RV Generator Set
i
7 ROUTINE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Generator Set Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Oil and Filter Change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
Fan Belt . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
Bio−diesel Fuels B5 − B20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-9
Air Cleaner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
AC Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
Crankcase Breather . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-11
Muffler/Spark Arrester . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Cleaning the Generator Set . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Initial Starting and Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
8 WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
ii
Safety Precautions
Thoroughly read the OPERATOR’S MANUAL Used engine oil has been identified by some
before operating the genset. Safe operation and state and federal agencies as causing cancer
top performance can be obtained only with or reproductive toxicity. Do not ingest, inhale,
proper operation and maintenance. or contact used oil or its vapors.
The following symbols in this Manual alert you to Benzene and lead in some gasolines have
potential hazards to the operator, service person been identified by some state and federal
and equipment. agencies as causing cancer or reproductive
toxicity. Do not to ingest, inhale or contact gas-
Alerts you to an immediate hazard oline or its vapors.
which will result in severe personal injury or
death. Do not work on the genset when mentally or
physically fatigued or after consuming alcohol
Alerts you to a hazard or unsafe or drugs.
practice which can result in severe personal in-
jury or death. Carefully follow all applicable local, state and
federal codes.
Alerts you to a hazard or unsafe
practice which can result in personal injury or GENERATOR VOLTAGE IS DEADLY!
equipment damage.
Generator output connections must be made
Electricity, fuel, exhaust, moving parts and batteries by a qualified electrician in accordance with ap-
present hazards which can result in severe person- plicable codes.
al injury or death.
The genset must not be connected to the public
GENERAL PRECAUTIONS utility or any other source of electrical power.
Keep ABC fire extinguishers handy. Connection could lead to electrocution of utility
workers, damage to equipment and fire. An ap-
Make sure all fasteners are secure and torqued proved switching device must be used to pre-
properly. vent interconnections.
Keep the genset and its compartment clean. Use caution when working on live electrical
Excess oil and oily rags can catch fire. Dirt and equipment. Remove jewelry, make sure cloth-
gear stowed in the compartment can restrict ing and shoes are dry and stand on a dry wood-
cooling air. en platform on the ground or floor.
Let the engine cool down before removing the FUEL IS FLAMMABLE AND EXPLOSIVE
coolant pressure cap or opening the coolant
drain. Hot coolant under pressure can spray Keep flames, cigarettes, sparks, pilot lights,
out and cause severe burns. electrical arc-producing equipment and
switches and all other sources of ignition well
Before working on the genset, disconnect the away from areas where fuel fumes are present
negative (−) battery cable at the battery to pre- and areas sharing ventilation.
vent starting.
Fuel lines must be secured, free of leaks and
Use caution when making adjustments while separated or shielded from electrical wiring.
the genset is running—hot, moving or electri-
cally live parts can cause severe personal inju- Use approved non-conductive flexible fuel
ry or death. hose for fuel connections at the genset.
iii
ENGINE EXHAUST IS DEADLY! BATTERY GAS IS EXPLOSIVE
Learn the symptoms of carbon monoxide poi-
soning in this Manual. Wear safety glasses and do not smoke while
servicing batteries.
Never sleep in the vehicle while the genset is
running unless the vehicle has a working car- When disconnecting or reconnecting battery
bon monoxide detector. cables, always disconnect the negative (−) bat-
tery cable first and reconnect it last to reduce
The exhaust system must be installed in accor- arcing.
dance with the genset Installation Manual.
Do not use engine cooling air to heat the ve- DO NOT OPERATE IN FLAMMABLE AND
hicle interior. EXPLOSIVE ENVIRONMENTS
Make sure there is ample fresh air when oper-
ating the genset in a confined area. Flammable vapor can cause a diesel engine to
overspeed and become difficult to stop, resulting in
MOVING PARTS CAN CAUSE SEVERE possible fire, explosion, severe personal injury and
PERSONAL INJURY OR DEATH death. Do not operate a diesel-powered genset
where a flammable vapor environment can be
Do not wear loose clothing or jewelry near mov- created by fuel spill, leak, etc., unless the gen-
ing parts such as PTO shafts, fans, belts and set is equipped with an automatic safety device
pulleys. to block the air intake and stop the engine. The
Keep hands away from moving parts. owners and operators of the genset are solely re-
sponsible for operating the genset safely. Contact
Keep guards in place over fans, belts, pulleys, your authorized Onan/Cummins dealer or distribu-
etc. tor for more information.
Mobile-3
iv
1. Introduction
1-1
Be prepared if an accident occurs. to be ready to respond to an accident. Learn to be
safety conscious and make safe practices a part of
Agencies such as the Red Cross and local police your work routine. Do not work when tired or after
and fire departments offer courses in first aid, CPR, consuming any alcohol or drug that makes the op-
and fire control. Take advantage of this information eration of equipment unsafe.
TABLE 1-1
HAZARDS AND THEIR SOURCES
1-2
SET REMOVAL 3. Disconnect the remote control plug wire from
the generator set (if applicable).
Some service procedures require removing the
generator set from the vehicle. Because of the wide
variety of installations, it is not possible to specify 4. Disconnect the generator load wires. Tag for
exact removal procedures for each genset. If a sat- identification when reconnecting.
isfactory method for removing a particular set can-
not be determined, contact the vehicle manufactur- 5. Disconnect the exhaust system and support
er or the set installer for their recommendations. brackets or hangers, to allow set removal.
WARNING Leakage of fuel in or around the When reinstalling the set, be sure all mounting
generator set compartment presents the hazard hardware, and electrical, exhaust, and fuel system
of fire or explosion that can cause severe per- components are connected exactly as they were
sonal injury or death. Do not disconnect or con- before removal. See the appropriate installation
nect battery cables if fuel vapors are present. manual during reinstallation for important safety
Ventilate the compartment thoroughly: park ve- precautions.
hicles outdoors in a well ventilated area.
1. Disconnect the generator set negative (-) bat- Check for oil and fuel leaks. Check the exhaust sys-
tery cable at the battery terminal. tem audibly and visually with the generator set run-
ning. Repair leaks immediately. Replace worn,
2. Disconnect the generator set positive (+) bat- damaged, or corroded exhaust and fuel line compo-
tery cable from the wire harness. nents before leaks occur.
1-3
Blank Page
1-4
2. Engine Controls
Fault Breaker CB12: A manual reset breaker that K14 Fuel Solenoid: It opens the fuel control valve
shuts down the engine for low oil pressure and high when the start/stop switch is placed in the Start
coolant temperatures. position.
