You are on page 1of 29

Transformer

Control Transformer

NDK JBK5
Control Transformer Control Transformer

Page K-01 Page K-04

JBK6 SG
Control Transformer Series Three-phase
Air-immersed
Transformer

Page K-06 Page K-08

Current Transformer

BH-0.66Ⅰ BH(SDH)-0.66Ⅱ
Current Transformer Current Transformer

Page K-11 Page K-15

BH-0.66Ⅲ RCT
Current Transformer Current Transformer

Page K-17 Page K-22

MES
Current Transformer

Page K-25

Potential Transformer

JDZ-1 JDG4-0.5
Voltage Transformer Voltage Transformer

Page K-26 Page K-27


Low Voltage VT & AVR & CT & PT
Transformer
2. Type designation
NDK-□

Rated output capacity (VA): 25VA~5000VA

Control

Single-phase

Corporation character

NDK Control Transformer 3. Operation conditions


1. General 3.1 Temperature: -5℃~+40℃, the average value within
1.1 Frequency: AC 50Hz/60Hz; 1 month should not exceed +30℃ and not exceed
1.2 Application: for control power supply of apparatus, +20℃ within 1 year;
partial illumination and indicator light of machine tool 3.2 Altitude: ≤2000m;
3.3 Relative humidity: ≤95%
and other mechanic equipments.
1.3 Standard: IEC/EN 61558, Q/ZT258.

4. Features
The transformer is characterized by excellent performances,
reliable operation, compact design, safe wiring, and wide
application, etc.

K-01 > >>


Low Voltage VT & AVR & CT & PT
Transformer
5. Technical data

Capacity Rated Rated Frequency


Model (VA) input voltage(V) output voltage(V) (Hz)

NDK-25 25
NDK-50 50
NDK-100 100
NDK-150 150
NDK-200 200
NDK-250 250
NDK-300 300
6, 12, 24,
NDK-400 400
230, 400 36, 110, 127, 50/60
NDK-500 500
230, 400
NDK-700 700
NDK-1000 1000
NDK-1500 1500
NDK-2000 2000
NDK-3000 3000
NDK-4000 4000
NDK-5000 5000

Note: Customized products are available.

6. Overall and mounting dimensions


NDK-25~1000
Emax

F
K

A C

Bmax Dmax

NDK-1500~5000

Dmax

K
Emax

F
10
20

A C
Bmax

> >> K-02


Low Voltage VT & AVR & CT & PT
Transformer
Mounting dimensions Mounting holes Overall dimensions
Model (A×C) (mm) (K×J) (mm) (B×D×E) (mm)

NDK-25 62.5×50 5×8 80×80×82


NDK-50 70×58 6×10 85×83×84
NDK-100 85×64 6×10 103×87×99
NDK-150 85×72 6×10 103×93×99
NDK-200 85×83 6×10 103×105×99
NDK-250 100×80 8×11 130×120×150
NDK-300 100×84 8×11 130×125×150
NDK-400 110×114 8×11 148×155×153
NDK-500 110×114 8×11 148×155×153
NDK-700 125×99 8×11 173×158×174
NDK-1000 125×123 8×11 173×186×174
NDK-1500 160×120 10×20 265×195×265
NDK-2000 160×130 10×20 265×205×275
NDK-3000 160×140 10×20 265×220×305
NDK-4000 190×180 10×20 315×260×305
NDK-5000 190×180 10×20 315×260×305

7. Wiring

7.1 NDK-100, capacity: 100VA, input 400V 230V, 7.2 NDK-100, capacity: 100VA, input 400V, output 36V;
output 36V 24V 12V 6V capacity 60VA 12V; capacity 40VA

0 230V 400V 0 400V


Primary
Primary

Iron core Iron core

Secondary
Secondary
36V 24V 12V 6V 0 36V 60VA 0 12V 40VA 0

7.3 NDK-100, capacity: 100VA, input 400V, output 36V 12V 7.4 NDK-100, capacity: 100VA, input 400V, output 36V

0 400V 0 400V
Primary Primary

Iron core Iron core

Secondary Secondary

36V 12V 0 36V 0

K-03 > >>


Low Voltage VT & AVR & CT & PT
Transformer
2. Type designation
JB K 5 - □ / □

Product code for the tropical zone:


