You are on page 1of 2

Data Sheet

s Fire Safety Products

Desigo® Fire Safety System


Remote Display Terminals (with RS─485 interface)
Models FT2014-U2 / R2 and FT2015-U2 / R2 (with Model FCA2016-U1)
ARCHITECT AND ENGINEER SPECIFICATIONS
Models FT2014-U2 / R2 and FT2015-U2 / R2: Model FCA2016-U1:
• 2” ─x─ 4-¾” backlit LCD screen • RS─485 module provides
• Event and audible status LEDs communication to Remote Display
Terminals (Models FT2014, FT2015)
• Supports Style 4 or Style 6 wiring
• Dual, standardized RS─485 interface
• Built-in transient protection • Supports ‘Class B’ (Style 4) and ‘Class A’
• Mounts in its own enclosure (Style 6) wiring configurations
Model
FT2015-U2 • Electrical isolation between the RS─485
• Optional system control
interface and Desigo panel
• Downloadable firmware • Ground-fault monitoring
 Built-in flash electrically erasable programmable
read-only memory (EEPROM) • up to eight (8) devices on the RS─485
• Scroll buttons to view additional events Style 6 loop Universal Fire Protocol
• Local sounder (UFP) limitation
• UL 864 9th Edition Listed, ULC Listed;
• UL 864 9th Edition Listed, ULC Listed; Model FM, CSFM & NYC Fire Dept. Approved
FM, CSFM & NYC Fire Dept. Approved FCA2016-U1

Product Overview
The Remote Display Terminals (Models FT2014-U2 / R2 Additionally, the remote display terminals have an LED
and FT2015-U2 / R2) are remote light-emitting diode to indicate system power; a separate ground-fault LED,
(LED) / liquid-crystal display (LCD) units that show the and four (4) additional user-programmable LEDs.
existing status of a Desigo 252 / 504-point system. There are also two (2) LEDs that indicate the
A LED will illuminate for any given Alarm, Gas Alarm, state of audible circuits on the system:
Supervisory and Trouble Desigo-system event.  One (1) LED to indicate that the circuits are ‘active’
A 2” ─x─ 4-3/4” LCD screen will give details of the  One (1) LED to indicate the circuits have been ‘silenced’
event in alphanumeric form. The display screen can When the Desigo FACP is in `normal’ state (with no
be scrolled to reveal additional events. Optional events present), the screen will annunciate the date
remote-system-control capabilities are also available. and time-of-day.
The Remote Display Terminals (as well as Model When an event has been triggered to the Desigo
FCA2016-U1) are FM (#3010); FDNY (#6104) and panel, the LCD display will show the following:
CSFM (#7165-0067:0259) Approved.  Event type and zone
 Custom message for that zone
 Usage of the zone
Specifications  ’Unacknowledged’ or ‘Acknowledged’ event
The remote display terminals have separate LEDs for In addition to the aforementioned features, the display
Alarm, Gas Alarm, Supervisory, and Trouble events on will show the total number of all types of events
a Desigo FACP. Each LED will flash when present on the system. The display has a backlight
‘unacknowledged’ events are present. The LED will feature that operates upon receiving any event status
change to ‘steady’, upon acknowledgment of the event. or when any operator buttons are pressed.

Desigo Remote Display Terminals (with RS─485 module) 6812


s Industry, Inc.
Building Technologies Division
Specifications ─ (continued) Temperature and Humidity Range
The Model FT2014-series display terminal has a local Products are UL 864 9th Edition Listed for indoor
sounder that operates when any new events are dry locations within a temperature range of
displayed on the system. Pressing the local sounder 120+/-3°F (49+/-2°C) to 32+/-3°F (0+/-2°C)
silence button or any operator buttons will silence the and a relative humidity of 93+/-2% at a
local sounder when an event is present. temperature of 90+/-3°F (32+/-2°C).
Each remote display terminal has a navigation button
that is used for displaying next-event or previous- Technical Data
event information in the sequence, and has a local
Voltage 3.3VDC
sounder silence button.
 Normal
Operating (Standby mode) Approx. 75 mA
Model FT2014-series has one (1) button used to Current:
RS─485  Alarm Approx. 136 mA
silence the local sounder. The Model FT2015-series
has three (3) control buttons for ‘acknowledging’ Interface Connection Bus structure
Communication mode Half-duplex
events, silencing audible circuits and resetting the
Number of participants 8, max.
system. Additionally, there are three (3) user- Maximum wire length 3,937 feet (1200 meters)
programmable buttons available. The Model FT2015- RS─485 Interface:
series has an integral key switch that enables the  Design 4-pole screw terminal
control buttons to operate. 12 to 22
Connections  Admissible Cross-
The remote display terminals are remotely connected American-Gauge Wires
section Cable
(AWG)
to the Desigo FACP, via the RS─485 interface. The
To the operating unit Plug-in-type connections
Model 252-point and 504-point Desigo panels require
Power FT2014-series 24VDC @ 55mA
the Model FCA2016-U1 RS─485 module to provide
Requirements FT2015-series 24VDC @ 55mA
communication to the remote display terminals.
Model FCA2016-U1 supports Style 4 or Style 6 wiring.
Up to eight (8) modules can be supported on a given Related Documentation
RS─485 communications bus.
Product Data Sheet Number
24-Volt power is required to run the remote display Remote Peripheral Module 6811
terminals, and can be provided from a Desigo FACP or 252-point Desigo System
other UL Listed 24VDC power source. 6815
504-point Desigo System
The remote display terminals have screw terminals Intelligent Voice
6821
capable of supporting 12 to 22 American Wire Gauge Communication system
(AWG).
The remote display terminals can be mounted to a (2)
two-gang electrical box or a (4) four-inch square
Details for Ordering
electrical box. No flush-trim kit is required. Each unit Part
Model Description
is approximately 12-1/4“(31.2cm.) wide; 9” (22.9cm.) Number
high; and 2-1/2” (6.4cm.) deep. FT2014-U2 S54400-F67-A1 Remote Display Terminal
Each RS─485 interface is approximately 1.97” (5cm.) FT2014-R2 S54400-B75-A1 Remote Display Terminal, Red
wide; 2.76” (7cm.) high; and 0.6” (1.5cm.) deep. The S54400-F68-A1 Remote Display Terminal
FT2015-U2
weight of Model FCA2016-U1 is 0.044 Lbs. (20g). [with control]
Remote Display Terminal
FT2015-R2 S54400-B15-A1
[with control], Red
FCA2016-U1 S54400-A39-A1 RS─485 Interface

Notice: This marketing data sheet is not intended to be used for system design or installation purposes.
For the most up-to-date information, refer to each product’s installation instructions.

Fire Safety Fire Safety


8 Fernwood Road 1577 North Service Road
s Industry, Inc. Florham Park, NJ 07932 East Oakville, Ontario May 2017
Supersedes sheet dated 8/2013
Building Technologies Division Tel: (973) 593-2600 (SII-FS) L6H 0H6 / Canada (Rev. 4)
FAX: (908) 547-6877 Printed in U.S.A. Tel: [905] 465-8000
URL: www.USA.Siemens.com/Desigo-Fire-Safety URL: www.Siemens.CA