2-1
S11 START-STOP-
PREHEAT SWITCH
COVER
J3 REMOTE DC CONTROL
A11 ENGINE MONITOR
CONNECTION RELAY - START BREAKER CB11
CIRCUIT BOARD
SOLENOID
2-2
OIL PRESSURE
OIL PRESSURE SENDER (M12)
SWITCH (S1)
(SHUTDOWN) COOLANT SHUTDOWN
SWITCH (S2)
OIL PRESSURE
SWITCH (S6)
(POWER LATCH)
COOLANT TEMPERATURE
SENDER (E2)
2-3
Engine Temperature Monitors Start-Disconnect Sequence: As the generator
gains speed and output voltage, A11-K15 starter
Refer to Figure 2-2 for the location of the engine protection relay energizes at about 90 VAC.
temperature sensors. A11-K15 NC contact opens and de-energizes start
solenoid relay K11. K11 then disconnects B+ from
Coolant Temperature Sender E2: The resistance the starter solenoid (to stop the cranking motor) and
of the sender unit changes with the engine coolant from the glow plug heaters. If the generator fails to
temperature and causes a reading on the coolant develop voltage, the engine will attempt to start but
temperature meter (optional). The meter range is will stop as soon as the Start switch is released.
100 to 250 F (40 to 121 C).
High Coolant Temperature Switch S2: This The two K15 NO (normally open) contacts close
switch closes if the coolant temperature rises to and function as follows:
250 F (121 C), activating the fault breaker CB12
Closes circuit for S1 and S2 (low oil pressure
and stopping the engine.
and high coolant temperature switches respec-
Control Operation tively)
To understand control operation, refer to the follow- Provides another ground path for K12 coil
ing text and the schematic diagram (Figure 2-3). (through K11 coil) similar to S6.
Starting Sequence: When start/stop switch S11 is Battery Charge Circuit: Alternator G1, powered
held in the Stop (preheat) position, battery B+ is by a belt from the engine, supplies B+ voltage to re-
connected to the coil of heater relay K13. The relay charge the generator set starting battery through
contacts close and connect B+ to heaters HR1 - circuit breaker CB13.
HR4.
After the preheat time interval, the operator holds Stopping Sequence: Placing S11 in the Stop posi-
S11 in the Start position. This connects B+ to K14 tion puts B+ (through diode CR2) on the ground side
fuel solenoid relay and through A11-K15 NC (nor- of the A11-K12 power relay. This causes K12 to de-
mally closed) contacts to K11 start solenoid relay. energize and disconnect B+ from CB12 and K1 fuel
These relays actuate K1 fuel solenoid, B1 solenoid/ solenoid. De-energizing K1 shuts off the fuel flow to
starter motor and heaters HR1 - HR4 (via K13 NC stop the engine.
contacts).
Fault Shutdown: Fault breaker CB12 opens to
A11-K12 power relay is actuated after a short delay, stop the engine any time a fault sensor closes the
when the control power latch switch S6 closes. S6 circuit to ground. The fault sensors as shown in Fig-
is closed when oil pressure rises to 5 psi (34 kPa), ure 2-2 are:
assuring engine lubrication before the set reaches
full operating speed. Normally open (NO) contacts S1 low oil pressure
on A11-K12 close, supplying B+ to the other compo-
nents on the engine monitor board. S2 high coolant temperature
2-4
ENGINE PARTS
B1 Starter and solenoid
BT1 Battery (12V)
E1 Sender (oil pressure)
E2 Sender (coolant temperature)
HR1-4 Heater - glow plug
E5 Fuel pump - electric
K1 Fuel solenoid
S1 Switch - low oil pressure
S2 Switch - high coolant
temperature
S6 Switch - control power latch
G1 Alternator
2-5
Remote Control Operation (Optional): The gen- CONTROL TROUBLESHOOTING
erator set may be operated from a remote switch
connected to the control receptacle J3. Installation
instructions are furnished with the kit available from The information in this section is divided into three
Onan. See Figure 2-4. flow charts. Determine the problem and then refer
to the appropriate flow chart (A, B, or C) for the trou-
bleshooting procedures.
J4 J3
RUN LIGHT
Check all modifications, repairs, and re-
placements performed since last satisfac-
tory operation of set. A loose wire connec-
tion overlooked when installing a replace-
OIL ment part could cause problems. An in-
PRESSURE correct connection, an opened switch or
circuit breaker, or a loose plug-in are all po-
tential problems that can be eliminated by
WATER a visual check.
TEMPERATURE
2-6
FLOW CHART A. ENGINE DOES NOT CRANK
WARNING Many troubleshooting procedures present hazards that can result in severe personal in-
jury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review Safety Precautions.
START
Is battery dead? yes Check battery per Checkout [A] and recharge
or replace. Check battery charger operation
per Checkout [C].
no
Check CB11 circuit breaker. If okay, jumper Check battery cables for clean tight connec-
battery cable B+ connection to B1 starter so- no tions (ref. Checkout [B]). Check B1 starter so-
lenoid terminal. Does engine crank? lenoid and motor: if bad, repair or replace.
yes
With S11 in Start position, is battery voltage Check B+ wiring to S11, and between S11 and
no
present between K11 terminal S and ground? K11. Check NC contacts of A11-K15. Re-
place if bad.
yes
If K11 does not energize, test per Checkout Check B+ wiring between K11 and B1 sole-
[D] and replace if bad. Is battery voltage pres- no noid terminal. Replace if bad. Check K1
ent at B1 solenoid terminal with S11 in Start plunger travel for freedom to bottom in sole-
position? noid (necessary to open pull coil circuit).
2-7
FLOW CHART B. ENGINE CRANKS BUT DOES NOT START
WARNING Many troubleshooting procedures present hazards that can result in severe personal in-
jury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review Safety Precautions.
START
Is engine getting fuel? Exhaust smoke should Check fuel system: fuel tank level, shut-off
be blue-white and fuel flow steady from fuel no valves, fuel lines and connections, fuel filters,
return line. fuel pump and injection pump. Okay?
yes
Is battery B+ applied to glow plug heaters Check B+ circuit through S11. Test S11 per
when switch S11 is in Preheat and Start posi- Checkout [G]. Test K14 per Checkout [F].
tions?
yes no
Incorrect fuel? See Operator’s Manual rec- Check switch S11 per Checkout [G]. Check
ommendations. heater relay per Checkout [E]. Check heater
wiring.
2-8
FLOW CHART C. ENGINE STARTS BUT STOPS AFTER RUNNING SEVERAL SECONDS
WARNING Many troubleshooting procedures present hazards that can result in severe personal in-
jury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review Safety Precautions.
Is a fault condition indicated by fault breaker Check for a possible fault condition. If none,
yes
CB12 on control panel? check fault monitors S1 through S4 and fault
breaker CB12 for improper wiring.
no
Check relay K12 per Checkout [H]. Is K12 Check for closing of S6 power latch switch. If
no
good? switch is OK, check mechanical adjustment of
K1 solenoid: is rod adjusted to correct length
to allow the hold-in coil of K1 to latch? If K1
adjustment is OK and problem remains, re-
yes place engine monitor PC board.
Does DC control breaker trip after generator Check all B+ wiring for shorts to ground.
yes
set is started? Check fuel solenoid adjustment.
2-9
Blank Page
2-10
3. Engine Control Service
With the starter motor running, check these voltage 3. If the contacts are good, battery voltage should
drops: be read between terminal 1 and ground. The
voltage drop measured across the contacts
1. From the battery negative post (not the cable should never exceed one volt in circuit applica-
clamp) to the cylinder block tion.