"H" humid tropics, "A” dry tropical zone

Rated capacity: 40VA~2500VA

Design serial number

Control

Machine tool transformer


JBK5
Control Transformer
1. General
1.1 Application: JBK5 series control transformers are
suitable for AC circuit of 50Hz/60Hz, 3. Operating conditions
used as control sources for various mechanical equipment 3.1 Temperature: -5℃~+40℃,
and general electrical appliances, and used as power should not exceed +35℃ the average value within 24 hours.
supplies for work lighting and signal lamps. If the lowest limit is -10℃ or -25℃, please declared.
1.2 Standard: IEC/EN 61558, Q/ZT205 3.2 Altitude: ≤2000m;
3.3 Relative humidity ≤90%, when the average lower limit value
is under +25℃ within the month;
≤50% when the temperature is +40℃.
And when lower temperature;
the humidity could be relatively higher.
But the teaperature is lower, the humidity higher.

4. Structure features
We always adopt gas argon arc welding for the connection
among iron cores and between iron core and clamping piece
(mounting piece) of JBK5 series control transformers,
which enables the product to be an entirety, so that the
structure is more reasonable and reliable.

The mounting piece adopts technique of casting at a time and


the earthing lugs are made of high quality corrosion protection
alloy material, which sharply improves the reliability of
grounding.

In addition, the products have advantages of reliable operation, K


low dissipation of energy, compact volume, safe wiring,
wide applicability, etc.

> >> K-04


Low Voltage VT & AVR & CT & PT
Transformer
5. Overall and mounting dimensions
JBK5-40~630 type

Dmax

F
Emax

A
K
A
C
Bmax

JBK5-1000~2500 type
Bmax

Dmax

Dimension (mm) Item


Overall dimensions (mm) Mounting dimensions (mm) Mounting holes (mm)

Capacity (VA) B max D max E max A C K


40~63 79 78 92 66 46 4.8
100 85 95 97 72 62 4.8
160 97 96 105 84 73.5 5.8
250 97 110 105 84 85 5.8
400 121 110 122 100 85 7
630 151 116 143 130 90 7
1000 230 170 156 160 142 7×14
1600 258 185 168 180 155 7×14
2500 285 210 175 210 175 7×14

K-05 > >>


Low Voltage VT & AVR & CT & PT
Transformer
2. Type designation
JBK6-□

Rated capacity :40VA~3000VA

Design serial number

Control

Transformer

Machine tool
JBK6
Control Transformer
1. General 3. Operation conditions
1.1 Application: 3.1 Temperature: -5℃~+40℃,
JBK6 series control transformers are suitable for AC the average value should not exceed +35℃ within 24 hours.
circuit of 50Hz/60Hz, used as control power for If the lowest limit is -10℃ or -25℃, declared.
machine tools and industrial mechanical equipment, 3.2 Altitude:≤2000m;
and used as power supplies for electronic equipment, 3.3 Relative humidity ≤90%, when the average value
work lighting and signal lamps. is under +25℃; ≤50% when the temperature is +40℃.
1.2 Standard: Q/ZT205. Put the temperature is lower, the humidity is higher.

4. Structure features
This series transformer is the successor of other control
transformers, is made of imported material with advanced
technique, with advantages of reliable operation,
low loss of energy, compact volume, safe wiring,
wide applicability, etc.

We always adopt gas argon arc welding for the connection


among iron cores and between iron core and clamping piece
(mounting piece) of JBK6 series control transformers
(40~630VA), which enable the product to be an entirety,
so that the structure is more reasonable and reliable.
The mounting piece adopts technique of casting at a time,
The earthing are made of high quality corrosion protection alloy
material, which improves the reliability of grounding, with
advantages of reliable operation, low dissipation of energy,
compact volume, safe wiring, wide applicability, etc. K
This series control transformers are embedded with overheated
protector (automatic reset) in the coil, and equipped with over-
current protection connection terminal at input end, and the
end of overheat protector and over-current protection
connection terminal are connected to the connection end of
input side of transformer winding in series. Consequently, this
series control transformer has functions of over-current
protection and overheat protection.

