You are on page 1of 8

Balluff Network Interface / IO-Link BNI IOL IP20 Device

BNI IOL-309-000-K024
BNI IOL-310-000-K025

Nr. 881678 E • Issue 1012 • Subject to modiÞcation

Balluff GmbH
Schurwaldstrasse 9
73765 Neuhausen a.d.F.
Germany
Tel. +49 7158 173-0
Fax +49 7158 5010
balluff@balluff.de

16 www.balluff.com
User‘s Guide
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

1 Notes to the user Appendix


1.1 About this guide 3
1.2 Structure of the guide 3 BNI IOL-3xx-000-xxxx
1.3 Typographical conventions 3
1.3.1 Enumerations 3 Product ordering Balluff Network Interface
1.3.2 Actions 3 code
1.3.3 Syntax 3 IO-Link Interface
1.3.4 Cross references 3
Functions
1.4 Symbol 3
309 = 8 Inputs/ Outputs can be parameterized
1.5 Abbreviations 3 310 = 16 Inputs/ Outputs can be parameterized
2 Safety
2.1 Intended use 4 Versions
2.2 General safety notes 4 000 = Standard version
2.3 Meaning of the warnings 4

3 Getting Started Mechanical design


K024 = plastic housing, rail mounting over plastics shell
3.1 Connection overview 5
K025 = plastic housing, rail mounting over plastics shell
3.2 Mechanical connection 6
3.3 Electrical connection 6
3.4 IO-Link Interface 6
3.5 Sensor-Hub Interface 6
3.6 Connection 6 Order information Product ordering code Order code
4 IO-Link Interface BNI IOL-309-000-K024 BNI004K
4.1 IO-Link data 7
BNI IOL-310-000-K025 BNI004L
4.2 Process data / Input Data 7
4.3 Parameter data / Request data 8
4.4 Errors 10
4.5 Events 10

5 Technical Data
5.1 Dimensions 11
5.2 Mechanical data 12
5.3 Electrical data 12
5.4 Operating conditions 12
5.5 Function indicators 13

Apendix
Product ordering code 15
Order information 15

2 www.balluff.com www.balluff.com 15
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

5 Technical Data 1 Notes to the user

1.1 About this guide This guide describes the Balluff IO-Link Sensor-Hub. Connection to the superordinate
IO-Link master assembly is established by means of IO-Link protocol. From functional
perspective this compact and inexpensive module is comparable to a passive junction
box: accepting digital and analogue sensor signals and conveying them through the
IO-Link-Interface.
Status I/O LED 1...8/16
1.2 Structure of the The guide is organized so that the sections build on one another.
Indicator Function guide Section 2: Basic safety information.
Section 3: The main steps for installing the device.
Yellow Input/-Output signal = 1 Section 4: IO-Link, parameter and process data for the device.
Section 5: Technical data for the device.
Out Input/-Output signal = 0

1.3 Typographical The following typographical conventions are used in this guide.
conventions

1.3.1 Enumerations Enumerations are shown in list form with bullet points.
- Entry 1,
- Entry 2.

1.3.2 Actions Action instructions are indicated by a preceding triangle. The result of an action is
indicated by an arrow.
¾ Action instruction 1
Ö Action result.
¾ Action instruction 2.

1.3.3 Syntax Numbers:


Ŧ Decimal numbers are shown without additional indicators (e.g. 123),
Ŧ Hexadecimal numbers are shown with the additional indicator hex (e.g. 00 hex).

1.3.4 Cross references Cross references indicate where additional information on the topic can be found (see
section 5 „Technical Data”)

1.4 Symbols Note


This symbol indicates general notes.

Note!
This symbol indicates a security notice which must be observed.

1.5 Abbrevations BCD Binary coded switch


BNI Balluff Network Interface
DPP Direct Parameter Page
EMV Electromagnetic Compatibility
E-Port Digital Input-Port
FE Function earth
IOL IO-Link
LSB Least SigniÞcant Bit
MSB Most SigniÞcant Bit
Sensor-Hub Sensor-Hub
SP Switching point
SPDU Service Protocol Data Unit

14 www.balluff.com www.balluff.com 3
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

2 Safety 5 Technical Data

2.1 Intended use This guide describes the Balluff Network Interface BNI IOL-… for the application as 5.5 LED Indicators
peripheral in-/ output module to establish connection of binary standard sensors or
actuators. Hereby it is about an IO-Link device which communicates by means of IO-Link
protocol with the superordinate IO-Link master assembly.