3-1
[E] 3. Open and close switch while observing the
ohmmeter. A normally open (NO) switch
HEATER (GLOW PLUG) RELAY CHECK should indicate infinite resistance when open
(K13) and continuity when closed. A normally closed
(NC) switch should indicate continuity when
1. Connect the relay coil voltage across the relay closed and infinite resistance when open.
coil terminals. The relay should activate if coil
is okay. 4. Replace switch if defective.
2. Place ohmmeter leads across switch. 7. Remove the jumpers and reconnect CB12-2A.
3-2
4. Generator/Voltage Regulator
GENERAL DESCRIPTION erator cooling air which is drawn in through the end
bell and discharged through an outlet in the blower
The YK generator (Figure 4-1) is a four-pole, revolv- end.
ing field, brush-type design with drip-proof
construction.
A ball bearing in the end bell supports the outer end
The generator rotor is directly coupled to the engine of the rotor shaft. The end bell is attached with four
flywheel with a rigid drive disc. Engine speed deter- studs that thread into the generator adapter casting.
mines generator output voltage and frequency. A The genset brushes are mounted in the end bell
centrifugal blower on the drive disc circulates gen- (see Figure 4-2).
STATOR GENERATOR
ASSEMBLY ADAPTER
FAN
END BELL GUARD
COVER
ROTOR
ASSEMBLY
OUTPUT AND
CONTROL LEADS
COLLECTOR
RINGS
GENERATOR
DRIVE DISK
GENERATOR
DRIVE HUB
END
STATOR BEARING
END BELL ASSEMBLY STATOR
(SEE FIGURE 4-2 FOR ASSEMBLY WRAPPER
BRUSH CONFIGURATION)
GENERATOR FAN
4-1
LEAD (F2 TO LEAD (F1 TO
VR1-2) VR1-1)
O-RING
BRUSH BLOCK
ASSEMBLY
4-2
FIGURE 4-3. SINGLE-PHASE GENERATOR SCHEMATIC
4-3
FIGURE 4-4. THREE-PHASE GENERATOR SCHEMATIC
4-4
GENERATOR OPERATION which in turn supplies the field. Rated output
voltage is thereby maintained as the load var-
Refer to Figures 4-3 and 4-4, the generator sche- ies.
matics, while working through the following descrip-
tion. ELECTRONIC VOLTAGE REGULATOR
1. Voltage regulator VR1 (three-phase: VR21) The voltage regulator controls the output of the gen-
supplies DC to the field winding (F1 - F2 leads) erator so that a constant voltage is maintained un-
through brushes and slip rings, thereby estab- der varying load conditions.
lishing a revolving 4-pole magnetic field. The
battery is connected during startup to initiate Only the basic functions of the regulator are de-
field excitation. Voltage regulator VR1 supplies scribed (Figure 4-5). Voltage from quadrature wind-
field current during operation. Rated output ings Q1/Q2 supply power to the voltage regulator it-
voltage is maintained as the generator load self. The voltage regulator in turn supplies an ex-
varies, by varying field current to maintain field citation voltage (F1/F2) that is directly proportionate
strength proportional to the load. to the output voltage (L1/L0) it senses. Any
2. The revolving magnetic field induces AC in the changes in the generator output voltage produce a
stator windings (T1 - T2 and T3 - T4) which are corresponding change in the excitation voltage pro-
connected to the load. vided by the regulator.
3. Under light load, the stator windings can supply On the HDKAG, the voltage regulator assembly in-
sufficient current for the field to maintain rated cludes a potentiometer which enables a slight de-
output voltage. gree of output voltage adjustment. The voltage reg-
4. As the load increases, load currents increase, ulator assembly contains no user-serviceable
resulting in a proportional increase of current, parts. If the assembly fails, it must be replaced.
BOARD SHOWN
WITHOUT COVER
4-5
GENERATOR SERVICE 4. Install the new brushes and springs in the hold-
er and keep them in place during assembly by
Always disconnect the battery cables (negative [-] inserting a piece of wire through the holder, as
first) from the battery to prevent accidental starting shown in Figure 4-7.
of the set while servicing the generator.
5. Install the brush holder. After tightening the
WARNING Accidental starting of the set while mounting screws, pull out the brush retaining
working on it can cause severe injury. To pre- wire.
vent accidental starting, disconnect the battery 6. Connect the F1 lead to the inner brush terminal
cables (negative [-] first) from the battery. (nearest the rotor windings). Connect the F2
The negative (-) cable is always disconnected lead to the outer brush terminal (nearest the
first, and connected last, to prevent arcing if a end bell).
tool accidentally touches the frame or other Slip Ring Inspection/Replacement
grounded metal parts of the set while discon-
necting or connecting the positive (+) cable. Inspect the slip rings for grooves, pits or other dam-
Arcing can ignite the explosive hydrogen gas age. If dust has accumulated on any generator
given off by the battery, and cause severe inju- components, they can be cleaned with filtered low-
ry. pressure air.
Brush Inspection/Replacement 1. Examine the slip rings while servicing the
brushes.
The generator should be inspected for brush wear 2. If the rings need cleaning or service, remove
and cleaning every six months. the rotor from the generator and dress the rings
WARNING Accidental starting of the generator
on a lathe.
set can cause severe personal injury or death. CAUTION Dressing the slip rings on a lathe
Stop the generator set and disable by discon- improperly may damage the generator rotor.
necting the starting battery cables (negative [-] Make certain that only an experienced techni-
cable first) before inspecting the generator. cian performs this job.
1. Remove the access cover for the brush assem-
bly. Generator Bearing
2. Check the brushes for wear with a piece of wire Inspect the bearing for evidence of outer case rota-
marked off 1 inch (25 mm) from one end (Fig- tion every 1000 hours of use. The bearing should
ure 4-6). Replace the brush and the spring if be replaced every five years, because the bearing
the wire goes into the brush holder 1 inch or grease gradually deteriorates due to oxidation.
more.
3. To replace brushes, remove the brush holder Replace the O-ring if it shows evidence of wear or
by disconnecting the two leads to the holder deterioration. Renew grease if necessary (moly
and removing the two mounting screws. only).
4-6
SPRING BRUSH
GENERATOR
BEARING
1 INCH
ES1676 WIRE
4-7
GENERATOR DISASSEMBLY/ASSEMBLY 5. Lift the rear of the set and place a wooden block
under the generator adapter to hold the stator
The following sections describe the disassembly and housing in place. Make certain that the en-
and reassembly procedures for the generator. Fig- gine-to-generator adapter (bolted to the en-
ure 4-8 illustrates generator disassembly. gine) is propped up high enough for the gener-
ator adapter assembly (bolted to the genera-
WARNING Generator components are heavy tor) to clear the rear genset mounts when it is
and can cause severe personal injury if dropped pulled off the set. A block approximately 3.5
during service. Be careful, use appropriate lift- inches wide (standard 2 x 4 lumber width) will
ing techniques, keep hands and feet clear dur- hold the adapter high enough. Remove the two
ing service, and use the recommended service rubber vibration isolators whose bolts were re-
procedures. moved in the last step.