> >> K-06


Low Voltage VT & AVR & CT & PT
Transformer
5. Overall and mounting dimensions
JBK6-40~630 type JBK6-1000~3000 type

Dmax

Emax
Emax

A C
Bmax

A C
Bmax

0 -5 % 380 +5%

-5% 380 +5% 0

Dmax
0 6 0 24 0 110
110 0 24 0 6 0

Dimension (mm) Item Overall dimensions (mm) Mounting dimensions (mm) Mounting holes (mm)

Capacity (VA) B max D max E max A C K


JBK6-40 79 78 97 66 46 4.8
JBK6-63 79 78 97 66 46 4.8
JBK6-100 85 94 102 72 62 4.8
JBK6-160 97 96 110 84 73.5 5.8
JBK6-250 97 110 110 84 85 5.8
JBK6-400 122 108 127 100 85 7
JBK6-630 152 116 148 130 90 7
JBK6-1000 152 165 168 125 123 8×11
JBK6-1600 194 155 200 160 123 8×11
JBK6-2500 194 200 200 160 168 8×11
JBK6-3000 194 200 200 160 168 8×11

K-07 > >>


Low Voltage VT & AVR & CT & PT
Transformer
2. Type designation
S G - □/□

Voltage grade (kV)

Rated capacity(kVA)

Normal cooling type

Three-phase

SG Three-phase
3. Normal working and mounting conditions
Air-immersed Transformer
3.1 Altitude not exceed2000m.
1. Scope of application 3.2 Ambient temperature within-5℃~+40℃.
SG series Three-phase Air-immersed Transformer, is natural 3.3 Relative humidity: less than 95%.
cooling indoor, it is applicable to the circuit of AC 3.4 In the ambient, there should not has the gas that corroding metal,
50Hz~60Hz, 1000V and below. It can be used in control destroying insulation. The transformer should not be corroded by
power of machine tool and mechanical equipment small type water, rain or snow.
power as well as work lighting and signal lamp power.

4. Configuration and characters


The transformers have two body types: exposed and fence. It has the
advantage of low consumption、small noise、better performance
against fire and free of pollution etc. The shell of the protective type
is made of steel plate, the transformer is in the shell. There are
several holes outside the shell to installation the power lines In
addition, this type can add the monitor meter of the voltage and
current according to the customer request, And if the capacity is
above 80KVA, it can also add the axial flow fan or wheels for
moving.

> >> K-08


Low Voltage VT & AVR & CT & PT
Transformer
5.Overall and mounting dimensions
5.1 The outline of SG series exposed dry cooling type transformer
(as sheet, fig.1)
5.2 The outline of SG series fence dry cooling type transformer
(as sheet, fig.2, fig.3, fig4, fig.5)

Exposed type Fence type (0.3kVA~3kVA)

Dmax

Bmax Dmax
Emax

Emax
A C
Bmax

Fence type (4kVA~20kVA) Fence type (30kVA~60kVA)

Bmax Dmax
Bmax Dmax
Emax

Emax
A A C
C

Fence type (80kVA~500kVA)

Bmax Dmax

铭牌

V V

A A A
Emax

K-09 > >>


Low Voltage VT & AVR & CT & PT
Transformer
Voltage (V) Overall dimensions (mm)
Connecting
Model Capacity Exposed Fence Exposed Fence
Input Output mark Mounting holes
Bmax Dmax Emax Bmax Dmax Emax A±5 C±5 A±5 C±5
SG-0.15 0.15 200 120 140 220 240 185 125 77 - -

SG-0.3 0.3 200 120 140 220 240 185 125 77 - - 6×15
SG-0.5 0.5 200 125 140 220 240 185 125 82 - -

SG-0.75 0.75 250 146 220 330 315 265 150 95 - -

SG-1 1 250 156 220 330 315 265 150 106 - -


Yyno
SG-1.5 1.5 660 380 315 220 260 370 355 315 220 103 - -
(Y/Yo) 8×16
SG-2 2 315 220 260 370 355 315 220 103 - -

SG-2.5 2.5 315 240 260 370 355 315 220 120 - -

SG-3 3 315 240 260 370 355 315 220 120 - -

SG-4 4 360 320 330 510 400 550 280 125 415 170
Yd
400 220 415 170
SG-5 5 (Y/△) 360 320 330 510 400 550 280 125
10×20
SG-6 6 360 320 330 510 400 550 280 125 415 170