2.2 General safety Installation and start up


notes Installation and start up are to be performed only by trained specialists. Any damage
resulting from unauthorized manipulation or improper use voids the manufacturer’s
guarantee and warranty.
The device complies with EMC Class A. Such equipment may generate RF noise. The
operator must take precautionary measures accordingly.
The device must be powered only using an approved power supply (see section 5
“Technical data”). Only approved cable may be used.
Overvoltage or reverse polarity of connectors may damage the device.

Operating and testing


The operator is responsible for observing local prevailing safety regulations.
When defects and non-clearable faults occur in the device, take it out of service and secure
against unauthorized use.
Approved use in ensured only when the housing is fully installed.

2.3 Meaning of the Note! LED Indicator Status LED 1


warnings The pictogram used with the word “Caution” warns against a possible
Indicator Function
hazardous situation affecting the health of persons or resulting in equipment
damage. Ignoring these warnings can result in injury or equipment damage. Green AUX supply voltage is OK
• Always observe the described measures for preventing this danger. Out AUX supply voltage < 18V

Status LED 2

Indicator Function
Green Module supply voltage is OK
Green ßasing Module supply voltage < 18V
Green, slowly ßashig Overload, total current > 1A
Out Module is without voltage

Status LED 3/4

Indicator Function
Green No communication
Green, negative pulsed Communication ok
Red ßashing Communication overload
Out Module is without voltage

4 www.balluff.com www.balluff.com 13
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

5 Technical Data 3 First Steps

5.2 Mechanical Data 3.1 Connection


Housing material PVC (UL94V-0) overview

IO-Link Port connector block 4 poles, 3.81mm

IO-Ports connector block 8 poles, 3.81mm

Enclosure rating IP20


BNI IOL-309-000-K024: 60 g
Weight
BNI IOL-310-000-K025: 90 g
Dimensions see images

5.3 Electical Data Operating voltage 18...30.2 V DC, per EN 61131-2

Ripple < 1%

Current draw without load < 80 mA

5.4 Operating- Operating temperature -5 0C ... 50 0C


conditions
Storage temperature -25 0C ... 70 0C

EMC EN 61000-4-2/3/4/5/6 - Severity level 4A/3A/4B/2A/3A


Figure 3-1: BNI IOL-309/310-000-K024/K025
EN 60068-2-6, EN 60068-2-27
Shock / vibration
EN 60068-2-29, EN 60068-2-64
1 IO-Link Interface
2 Port 1-8/16 Input/Output
3 Port 1-8/16 24V
4 Port 1-8/16 GND
5 Status LED: Port 1-8/16
6 Status LED: Communication
7 Status LED: Supply Module
8 Status LED: Supply Module AUX

12 www.balluff.com www.balluff.com 5
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

3 First Steps 5 Technische Data

3.2 Mechanical BNI IOL-309/310-000-K024/K025: Standard DIN rail mounting 5.1 Dimensions
connections

3.3 Electrical The Sensor-Hub Modules require no separate supply voltage connection.
connections Power is provided through the IO-Link interface by the host IO-Link Master.

3.4 IO-Link interface IO-Link is established by a 4 poles male.

Pin Requirement
24V Power supply controller, +24V, max. 1,0A
AUX
24V

IOL
0V

Power supply output,


AUX
+24V, max. 1,6A
0V GND, reference potential
IOL C/Q, IO-Link Data transmission channel

3.5 Connecting the ¾ Connection protection ground to FE terminal, if present.


 Sensor-Hub ¾ Connect the incoming IO-Link line to the Sensor Hub.

3.6 Connecting
Sensors/Actuators Figure 5-1: BNI IOL-310-000-K025
Pin Requirements
 1 2 3 4 5 6 7 8
Input / Output
Input: EN: 61131-2, Type: max 30V
I/O
I/O

Output: max: 350mA


Total current all output max. 1,6A.

24V +24V, Total current max. 1A


24V

GND GND Reference potential


GND

   Note:
For the digital sensor inputs follow the input guideline per EN 61131-2, type 2.
Outputs may be loaded by max. 350mA.