6. Remove the end bell cover and disconnect F1
Note that the control box and air cleaner assembly
need not be removed from the set to disassemble the (outer) and F2 (inner) lead wires from the brush
generator. These components may remain attached holder terminals.
to the stator housing, and will be removed with it.
7. Pull each brush away from the commutator
Disassembly rings and insert a piece of stiff wire into the
small hole in the brush holder. See Figure 4-7.
1. Remove the generator set from the vehicle and
Note that the brushes may be secured (as de-
place it on a sturdy work bench. Refer to Sec- scribed in the last two steps) at any convenient
tion 1 of this manual for removal guidelines. point during this procedure.
WARNING Accidental starting of the set 8. Remove four nuts and lock washers from the
can cause severe personal injury or death. generator stud bolts. Remove the end bell cov-
Disconnect the battery cables, negative (-) er and pry the end bell free of the rotor bearing.
lead first, when repairs are made to the en- Be careful not to damage the brush holder.
gine, controls or generator. 9. Pull the stator/wrapper assembly with the con-
trol boxes off the rotor and away from the en-
2. Remove the cover from the AC control box and gine. Set it aside.
disconnect all stator leads (Q1-Q50/60,
T1-T2-T3-T4, F1-F2, S1-S2). Disconnect 10. Remove the four bolts that hold the generator
leads at the load circuit breaker(s). If the lead adapter and fan guard to the engine-to-genera-
markings do not clearly identify reconnection, tor adapter. Pull the adapter/guard assembly
mark the leads with tape. off the adapter and set it aside.
11. Loosen the six bolts that hold the rotor drive
3. Remove the bonding strap between the stator disk to the engine flywheel. Loosen these bolts
assembly and the drip pan. in an alternating pattern, so that the drive disk
4. Loosen and remove the two bolts that extend does not bend from the weight of the rotor.
through the rear genset mounts (under the sta- 12. Pull the rotor, fan and drive disk assembly off
tor housing). the flywheel and set them aside.
4-8
END BELL BRUSH
ASSEMBLY BLOCK
O-RING FAN
STUD BOLT
(1 OF 4) SPRING
BRUSH END
BEARING
ENGINE-GENERATOR
ADAPTER
MOUNTING
FOOT
STATOR
ASSEMBLY xES2095s
4-9
Rotor Disassembly 2. Apply Loctite #680 adhesive to the shaft mating
surface.
1. Place the rotor assembly on a wood block in the 3. Apply Loctite #747 activator to the bearing mat-
horizontal position. The drive disc and fan ing surface.
should not be resting on anything, or dis-
tortion may occur. 4. Install the bearing and allow ten minutes curing
time before handling the assembly.
2. Remove the six bolts that hold the drive disk
and fan to the rotor hub. Remove the drive disk
and fan. Rotor Reassembly
3. Use a gear puller to remove the end bearing After necessary service checks and repairs are
from the rotor shaft. made, the rotor and generator are reassembled us-
ing the reverse procedure of disassembly except for
CAUTION The end bearing will be dam- the rotor as noted below. Regrease the O-ring us-
aged if pulled on the outer race. If the bear- ing moly grease only. Apply required torque value
ing must be removed, replace it; this bear- shown in Figure 4-9.
ing should not be reused. CAUTION The drive disk will be damaged if the
bolts are tightened and it is not properly cen-
Rotor Bearing Replacement
tered. Center the disk accurately before begin-
1. Clean the bearing and shaft mating surfaces. ning to tighten the drive disk.
4-10
COLLECTOR ROTOR
RINGS WINDINGS
GENERATOR
DRIVE DISK
GENERATOR
DRIVE HUB
END
BEARING
ROTOR
ASSEMBLY
GENERATOR
FAN
4-11
Blank Page
4-12
GENERAL A. NO AC OUTPUT VOLTAGE AT RATED EN-
GINE RPM
This section contains troubleshooting information
for the HDKAG generator and voltage regulator.
Make the following visual checks before starting: B. UNSTABLE OUTPUT VOLTAGE, ENGINE
SPEED STABLE
Check any modification or repair that was done
since the last satisfactory operation of the set.
C. OUTPUT VOLTAGE TOO HIGH OR TOO
Verify that it was done properly.
LOW
Check to see that generator leads are con-
nected correctly. Also check the voltage regu- D. UNBALANCED OUTPUT VOLTAGE
lator and control component connectors. A
loose, contaminated, or misplaced wire con-
nection can be detected by close inspection. To troubleshoot a problem, start at the upper left
corner of the chart that corresponds to the problem,
Check for an open circuit breaker. If the break- and answer all questions either YES or NO. Follow
er is open, check for an overloaded circuit and the chart until the problem is found. Perform the ref-
correct load problems before resetting the erenced test or adjustment procedures in the Gen-
breaker. erator/Regulator Tests section.
TROUBLESHOOTING PROCEDURES
Components referenced in the flow charts, tests
Determine the type of problem, then refer to the cor- and adjustment procedures are found in the sche-
responding flow chart (A, B, C, or D) for trouble- matics and wiring diagrams in Section 9 of this
shooting procedures. manual.
5-1
FLOW CHART A. NO AC OUTPUT VOLTAGE AT RATED ENGINE RPM
WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machin-
ery hazards should perform service procedures. Review Safety Precautions.
START
Are load circuit breakers closed? no Locate cause of overload and correct as re-
quired. Reset breaker, or replace if bad.
yes
no
no
Are brushes stuck in holder or not Release brushes if jammed in holder. Clean
making good contact with slip rings? yes slip rings if dirty.
no
Examine brush block connections. Are F1 no Connect brush leads to correct terminals.
and F2 leads installed on correct terminals?
yes
Test continuity of rotor, stator per Tests yes Replace component if defective.
[B], [C]. Are there opens or grounds?
5-2
FLOW CHART B. UNSTABLE VOLTAGE, ENGINE SPEED STABLE
WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review Safety Precautions.
START
Are there any broken wires or loose connec- yes Repair as required.
tions on voltage regulator assembly?
no
Check wiring harness from regulator assem- no Repair wiring or replace as required.
bly to end bell per TEST [F]. Check OK?
yes
5-3
FLOW CHART C. OUTPUT VOLTAGE TOO HIGH OR TOO LOW
WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machin-
ery hazards should perform service procedures. Review Safety Precautions.
START
Is engine running at correct RPM? no Set RPM per instructions in appropriate
engine manual.
yes
Is the set AC output overloaded? yes Remove part of the set load.
no
Are voltage regulator connections secure? yes Are generator output leads properly con-
nected? See TEST [H].
yes
CAUTION A new printed circuit board can be
damaged by malfunctioning components within Perform procedure [D]. If correctly func-
the control. Do not install a new PC board until all tioning rotor/stator indicates a bad volt-
other problems have been located and corrected. age regulator, replace it per procedure
[E].
5-4
FLOW CHART D. UNBALANCED GENERATOR OUTPUT VOLTAGE
WARNING Many troubleshooting procedures present hazards that can result in severe personal
injury or death. Only qualified service personnel with knowledge of fuels, electricity, and machinery
hazards should perform service procedures. Review Safety Precautions.