SG-8 8 400 320 350 560 430 600 280 130 465 200

SG-10 10 430 350 390 560 430 600 310 145 465 200

SG-15 15 Dy 480 355 410 600 440 620 310 155 515 210
380 110
SG-20 20 (△/Y) 520 360 430 650 440 650 310 160 545 210

SG-30 30 690 430 500 870 500 780 420 170 765 270 Φ10
SG-40 40 710 450 510 960 640 830 420 175 865 320

SG-50 50 770 470 570 960 640 830 420 190 865 320

SG-60 60 Dd 780 490 570 1000 640 860 420 200 895 320
220 36
(△/△)
SG-80 80 855 500 600 1060 830 1080 420 205 with weels

SG-100 100 870 520 620 1140 840 1140 420 220 with weels

SG-150 150 960 580 700 1180 980 1250 640 240 with weels Φ14

SG-200 200 1000 600 750 1260 1000 1300 680 245 with weels

SG-300 300 1150 750 1000 1480 1020 1480 750 460 with weels Φ14
SG-500 500 1350 920 1260 1700 1500 1700 820 510 with weels

Notice: 6. Order notice


1. The dimensions of the above only for reference, when 6.1 product designation: three-phase normal-type transformer
the input current is more than 300A, the customer need to 6.2 product type
order specially, and the size will change correspondingly. 6.3 output capacity: 20kVA
2. You can choose the rated input/output voltage in the 6.4 frequency: 50Hz
sheet arbitrarily according to the demand. 6.5 rated input voltage (line-to-line voltage):380V
3. The voltage and size out of the sheet, should confer 6.6 rated input voltage (line-to-line voltage):220V
with consumer on their demand. 6.7 connection mode: input is “Y”, output is “△” or Mark Y/△
4. SG-80kVA and above fence type transformer body 6.8 exposed or fence: exposed
have wheels and fan cooling system, with ammeter
and voltmeter, as fig.5.
5. SG-4kVA~60kVA fence type transformer only have
body, with one indicator light of power, as fig.3, fig.4.
6. SG-0.3kVA~3kVA fence type transformer’s wiring
terminals are outside, with an indicator light of power,
as fig.2.
K

> >> K-10


Low Voltage VT & AVR & CT & PT
Current Transformer
3. Type designation
BH-0.66 -□Ⅰ

Category number

Width of window for bars

Current transformer series

BH-0.66 I
Current Transformer
1. Application
To be used in combination with measurement instruments:
ammeters, watt-hour meters, measurement units,
control relays, etc.

2. Technical data
2.1 Secondary current Isn: 5A
2.2 Rated voltage Ue:660 V
2.3 Frequency: 50/60 Hz
2.4 Instrument security factor (FS): 10
2.5 Operating temperature: -5°C to +40°C, humidity <80%
2.6 Standards: IEC 60044-1
2.7 Installation type: busbar or plate fixing

K-11 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
4. Technical data
Power(VA)
Accuracy class Number of
Transformation Overall and installing
turns through
Model ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

5/5 5 2.5
10/5 5 2.5
15/5 5 2.5
20/5 5 2.5

86
25/5 5 2.5
30/5 5 2.5
P1
40/5 5 2.5
38 68
BH-0.66 Solid type 50/5 5 2.5 82
68
75/5 5 2.5

75/5 2.5 1
S1 S2
φ22

80
P1
100/5 2.5 1
38 34
61
BH-0.66 20Ⅰ

30/5 5 2.5 5
50/5 5 2.5 3
75/5 5 2.5 2
75/5 2.5 1 S1 S2

100/5 2.5 1
80
11

100/5 5 5 2
150/5 5 2.5 1 φ23
P1
200/5 5 5 1 30.5
33
32
250/5 5 5 1
60.5
300/5 5 5 1
BH-0.66 30Ⅰ 400/5 5 5 1
30/5 2.5 2.5 5
50/5 2.5 2.5 3
75/5 2.5 2.5 2 S1 S2

75/5
98

5 2.5 1
31
21
11

100/5 5 2.5 1
100/5 5 5 2 P1

150/5 2.5 2.5 1 11.5


21.5
200/5
250/5
5
5
5
5
1
1
31.5
44
42 K
75
BH-0.66 30ⅠB
300/5 5 5 1

> >> K-12


Low Voltage VT & AVR & CT & PT
Current Transformer
Power(VA)
Accuracy class Number of
Transformation Overall and installing
turns through
Model ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

30/5 5 2.5 5
50/5 5 2.5 3
75/5 5 2.5 2
75/5 2.5 1
100/5 2.5 1
φ31
S1 S2
100/5 5 5 2

