERENCE #2
Installation from site Borunga S/S, North South Wales, synchronous condensers with water cooling
275 kV BUS
11 kV BUS
11 kV/ 400V
MO scope of supply
SC PM VSD
~ ~
400V
NGR
M M M
400V
Radiator fans Water pumps Lube oil pumps Auxiliary power Pony motor
REFERENCE #3
Installation from site Darlington Point, North South Wales, synchronous condensers with CACA cooling
REFERENCE #4
REFERECE #5
Preliminary data
Key benefits:
– Redundancy No need for big 2-POL syncon´s
– Higher inertia to get high inertia or SCL support
– Control
VSC Synchronous
Condenser
Hybrid Synchronous Condenser – Best of both technologies, STATCOM and Synchronous Condenser
Hybrid Synchronous Condenser – Best of both technologies, STATCOM and Synchronous Condenser