START
Remove load at generator terminals. Is no Check for correct grounding of generator
output still unbalanced? and load.
yes
yes
yes
5-5
Blank Page
5-6
Section 6. Generator/Regulator Tests
CONNECT LEADS
BETWEEN EACH RING
AND ROTOR SHAFT
ES2068s
LEAD (F2 LEAD (F1
TO VR1-2) TO VR1-1)
TEST POINTS FIGURE 6-2. TESTING ROTOR FOR GROUNDS
6-1
Testing for Open or Shorted Windings [C] TESTING GENERATOR STATOR
Perform this test with an accurate meter such as a Isolate the stator windings by disconnecting all six
digital ohmmeter. stator leads. Test for open circuits between T1-T2,
T3-T4 and Q1-Q2, and for grounded circuits be-
1. Isolate the rotor windings by disconnecting the tween T1, T3 and B1 and the stator laminations or
two leads to the brush holder. other unpainted grounding point.
2. Using ohmmeter, check resistance between
F1 and F2 by connecting leads between the F1 Using proper test equipment, check the stator for
and F2 slip rings, Figure 6-3. grounds, opens, and shorts in the windings.
ES2070s
CONNECT LEADS BETWEEN
CONNECT LEADS BETWEEN EACH WINDING AND GROUND
F1, F2 SLIP RINGS ES2069s
FIGURE 6-3. TESTING ROTOR FOR AN FIGURE 6-4. TESTING STATOR WINDING
OPEN CIRCUIT FOR GROUNDS
6-2
Testing for Open or Shorted Windings [D] DYNAMIC ROTOR/STATOR TEST
Test for continuity between coil leads as shown in The following procedure serves as a functional volt-
Figure 6-5; all pairs should have equal resistance. age regulator check, by determining if the problem
Use an accurate instrument for this test such as a is in the voltage regulator or in the generator. The
Wheatstone Bridge. voltage regulator is temporarily replaced with a
12-volt battery (the genset starting battery is usable
Stator resistances (measured at 25 C) are: here); 12 volts applied to the F1/F2 exciter stator
Standard single-phase: should produce approximately 125 volts generator
T1-T2, T3-T4: 0.221 ohms output voltage at L1 and L2, with no load.
Q1-Q60: 1.997 ohms
WARNING Electrical shock can cause severe
Q1-Q50: 2.405 ohms
personal injury or death. Do not touch electrical
Standard three-phase: wiring or components during testing. Discon-
T1-T4, T2-T5, T3-T6, nect electrical power by removing starting bat-
T7-T10, T8-T11, T9-T12: 0.505 ohms tery negative (-) cable before handling electrical
Q2-T11: 0.252 ohms wiring or components.
Extended-stack three-phase:
T1-T4, T2-T5, T3-T6, Use a sharp voltage probe and touch it carefully to
T7-T10, T8-T11, T9-T12: 0.153 ohms the connector pins or output terminals when making
Q2-T11: 0.305 ohms these tests.
Extended-stack three-phase heavy-duty: 1. Stop the generator set.
T1-T4, T2-T5, T3-T6,
2. Unplug the voltage regulator from the wiring
T7-T10, T8-T11, T9-T12: 0.107 ohms
harness.
Q2-T11: 0.214 ohms
CAUTION Failure to unplug the voltage
If a winding is shorted, open or grounded, replace
the stator assembly. Before replacing the assem- regulator at this point in the procedure
bly, check the leads for broken wires or insulation. could lead to equipment damage.
3. Using jumpers and a spare plug or other con-
nector, connect a 12-volt battery to the F1/F2
terminals as illustrated in Figure 6-6.
4. Start the generator set. Use a voltmeter to
measure the outputs at J4-4 - J4-6, L1 - L2, L1 -
L0, L2 - L0, Q60 - Q1 (50 Hz sets: Q50 - Q1),
and S1 - S2. The output voltages should read
as follows (all voltages apply to both 50 Hz and
60 Hz sets):
J4-4 - J4-6: 62 VAC 20 VAC
L1 - L2: 125 VAC 20 VAC
CONNECT LEADS L1 - L0: 62 VAC 20 VAC
BETWEEN PAIRS L2 - L0: 62 VAC 20 VAC
OF STATOR
WINDING LEADS Q60 - Q1: 75 VAC 20 VAC
(50 Hz sets) Q50 - Q1: 75 VAC 20 VAC
S1 - S2: 62 VAC 20 VAC
ES2071s
If these voltages are measured, then the gen-
FIGURE 6-5. TESTING STATOR WINDING erator is operating correctly and the problem is
RESISTANCE elsewhere.
6-3
MEASURE MEASURE
125 VAC 62 VAC
MEASURE
62 VAC
MEASURE
62 VAC
-
+ MEASURE
75 VAC
APPLY
12 VDC MEASURE
62 VAC
MEASURE
75 VAC
6-4
[E] VOLTAGE REGULATOR sure the generator set has stabilized and is running
REPLACEMENT at the correct speed (frequency). The regulator is
adjusted with the set running.
Use the following procedure for replacing the AC
voltage regulator assembly.
WARNING Accidental starting of the set can
1. Stop the generator set and disconnect the cause severe personal injury or death. Discon-
starting battery leads, negative (-) lead first. nect both battery cables, negative (-) cable first,
when repairs are made to the engine, controls,
2. Unscrew the voltage regulator from the control or generator.
box.
WARNING Contact with high voltage can cause
3. Disconnect the regulator from the wiring har- severe personal injury or death. Do not touch
ness. any exposed wiring or components with any
part of the body, clothing, tool or jewelry. Do not
4. Remove the mounting screws from the old volt- use non-insulated tools inside the control.
age regulator, then install the new regulator. Stand on an insulating mat or dry wood platform
when the control doors are open.
5. Reconnect the plug connection to the wiring
harness.
Output voltage adjustments are found on the volt-
6. Set voltage as outlined in [G] Voltage Adjust- age regulator board under the DC control box. A re-
ment. movable cover protects the board. See Figure 6-7.
6-5
VOLTAGE ADJUST: Trim pot adjusts
output voltage level. Turn pot
clockwise to increase voltage. Turn pot
counterclockwise to decrease voltage.
BOARD SHOWN
WITHOUT COVER
6-6
Section 7. Routine Maintenance
SERVICE TIME
Daily Weekly Monthly 6 Months Yearly
or or or or or
after after after after after
SERVICE THESE ITEMS 8 hours 50 hours 100 hours 250 hours 500 hours
Inspect set x1
Check oil level x
Check coolant level x
Check fuel level x
Check air cleaner dust cap (clean if required) x3 x
Check battery charging system x
Check drive belt tension x4
Clean out spark arrester x
Check battery specific gravity x
Change crankcase oil and filter x2
Drain water/sediment from fuel filter x
Check antifreeze x
Clean generator assembly x
Drain sediment from fuel tank x5
Clean crankcase breather x3
Check fuel shut-off linkage x
Change fuel filter element x
Check genset brushes x
Change air cleaner element x3
Clean cooling system x
1 - Check for oil, fuel, cooling and exhaust system leaks. Check exhaust system audibly and visually
with genset running and repair any leaks immediately.