98
150/5 5 2.5 1

42
11
200/5 5 5 1
250/5 5 5 1 P1

300/5 5 5 1 11
42
400/5 5 5 1 40
43
500/5 10 10 5 5 1 75

BH-0.66 40Ⅰ 600/5 10 10 5 5 1


150/5 2.5 1
200/5 2.5 2.5 1
250/5 5 5 1
300/5 5 5 1 φ37
S1 S2

400/5 5 5 1

98
500/5 10 10 5 5 1
600/5 10 10 5 5 1 16

750/5 10 10 10 10 1 P1
50
800/5 10 10 10 10 1
51
40
82
1000/5 10 10 10 10 1
BH-0.66 50Ⅰ 1200/5 20 20 20 20 1
200/5 5 1
250/5 5 5 1
300/5 5 5 1
400/5 5 5 1 S1 S2

500/5 10 10 5 5 1
126

600/5 10 10 5 5 1
21

750/5 10 10 10 10 1
P1
800/5 10 10 10 10 1 φ46

50
1000/5 10 10 10 10 1 62
102 40
1200/5 20 20 20 20 1
BH-0.66 60Ⅰ 1500/5 20 20 20 20 1

K-13 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
Power(VA)
Accuracy class Number of
Transformation Overall and installing
Model turns through
ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

300/5 5 5 1
400/5 5 5 1
500/5 10 10 1 S1 S2

600/5 10 10 1

30.5
138

11
750/5 10 10 10 10 1
800/5 10 10 10 10 1
P1
1000/5 10 10 10 10 1
1200/5 20 20 20 20 1 50
60.5 φ52
81.5
1500/5 20 20 20 20 1 46
118
BH-0.66 80Ⅰ 2000/5 20 20 20 20 1
600/5 10 10 1

750/5 10 10 10 10 1 S1 S2

800/5 10 10 10 10 1

154
42
32
22
1000/5 10 10 10 10 1
P1

1200/5 20 20 20 20 1 50
φ62
62
82
102
1500/5 20 20 20 20 1

2000/5 20 20 20 20 1

46
145
BH-0.66 100Ⅰ 2500/5 40 40 40 40 1

1000/5 10 10 10 10 1
S1 S2

φ62
1200/5 20 20 20 20 1
136
36

1500/5 20 20 20 20 1

P1
2000/5 20 20 20 20 1
50
126
2500/5 40 40 40 40 1 190

3000/5 40 40 40 40 1
46

BH-0.66 120Ⅰ 4000/5 40 40 40 40 1

> >> K-14


Low Voltage VT & AVR & CT & PT
Current Transformer
2. Technical data
2.1 Secondary current Isn: 5A
2.2 Rated voltage Ue: 660 V
2.3 Frequency: 50/60 Hz
2.4 Instrument security factor (FS): 10
2.5 Operating temperature: -5°C to +40°C, humidity <80%
2.6 Altitude: ≤1000m
2.7 Standards: IEC 60044-1
2.8 Installation type: Busbar or plate fixing

3. Type designation
BH(SDH)-0.66 - □ Ⅱ

Category number

Width of window for bars

BH(SDH)-0.66 II Current transformer series

Current Transformer
1. Application
To be used in combination with measurement instruments:
ammeters, watt-hour meters,
measurement units, control relays, etc.

4. Technical data

Rated output(VA)
Accuracy class Number of
Transformation Overall and installing
Model turns through
ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

150/5 5 2.5 1
200/5 5 5 1
S1 S2

250/5 5 5 1
104

300/5 5 5 1
31

400/5 5 5 1
P1
500/5 10 10 5 5 1
600/5 10 10 5 5 1 42
44
78.5 46
BH(SDH)-0.66 40 Ⅱ 750/5 10 10 10 10 1

K-15 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
Rated output(VA)
Accuracy class Number of
Transformation Overall and installing
Model turns through
ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

150/5 2.5 1
200/5 5 5 1
250/5 5 5 1
300/5 5 5 1 S1 S2

400/5 5 5 1

106

31.5
500/5 10 10 5 5 1
600/5 10 10 5 5 1
P1
750/5 10 10 10 10 1
800/5 10 10 10 10 1 52
54
1000/5 10 10 10 10 1 87 46
BH(SDH)-0.66 50 Ⅱ
1200/5 20 20 20 20 1
300/5 5 5 1
400/5 5 5 1
500/5 10 10 5 5 1 S1 S2

