4. PURLIN 1.1. LOADS + DL- Self weight of purlin + 15 Kg / m2 © LL-75Kg/m2 ‘+ Electrical Fascia load ~ 40 Kg / RM . ‘+ WL~As per IS 875. Calculations attached, ‘+ Seismic load : As per 1S 1893 - Zone Ill 1.2. Purlins are assumed to be continuous over support 1.3. Max yield strength of steel = 340 N/mm 1.4. Limiting deflection in purlin is considered as span / 120. 2. PORTAL (Column + Rafter) 2.1, LOADS ~ ‘+ DL- Self weight of portal + 20 Kg / m2 © LL-75Kg/ m2 ‘+ Electrical Fascia Load - 40 Kg / RM + WL~As per IS 875. Calculations attached. ‘+ Seismic load : As per IS 1893 — Zone II 2.2. Column and rafter are assumed to be rigidly connected. Portal is assumed to be fixed based. 2.3. Max yield strength of steel = 250 N / mm2 2.4. Limiting vertical deflection in portal is considered as span / 180. 2.5. Limiting horizontal sway in portal is considered as height / 150. 3. FOUNDATION 3.1. LOADS REACTION FROM PORTAL 3.2, Safe Bearing Capacity of soil assumed to be 150 KN / m2. 3.3. Foundations are designed using M30 grade concrete and Fe 416 steel 4. APPLICABLE CODES AND DESIGN METHODOLOGY 4.1, |S : 800-2007 ~ Limit State Design — For design of portal (Rafter + Column) 4.2. 1S : 801 — For design of cold roll formed members (Purtins) 4.3. |S : 456 — Limit State Design for design of foundations, 4.4, |S : 875 — For Dead load, Live load & Wind loads 4. IS : 1893 — For seismic loads