2 - Perform after first 35 hours of operation on new genset.
3 - Perform more often in extremely dusty conditions.
4 - Visually check belts for evidence of slippage.
5 - Drain one cup of fuel to remove water and sediment.
7-1
GENERATOR SET INSPECTION WARNING Fuel leakage will create a fire hazard
which can result in severe personal injury or
Inspect the generator set daily or after every eight death if ignited. While checking for leaks, do
hours of operation, whichever comes first. Check not smoke or allow any spark, flame, pilot light
the exhaust, fuel, and DC electrical systems as de- or other ignition source in the area. If any leaks
scribed below. Also check the mechanical condi-
are detected, have them corrected immediately.
tion of the set.
Check these gauges while the set is running. With the genset off, check the battery terminals for
clean and tight connections. Loose or corroded
Oil Pressure Gauge: Oil pressure should be 40 to connections create resistance which can impede
60 psi (276 to 414 kPa) when the engine is at oper- starting. Clean and reconnect loose battery cables.
ating temperature. Always disconnect the negative battery cable first
and connect it last, to reduce the possibility of arc-
Coolant Temperature Gauge: Coolant tempera- ing.
ture should be 165 to 195 F (74 to 91 C), de-
pending on load and ambient temperature. WARNING Ignition of explosive battery gases
can cause severe personal injury. Do not
DC Voltmeter: Battery voltage during operation smoke. Wear goggles, protective rubber gloves
should be 14 to 15 volts. and apron when servicing batteries.
Exhaust System
Mechanical
With the set running, inspect the entire exhaust sys-
Check for any signs of mechanical damage. Start
tem including the exhaust manifold, exhaust elbow,
the set and listen for any unusual noises that may
muffler and exhaust pipe. Visually and audibly
indicate mechanical problems.
check for leaks at all connections, welds, gaskets,
and joints. If any leaks are detected, shut down Check the mounting fasteners to make sure the set
the genset and do not operate until corrected. is secure in its compartment. If an under-floor hous-
Replace corroded exhaust components before ing is used, make sure that the set is secured to the
leaks occur. housing. Check the condition of the housing com-
ponents and make sure they are secure to the ve-
WARNING Inhalation of exhaust gases can re- hicle.
sult in severe personal injury or death. Inspect
exhaust system audibly and visually for leaks Make sure that the generator set air inlet and outlet
daily. Repair all leaks immediately. areas are not blocked with debris.
Fuel System Clean the generator set whenever dust and dirt be-
gin to accumulate. Dust and dirt can usually be re-
With the set running, inspect the fuel supply lines, moved with a damp cloth. Steam cleaning may be
return lines, filters, and fittings for leaks. Check flex- needed to remove road contaminants. Do not clean
ible sections for cuts, cracks and abrasions. See the genset while the engine is running. Protect the
that the fuel lines do not rub against anything that generator, air cleaner, control panel, and electrical
could break them. Replace worn fuel line compo- connections from cleaning solvents. Cleaning sol-
nents before leaks occur. vents can damage electrical connectors.
7-2
OIL AND FILTER CHANGE gine oil can cause cancer or reproductive toxic-
ity. When adding, changing or working with
Change the oil and filter at the intervals listed in used oil, take care not to breathe, ingest or
Table 7-2. Use oil that meets the API classification come into excessive contact with these sub-
and SAE viscosity grade indicated in the previous stances. Wash hands after use. Wear protec-
section. tive clothing and equipment. Provide adequate
ventilation.
Engine Oil Change
Run the engine until thoroughly warm. Stop the en- Oil Filter Change
gine, open the drain valve (Figure 7-1) and drain the
oil into a container. When completely drained, close Spin off the oil filter and discard it. Thoroughly clean
the valve and refill the crankcase with new oil. the filter mounting surface. Apply a thin film of oil to
the filter gasket, and spin the filter on until the gasket
WARNING Hot crankcase oil can cause burns if
just touches the mounting pad. Then turn an addi-
it is spilled or splashed on skin. Keep fingers tional 3/4 turn. Do not over-tighten the filter.
and hands clear when removing the oil drain
plug and wear protective clothing.
With oil in the crankcase, start the set and check for
WARNING State or federal agencies have de- leakage around the filter gasket. Tighten the filter
termined that prolonged contact with used en- only enough to eliminate leaks.
OIL
DIPSTICK DRAIN OIL FILTER
VALVE
7-3
COOLING SYSTEM Add coolant to the recovery tank (or separate ex-
pansion tank if equipped) to the full-cold level.
The cooling system must be filled with coolant
before the genset can be operated. Cooling sys-
tem capacity is listed in the Specifications section. Start the engine, then remove the pressure cap and
monitor the coolant level. As trapped air is expelled
Coolant Requirements from the system, the coolant level will drop. Add
Engine coolant must inhibit corrosion and protect coolant to replace it. Replace the pressure cap
against freezing. A 50/50 mixture of ethylene glycol when the coolant level is stable.
anti-freeze and water is recommended for normal
operation and storage. Use only a reliable brand of
Coolant Level
antifreeze that contains a rust and corrosion inhibi-
tor. The antifreeze must not contain a stop-leak
additive. Check the coolant level at the intervals specified in
the Periodic Maintenance Schedule. Check by ob-
Do not exceed a 50/50 mixture of ethylene glycol serving the coolant level in the recovery tank (or
and water. A higher proportion of ethylene glycol separate expansion tank if equipped) when the sys-
will alter the heat transfer properties of the coolant. tem is cold. See Figure 7-2 for a typical cooling sys-
A 50/50 mixture will provide freeze protection to tem. Engine coolant is at the proper level when the
-34 F (-37 C). recovery tank level is between FULL and LOW
marks.
Water used for engine coolant should be clean, low
in minerals, and free of corrosive chemicals. Use WARNING Coolant in a warm engine is under
distilled or soft water if available. Avoid the use of pressure and can flash to steam causing severe
well water, which may contain minerals that can burns if the radiator cap or drain cock are
clog the heat exchanger core and reduce cooling ef- opened. Let the engine cool down before open-
ficiency. ing the radiator cap or drain cock.
Filling the Cooling System
CAUTION The high engine temperature cutoff
Verify that all drain cocks are closed and all hose will shut down the engine in an overheat condi-
clamps are secure. Remove the cooling system tion only if the coolant level is sufficiently high
pressure cap and slowly fill the cooling system with to physically contact the shutdown switch.
the coolant mixture. Loss of coolant will allow engine to overheat
without protection of shutdown device, thereby
CAUTION Exceeding the recommended fill causing severe damage to the engine. It is
rate can cause incomplete filling of the engine therefore imperative that adequate engine cool-
block, leading to engine damage during warm- ant levels be maintained for operational integri-
up. Always follow the recommended fill proce- ty of the cooling system and engine coolant
dure. overheat shutdown protection.
7-4
HOSE IS CONNECTED AT
RADIATOR CAP
BRACKET
RECOVERY
TANK
OVERFLOW
HOSE
7-5
Flushing and Cleaning FAN BELT
A loose fan belt can cause the engine to overheat.