600/5 10 10 5 5 1

110
31.5
750/5 10 10 10 10 1
800/5 10 10 10 10 1
P1

1000/5 10 10 10 10 1 53
62
1200/5 20 20 20 20 1 102
48

BH(SDH)-0.66 60 Ⅱ 1500/5 20 20 20 20 1
600/5 10 10 1
750/5 10 10 1 S1 S2

800/5 10 10 10 10 1
32.5
118

1000/5 10 10 10 10 1
P1
1200/5 20 20 20 20 1
60
1500/5 20 20 20 20 1 82
122 47
BH(SDH)-0.66 80 Ⅱ 2000/5 20 20 20 20 1
1000/5 10 10 10 10 1
S1 S2

1200/5 20 20 20 20 1
122
32.5

1500/5 20 20 20 20 1
P1

2000/5 20 20 20 20 1 74
102
BH(SDH)-0.66 100 Ⅱ 2500/5 40 40 40 40 1
140 50

1000/5 10 10 10 10 1
1200/5 20 20 20 20 1 S1 S2

1500/5 20 20 20 20 1
154
52

2000/5 20 20 20 20 1
2500/5 40 40 40 40 1 P1

BH(SDH)-0.66 120 Ⅱ
3000/5 40 40 40 40 1 54
122
169 48
K
4000/5 40 40 40 40 1

> >> K-16


Low Voltage VT & AVR & CT & PT
Current Transformer
2. Technical data
2.1 Secondary current Isn: 5A
2.2 Rated voltage Ue: 660 V
2.3 Frequency: 50/60 Hz
2.4 Instrument security factor (FS): 10
2.5 Operating temperature: -5°C to +40°C, humidity <80%
2.6 Standards: IEC 60044-1
2.7 Installation type: busbar or plate fixing

3. Type designation
BH-0.66 - □ Ⅲ

Category number

Width of window for bars

BH-0.66 III
Current transformer series
Current Transformer
1. Application
To be used in combination with measurement instruments:
ammeters, watt-hour meters,
measurement units, control relays, etc.

4. Technical data

Rated output(VA)
Accuracy class Number of
Transformation Overall and installing
Model turns through
ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

75/5 2.5 1
S1 S2
86
44.5
11

P1

100/5 5 1
φ20
22
41
150/5 10 5 1 64
45
54

36

200/5 10 5 1
BH-0.66 20 Ⅲ

K-17 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
Rated output(VA)
Accuracy class Number of
Transformation Overall and installing
Model turns through
ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

150/5 10 5 5 5 1 68
S1 S2 59
200/5 10 5 5 5 1 50

92

P1
54
31
21
11
250/5 10 5 5 5 1

300/5 10 10 5 5 1
11
21
400/5 10 10 5 5 1 31
49

BH-0.66 30 Ⅲ 500/5 10 10 10 10 1 72

150/5 10 5 1
200/5 10 5 1 68
59
250/5 10 5 1 S1 S2 50

300/5 10 10 5 5 1

102

31
11

P1
62
42
400/5 10 10 5 5 1
500/5 10 10 10 10 1
600/5 10 10 10 10 1
11
750/5 10 10 10 10 1 31
42
800/5 10 10 10 10 1 59
84
BH-0.66 40 Ⅲ 1000/5 10 10 10 10 1
300/5 10 10 1
400/5 10 10 1 S1 S2
68
φ36 59
500/5 10 10 10 10 1 107 50

41
21
11

P1
65
52
600/5 10 10 10 10 1
750/5 10 10 10 10 1
11
800/5 10 10 10 10 1 21
41
52
1000/5 10 10 10 10 1 61
88
BH-0.66 50 Ⅲ 1200/5 20 20 20 20 1
500/5 10 10 10 10 1
68
600/5 10 10 10 10 1 S1 S2 59
P1 50
750/5 10 10 10 10 1
123
86
34

800/5 10 10 10 10 1
1000/5 10 10 10 10 1
1200/5 20 20 20 20 1 62
90
BH-0.66 60 Ⅲ 1500/5 20 20 20 20 1 112

500/5 10 10 10 10 1
600/5 10 10 10 10 1 68
S1 S2
59
750/5 10 10 10 10 1 P1 50

800/5 10 10 10 10 1
152
109
54

1000/5 10 10 10 10 1
1200/5 20 20 20 20 1
1500/5 20 20 20 20 1 82
K
105
2000/5 40 40 40 40 1 132

BH-0.66 80 Ⅲ 2500/5 40 40 40 40 1

> >> K-18


Low Voltage VT & AVR & CT & PT
Current Transformer
Rated output(VA)
Accuracy class Number of
Transformation Overall and installing
Model turns through
ratio(Ipn/Isn) (A) dimensions (mm)
iron core
1 0.5 0.5S 0.2