Figure 5-2: BNI IOL-309-000-K024

6 www.balluff.com www.balluff.com 11
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

4 IO-Link Interface 4 IO-Link Interface

4.4 Errors 4.1 IO-Link Data BNI IOL-309-000-K024


IO-Link Version 1.0
Error Code Additional Code
Data transmission rate COM2 (38,4 kBaud)
11hex Index not available
Frame type 2.5
Device application error: 80 hex 12 hex Subindex not available
Minimal cycle time 3 ms
30 hex Value out of range
Process data cycle time 3 ms, at minimal cycle time

Vendor ID 0x0378
4.5 Events Class / QualiÞer
Code ( high + low) Device ID 0x050901
Mode Type Instance

Appears Error AL Device Hardware Supply Supply low voltage U2 = Supply +24V BNI IOL-310-000-K025

C0 hex 30 hex 03 hex 5000 hex 0100 hex 0010 hex 0002 hex
IO-Link Version 1.0

F3 hex 5112 hex


Data transmission rate COM2 (38,4 kBaud)

Frame type 1
Parameter Data

Disappears Error AL Device Hardware Supply Supply low voltage U2 = Supply +24V

80 hex 30 hex 03 hex 5000 hex 0100 hex 0010 hex 0002 hex
Minimal cycle time 3 ms

B3 hex 5112 hex


Process data cycle time 12 ms, at minimal cycle time

Appears Error AL Device Hardware Supply Supply periphery Vendor ID 0x0378

C0 hex 30 hex 03 hex 5000 hex 0100 hex 0060 hex


Device ID 0x050902

F3 hex 5160 hex

Disappears Error AL Device Hardware Supply Supply periphery


4.2 Process Data The following process date are exchanged between IO-Link and slave:

80 hex 30 hex 03 hex 5000 hex 0100 hex 0060 hex Input Data: Data that are transmitted from the device to the master.
Output Data: Data that are transmitted from the Master to the device.
B3 hex 5160 hex

Output Data Byte 0 1 *1)


Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Pin 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

Input Data Byte 0 1 *1)


Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Pin 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

*1) only in case of BNI IOL-310-000-K025

10 www.balluff.com www.balluff.com 7
Balluff Network Interface / IO-Link BNI IOL IP20 Device Balluff Network Interface / IO-Link BNI IOL IP20 Device

4 IO-Link Interface 4 IO-Link Interface

4.3 Parameter Data /


SPDU Byte 2 *1) 3 *1)
Request Data
Object name Length Default value Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Sub
Index
Index Pin 16 15 14 13 12 11 10 9
0x10 0 Vendor name 8 Byte BALLUFF
Subindex 16 15 14 13 12 11 10 9
0x11 0 Vendor text 16 Byte www.balluff.com
BNI IOL-309-000-K024 00 = Output low
BNI IOL-309-000-0000 01 = Output high
0x12 0 Product name 21 Byte 10 = Output last state
Range BNI IOL-310-000-K025
BNI IOL-310-000-0000 11 = as 00
0x13 0 Product ID 7 Byte Ordering code
0x44 Under voltage (only reading)
BNI IOL-310-000-K025:
IO Sensor/Actor Hub IP20 16Bit Byte 0 1
0x14 0 Product text 23 Byte
BNI IOL-309-000-K024: Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
IO Sensor/Actor Hub IP20 8Bit
Description - - - - - - - - - - - - - UA - UB
0x16 0 Hardware Revision 3 Byte
0x17 0 Firmware Revision 3 Byte 0 = no under voltage
0x40 0 0x0000 - 1 = under voltage recognized
Inversion 2 Byte 0x0000
64 1-16 0-FFFF - = not used
0x41 0 ConÞguration 0x0000 -
2 Byte 0x0000 0x45 Monitoring Output „Actuator short circuit“ (only reading)
65 1-16 Input / Output 0-FFFF
Parameter Data

0x000000 Byte 0 1 *1)


0x42 0 In case of error 00 -
4 Byte 0x00000000 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
66 1-16 Pin 1 to Pin 16 0-FFFFF
FFF Pin 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9
0x44 0 0x0000 -
Under voltage 2 Byte 0x0000
68 1-16 0xFFFF 0 = high set and high recognized
0x45 0 Monitoring 0x0000 - 1 = high set but low recognized
2 Byte 0x0000
69 1-16 Outputs 0xFFFF
0x47 0 Monitoring 0x0000 -
2 Byte 0x0000 0x46 Monitoring output „Actuator Warning“ (only reading)
70 1-16 Outputs 0xFFFF
Byte 0 1 *1)
0x40 Inversion (reading/writing) Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Byte 0 1 *1) Pin 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Pin 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 0 = low set and low recognized
1 = low set but high recognized
0 = not inverted
1 = inverted
*1) only in case of BNI IOL-310-000-K025
0x41 ConÞguration Input/Output (reading /writing)
Byte 0 1 *1)
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Pin 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9

0 = Input
1 = Output
0x42 In case of error Pin 1 to Pin 16 (reading /writing)
Byte 0 1
Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
Pin 8 7 6 5 4 3 2 1
Subindex 8 7 6 5 4 3 2 1

8 www.balluff.com www.balluff.com 9