Once a year, drain, flush and refill the cooling sys- The belt tension must be correct for the set to run
tem with new coolant. To drain the system, open the well.
radiator coolant drain and the cylinder block drain
on the the rear (non-service access) side of engine. First, remove the generator set’s starting battery
See Figure 7-2. cables (negative [-] cable first).
WARNING Accidental starting of the set can
WARNING Contact with hot coolant can cause cause severe personal injury or death. Stop the
severe burns. Do not bleed hot, pressurized generator set and disable it by disconnecting
coolant from a closed cooling system. the starting battery cables (negative [-] cable
first) when maintaining or repairing the engine,
Chemical Cleaning: Rust and scale slow heat ab- controls, or generator.
sorption and can block coolant flow. Clean the cool- To reach the fan belt, remove the belt guard from the
ing system if rust and scale have collected on the front of the set. Do not operate the genset with-
engine water jacket or in the heat exchanger. Use a out the belt guard in place.
good cleaning compound and follow its instructions.
To adjust the belt, loosen the bolt that passes
through the long slot in the alternator mounting
Flushing: After cleaning, or before filling the sys-
bracket and slide the alternator until the tension is
tem with new coolant, drain the system and fill with
right. See Figure 7-3.
clean water. Run the genset for 10 minutes, then
drain the system completely. Refill with the coolant Belt tension is correct when a finger pressure of 22
mixture. pounds (10 kg) at the middle of the belt deflects it
about 0.4 inch (10 mm).
CAUTION Never pour hot water into a cold en-
gine or cold water into a hot engine. Doing so
can crack the head or the cylinder block. Do not PUMP/
operate the unit without water for even a few FAN ADJUST
PULLEY
minutes. TENSION
HERE
Thermostat
Pressure Cap
7-6
FUEL SYSTEM Low fuel in the tank promotes condensation. In
warm weather, the fuel tank cools at night quicker
Use the best fuel available. Fuel quality is important
than the fuel. If the fuel level is low, the upper por-
for dependable performance and satisfactory en-
tion of the tank will cool more rapidly, forming con-
gine life.
densation. In cold weather, the warm fuel returning
WARNING Ignition of fuel can cause serious from the injectors heats the fuel in the supply tank. If
personal injury or death by fire or explosion. Do the fuel is low, condensation may form on the upper
not permit any flame, cigarette, pilot light, spark part of the tank. To avoid condensation, fill the
or other igniter near the fuel system. fuel tank every time the genset is used.
Use ASTM 2-D (no. 2 Diesel) or ASTM 1-D (No. 1 The wrong fuel or dirty fuel will shorten the life of the
Diesel) fuel with a minimum Cetane number of 45. fuel filter. See the Periodic Maintenance Schedule
Number 2 diesel fuel gives the best economy and for the filter change interval.
performance under most conditions. Use number 1
CAUTION Dirt or water in the system will cause
diesel fuel when ambient temperatures are below
32 F (0 C), and during long periods of light engine severe damage to both the injection pump and
load. the injection nozzles. It is extremely important
that the fuel be kept clean and free of water.
Use low sulfur content fuel which has a cloud point
at least 10 degrees below the lowest expected fuel Refer to the Periodic Maintenance Schedule for the
temperature. (Cloud point is the temperature at recommended filter change interval. However, if
which wax crystals begin to form in diesel fuel.) the engine shows signs of fuel starvation (reduced
power or surging), the fuel filter must be changed.
Fuel Handling Precautions This involves purging the fuel system of trapped air.
See Priming the Fuel System later in this section.
Prevent dirt, water or other contaminants from en-
tering the fuel system. Filter or strain the fuel as the High Pressure Fuel System: The injection pump,
tank is filled. fuel injection lines and fuel injectors are the high
pressure fuel system. See Figure 7-4. The high-
CAUTION Due to the precise tolerances of die- pressure system is self-priming; trapped air is
sel injection systems, dirt or water in the system forced out through the injection nozzles.
will cause severe damage to both the injection
pump and the injection nozzles. It is extremely Low Pressure Fuel System
important that the fuel be kept clean and water
free. The electric fuel pump, fuel filter and injection pump
inlet comprise the low pressure fuel system. See
Condensation (water) can cause clogging of fuel fil- Figure 7-4. These components are normally
ters as well as freezing problems. Water mixing primed (purged of trapped air) at set installation. Be
with the sulfur in the fuel forms acid which can cor- sure to check the fuel level in the tank and that the
rode and damage engine parts. shutoff valve is open.
7-7
FUEL RETURN
INJECTION PUMP LINE FITTING
FUEL INLET
INJECTION LINE
CONNECTING NUT
7-8
BIO−DIESEL FUELS B5 − B20 The effectiveness of all commercially available
conventional anti−microbial additives, when
B5 bio−diesel fuel that meets industry specifica-
used in bio−diesel, is not known. Consult your
tions and quality is suitable for use with this genera-
fuel and additive supplier for assistance.
tor set.
Bio−Diesel Above B5 and up to B20 WARNING It is highly recommended that specific
Bio−Diesel Blends market applications are avoided or excercised with
extra care due to some of the properties of bio−die-
The following must be verified before using bio−die- sel fuel blends such as cold weather operation, long
sel blends up to B20:
term storage, material incompatibilities and other
The generator set is at Spec H or higher. effects on engine operating characteristics. Such
The vehicle propulsion engine is capable of us- applications that should use standard fuels include
ing B20 when sharing the same fuel tank. applications that will experience seasonal usage,
The OEM has installed B20 compatible fuel line storage for periods exceeding 90 days, and ex-
from fuel tank to generator set. treme temperatures or humidity.
The OEM has installed a water separator in the
Storage Requirements:
fuel line just before the generator set.
If using bio−diesel for seasonal applications
Approved Bio−Diesel Fuel:
(stored more than 90 days), the generator must
For biodiesel blends above B5 and up to B20, be purged before storage by running the en-
Cummins Onan requires that the fuel meet the gine on pure diesel fuel meeting ASTM D975
specifications outlined in ASTM D7467. for a mininmum of 30 minutes.
The biodiesel component of this fuel blend
must meet ASTM D6751 or EN14214 and the Warranty Coverage:
petroleum diesel component must meet ASTM
D975. Cummins Onan Warranty covers failures that are a
direct result of defects in material or factory work-
Blended bio−diesels fuels should be bought
manship. Generator damage, service issues and/or
pre−blended and not made by customers.
performance issues determined by Cummins Onan
to be caused by bio−diesel fuel blends not meeting
Bio−Diesel Properties: the specifications outlined in the applicable Installa-
Bio−diesel has poor oxidation stability which tion, Operator, and Service Manuals are not consid-
can accelerate fuel oxidation. Fuel oxidation ered to be defects in material or workmanship and
will reduce generator performance. This effect may affect your generator’s warranty.
is accelerated at increased ambient tempera-
tures.
Bio−diesel properties change at low ambient
temperatures (below 23F/−5C). Necessary
precautions must be taken when operating the
generator with bio−diesel blends in low ambi-
ent temperatures, such as a fuel heater, hose
insulation, or additional anti−gel fuel additives.