800/5 10 10 10 10 1

S1 S2

1000/5 10 10 10 10 1 P1

108
150

53
1200/5 20 20 20 20 1

102
1500/5 20 20 20 20 1 125
152

2000/5 40 40 40 40 1

68
59
50
2500/5 40 40 40 40 1
BH-0.66 100 Ⅲ

1000/5 10 10 10 10 1

S1 S2
1200/5 20 20 20 20 1 P1

151
109

52
1500/5 20 20 20 20 1

2000/5 40 40 40 40 1
122
147
2500/5 40 40 40 40 1 174

3000/5 40 40 40 40 1
61
52
70

4000/5 40 40 40 40 1
BH-0.66 120 Ⅲ

5. Features
5.1 The product is characterized by high accuracy, fewer accessories and easy mounting, etc.
5.2 Made of single or several pieces of enameled wire evenly distributed around the core, secondary winding is characterized by good
magnetic conductivity capability, low power consumption, small magnetic-flux-leakage and convenient compensation adjustment.
5.3 Encapsulated in fire-reatardant plastic, the enclosure is characterized by good insulation capacity, high intensity, elegant apperance,
light convenient mounting, ect.

K-19 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
6. Installation

The fig below illustrates how the current transformer BH is mounted


Fixing through busbar

Screw M5

Busbar(one or several pcs)


Fixing plate

Insulation baffle
Insulation seat gasket

Base mounting

Busbar or cable

Screw M4 and washer

Mounting base

Surface of switchgear

> >> K-20


Low Voltage VT & AVR & CT & PT
Current Transformer

The fig below illustrates how the current transfcrmer BH-0.66 is mounted
Fixing through busbar

Screw M5

Insulation seat gasket

Busbar(one or several pcs)

Insulation baffle

Base mounting

Busbar or cable

Mounting base

Surface of switchgear

Screw and washer

K-21 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
2. Technical data
2.1 Secondary current Isn: 5A
2.2 Rated voltage Ue: 660 V
2.3 Frequency: 50/60 Hz
2.4 Instrument security factor (FS): 10
2.5 Operating temperature: -5℃+40℃, humidity<80%
2.6 Standards: IEC 60044-1
2.7 Installation type: busbar or plate fixing

3. Type designation
RCT - □

Diameter of window for bars

RCT Current Transformer


1. Application Current transformer series
1.1 Application: to be used
in combination with measurement
instruments: ammeters, watt-hour meters,
measurement units, control relays, etc.

4. Features
4.1 The product is characterized by compact design,
light weight, etc.
4.2 Made of single or several pieces of enameled wire evenly
distributed around the core, secondary winding is
characterized by good magnetic conductivity capability,
low power consumption, small magnetic-flux-leakage
and convenient compensation adjustment.
4.3 Encapsulated in fire-retardant plastic,
the enclosure is characterized by good insulation capacity,
high intensity, elegant appearance, light weight,
convenient mounting, etc.

> >> K-22


Low Voltage VT & AVR & CT & PT
Current Transformer
5. Technical data
Rated output(VA)
Number of
Current Overall and installing
Model Accuracy class turns through
ratio (A) dimensions (mm)
iron core
0.5 1

75/5 2.5 2.5 1

94
φ25
φ78

100/5 2.5 2.5 1 76 8.5


94 55

RCT-25

75/5 2.5 2.5 1

100/5 2.5 2.5 1

150/5 5 5 1

94
φ35
φ78

200/5 5 5 1
76 8.5
94 55

250/5 5 5 1

300/5 5 5 1
RCT-35

400/5 5 5 1

500/5 10 10 1

600/5 10 10 1

120
750/5 10 10 1
φ105 φ60

800/5 10 10 1 8.5
80 55
110

1000/5 10 10 1

RCT-60 1200/5 10 10 1

800/5 10 10 1

1000/5 10 10 1
153

1200/5 10 10 1

φ136 φ90
1500/5 10 10 1

80 8.5

RCT-90 1600/5 10 10 1 110 42

1500/5 10 10 1

1600/5 10 10 1
180

2000/5 20 20 1
φ110

2500/5 20 20 1 φ162

80
110 8.5
RCT-110 3000/5 20 20 1 42

K-23 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
5. Technical data

Rated load (VA)


Model Current rate (A) Overall and installing dimensions (mm)
0.5 class
150/5 5 41

200/5 10

88
250/5 10
φ31

300/5 10

45
MES-30 400/5 10 80

52
300/5 5

400/5 5

88
11
41

500/5 10

45
MES-40 600/5 10 80

600/5 10 56

750/5 10

φ50

800/5 10
118
12

61

1000/5 10

1200/5 10
82

1500/5 10 101
MES-60

500/5 10
118 56

600/5 10

750/5 10

800/5 10
130

42

22
32

102
1000/5 10
60

φ62
1200/5 10 62
82
P1
126
1500/5 10 14
145
14

MES-100I 2000/5 10 K
125 53

2000/5 30

2500/5 30
148

53

102
3000/5 30
65

P1
2.2
1.4

4000/5 30 14 133 14
MES-100II 152

> >> K-24


Low Voltage VT & AVR & CT & PT
Current Transformer
2. Technical data
2.1 Secondary current Isn: 5A
2.2 Rated voltage Ue: 660 V
2.3 Frequency: 50/60 Hz
2.4 Instrument security factor (FS): 10
2.5 Operating temperature: -5℃to +40℃,
the average value within 24h
shall not exceed +35℃, humidity <80%.
2.6 Standards: IEC 60044-1
2.7 Installation type: busbar or plate fixing

3. Type designation
MES - □

Width of window for bars

Current transformer series

MES Current Transformer


1. Application
1.1 Application: to be used
in combination with measurement 4. Normal working conditions
instruments: ammeters, watt-hour meters, and mounting conditions
measurement units, control relays, etc. 4.1 Installation site: Indoors.
4.2 Ambient temperature: -5℃~40℃, temperature ≤30℃.
4.3 Ambient humidity: Relative humidity ≤80%.
4.4 Altitude: ≤1000m.
4.5 Atmospheric condition: Be free from severe contamination.

K-25 > >>


Low Voltage VT & AVR & CT & PT
Current Transformer
2. Technical data
2.1 Rated voltage Ue: 1.14kV
2.2 Frequency: 50 Hz
2.3 Operating temperature: -5℃ to +40℃, humidity <80%
2.4 Standards: IEC 60044-2

3. Type designation
JDZ - 1

Rated primary voltage Upn(kV)

Voltage transformer series

JDZ Voltage Transformer

1. Function
1.1Function: Adopting the value of voltage on the
primary to the characteristics of metering or
protection devices by supplying a secondary
voltage that is proportional and lower;
Used in combination with measurement instruments:
ammeters, watt-hour meters,
measurement units, control relays, etc.

4. Technical data

Rated
Transformation ratio Accuracy Max. output
Model output Overall and installing dimensions (mm)
Upn/Usn (V) class (VA)
(VA)

380-690/100 5 3 30 A1 A2 B
K
95max

690-1140/100 5 3 30 62.5 65
110max 92

> >> K-26


Low Voltage VT & AVR & CT & PT
Current Transformer
2. Technical data
2.1 Rated voltage Ue: 0.5kV
2.2 Frequency: 50 Hz
2.3 Operating temperature: -5℃ to +40℃, humidity <80%
2.4 Standards: IEC 60044-2

3. Type designation
JDG4 - 0.5

Rated primary voltage Upn(kV)

Voltage transformer series

JDG4-0.5
Voltage Transformer
1.Function
1.1 Function: Adopting the value of voltage on the
primary to the characteristics of metering or
protection devices by supplying a secondary voltage
that is proportional and lower;
Used in combination with measurement instruments:
ammeters, watt-hour meters,
measurement units, control relays, etc.

4. Technical data

Rated
Transformation ratio Accuracy Max. output
Model output Overall and installing dimensions (mm)
Upn/Usn (V/V) class (VA)
(VA)

200/100 15 0.5 100


a b

220/100 15 0.5 100


78±0.55
155max

96

380/100 15 0.5 100


65±0.49
125max

500/100 15 0.5 100

K-27 > >>