Bio−diesel fuel blends are an excellent medium
for microbial growth. Microbes cause fuel sys-
tem corrosion and premature filter plugging.
7-9
AIR CLEANER 1. Keep the battery case clean and dry.
The air cleaner element (Figure 7-5) is a dry type 2. Make certain that the battery cable connec-
and should never have oil applied to it. Avoid touch- tions are clean and tight. Use a terminal puller
ing the element except when cleaning it. Instruc- tool to remove the battery cables.
tions for cleaning the element are on a label at- Remove corrosion from the battery terminal
tached to the element. Change the element yearly, connections. Wash the terminals with an am-
or more often in extremely dusty conditions. monia solution or a solution consisting of 1/4
pound (about 100 grams) of baking soda in 1
OUTLET quart (about 1 liter) of water. Be sure the vent
INLET plugs are tight to prevent cleaning solution from
entering the cells. After cleaning, flush the out-
side of the battery and the surrounding areas
with clean water.
3. Identify the cable as positive (+) or negative (-)
AIR CLEANER before making the battery connections. Al-
ELEMENT ways connect the negative (-) cable last, to re-
duce the risk of arcing.
4. Maintain the electrolyte level by adding distilled
water. Fill each cell to the split-level marker in
the battery. The water component of the elec-
trolyte evaporates, but the sulfuric acid compo-
AIR CLEANER
nent remains. For this reason, add water, not
BAND W/CUSHION electrolyte to the battery.
5. Use a battery hydrometer to check the specific
VALVE WING gravity of the electrolyte in each battery cell
BOLT
(Figure 7-6). Charge the battery if the specific
FIGURE 7-5. AIR CLEANER ASSEMBLY gravity measures less than 1.215. Do not over-
charge the battery. Stop charging the battery
when the electrolyte specific gravity reaches
BATTERY CARE 1.260, at approximately 80 F (27 C).
7-10
AC GENERATOR CRANKCASE BREATHER
Generator Brushes Clean the crankcase breather element at the
scheduled intervals, using the following procedure
The generator should be inspected for brush wear (see Figure 7-7).
and cleaning as required per the Periodic Mainte- 1. Remove the cap nuts and gaskets from the top
nance Schedule. Perform this procedure according of the cylinder head cover. Carefully remove
to the steps in Section 4 of this manual. the cover. Avoid damaging the gasket.
WARNING Accidental starting of the generator 2. From inside the cover, remove two machine
set can cause severe personal injury or death. screws securing the breather element, plates
Stop the generator set and disable by discon- and shield.
necting the starting battery cables (negative [-]
cable first before inspecting the generator. 3. Clean the element in a suitable solvent. Dry the
element, then saturate with engine oil before re-
placing.
Generator Bearing
WARNING Many cleaning solvents present
Inspect the bearing for evidence of outer case rota- a hazard of severe personal injury or death.
tion every 1000 hours of use. The bearing should Follow the manufacturer’s instructions and
be replaced every five years, because the bearing proceed with care.
grease gradually deteriorates due to oxidation. See
Section 4 of this manual for information on the gen- 4. If necessary, clean other breather components
erator bearing. in solvent before reassembling.
CAP NUT AND CYLINDER
GASKET HEAD COVER
BREATHER
PIPE JOINT
BREATHER
ELEMENT PIPE
PLATE 2
BREATHER
ELEMENT
ELEMENT
PLATE 1
OIL
SHIELD
7-11
MUFFLER/SPARK ARRESTER CLEANING THE GENERATOR SET
Clean the generator set at least every six months.
The exhaust spark arrester mounted inside the muf-
Dust usually can be removed with a damp cloth.
fler is necessary for safe operation. It must be peri- Some road contaminants may require steam clean-
odically cleaned out for maximum efficiency, and to ing. Do not steam clean the generator set while the
meet Forest Service requirements (RV use). See engine is running. When cleaning, protect the area
the maintenance schedule for cleaning intervals. so spray is not directed into the generator, air clean-
er, control box, fuel solenoid, or electrical connec-
tions. Do not clean with solvents; they can damage
To clean the spark arrester, park the vehicle on a electrical connectors.
non-flammable, washable surface, and remove the
1/8 inch pipe plug from the bottom of the muffler. INITIAL STARTING AND CHECKS
Run the generator set with a full load for five min-
WARNING Exhaust gas presents the hazard of
utes. Stop the generator set and allow the muffler to severe personal injury or death. Do not operate
cool. Replace the pipe plug in the muffler. See Fig- the generator set inside any room or building.
ure 7-8.
If none of the fuel line junctions have been loosened
between the electric fuel pump and the injection
pump, the fuel system should not need priming.
However, if priming is necessary, it should be done
according to the following procedure.
7-12
8. Wiring Diagrams
The electrical schematics and wiring diagrams that apply to the generator set covered in this manual are listed
below.
8-1
612−6635
8-2
P4 J4
12 12
11 11
L1
10 10
9 9 L2
2 2
1 1
AC
T1 S1
VR1
F1 2 A1 1
Q6 0 Q1
A1 T2
AC
F2 S2
NOTE:
Q5 0 T3
1. FROM J2−15 FOR FIELD FLASHING.
SEE NOTE 2
T4
2. QUADRATURE POWER CONNECTION Q60−60 HZ,
MAIN
Q50−50 HZ UNITS.
FIELD ARMATURE
STATOR 3. AVR REFERENCE VOLTAGE.
G1
SCHEMATIC
1 1 0 / 2 2 0 V, 1 1 5 / 2 3 0 V & 1 2 0 / 2 4 0 V AS SHOWN
SEE RECONNECTI ON CHART FOR OTHER VOL TAGES
7 6
A B C HZ CODE
VOL TAGE
120 240 120/ 240
10 3
L1 L1 L1
11 2 S1 S1 S1
Q1 Q1
12 1 T3 T1 Q1 T1 T1
SCHEMATI C
S2 S2
SEE NOTE 3
T3 T3
L1 L0 S2 L0(N)
T1 S1
2
T4 T4
L2 T4 S2
L0 L2
G1 F1
T2 F2
Q6
0
L0 T3
Q
Q5
1
L1 L0 L1 L2 L0 L 1 L 0 ( N) L 2
0
DI AGRAM
GND
SEE NOTE 2
A1
T1 T3 T2 T4 T1 T2 T3 T4 T1 T2 T3 T4
WIRING DIAGRAM GND
GENERATOR
1 1 0 / 2 2 0 V, 1 1 5 / 23 0 V & 1 2 0 / 2 4 0V AS SHOWN RECONNECTION CHART
SEE RECONNECTI ON CHART FOR OTHER VOL TAGES
612−6637
8-3
612-6732
8-4
Cummins Power Generation
1400 73rd Ave. NE
Minneapolis, MN 55432 USA
Phone 1 763 574 5000
Toll-free 1 800 888 6626
Fax 1 763 574 5298
Email www.cumminsonan.com/contact
www.cumminsonan.com
CumminsR, OnanR, the “C” logo, and “Performance you rely on.”
are trademarks of Cummins Inc.
E2012 Cummins Power Generation, Inc. All rights reserved.