You are on page 1of 5

Compare Products

LC1D95M7 LC1D65M7
TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 95 A - CONTACTOR 600VAC 65AMP IEC +OPTIONS
220 V AC 50/60 Hz coil
View Details
View Details

Price 3,100,900.00 IDR

TeSys D TeSys D
range of product

TeSys TeSys
range

TeSys D
product name

Contactor Contactor
product or component type

LC1D LC1D
device short name

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Motor control Motor control
contactor application Resistive load Resistive load

AC-1 AC-1
utilisation category AC-3 AC-2
AC-4 AC-3
AC-4

3P 3P
poles description

3 NO 3 NO
power pole contact composition

Power circuit: 1000 V AC 25...400 Hz Power circuit: <= 690 V AC 25...400 Hz


[Ue] rated operational voltage

125 A (at <60 °C) at <= 690 V AC-1 for power circuit 65 A (at <60 °C) at <= 440 V AC AC-3 for power
[Ie] rated operational current 95 A (at <60 °C) at <= 440 V AC-3 for power circuit circuit
80 A (at <60 °C) at <= 440 V AC AC-1 for power
circuit

25 kW at 220...230 V AC 50 Hz (AC-3) 18.5 kW at 220...230 V AC 50 Hz


motor power kW 45 kW at 1000 V AC 50 Hz (AC-3) 30 kW at 380...400 V AC 50 Hz
45 kW at 380...400 V AC 50 Hz (AC-3) 30 kW at 415 V AC 50 Hz
45 kW at 415...440 V AC 50 Hz (AC-3) 30 kW at 440 V AC 50 Hz
45 kW at 660...690 V AC 50 Hz (AC-3) 37 kW at 1000 V AC 50 Hz
55 kW at 500 V AC 50 Hz (AC-3) 37 kW at 500 V AC 50 Hz
37 kW at 660...690 V AC 50 Hz

15 hp at 230/240 V AC 60 Hz for 1 phase motors 10 hp at 230/240 V AC 60 Hz for 1 phase motors
motor power HP (UL / CSA) 25 hp at 200/208 V AC 60 Hz for 3 phases motors 20 hp at 200/208 V AC 60 Hz for 3 phases motors
30 hp at 230/240 V AC 60 Hz for 3 phases motors 20 hp at 230/240 V AC 60 Hz for 3 phases motors
60 hp at 460/480 V AC 60 Hz for 3 phases motors 40 hp at 460/480 V AC 60 Hz for 3 phases motors
60 hp at 575/600 V AC 60 Hz for 3 phases motors 50 hp at 575/600 V AC 60 Hz for 3 phases motors
7.5 hp at 115 V AC 60 Hz for 1 phase motors 5 hp at 115 V AC 60 Hz for 1 phase motors

AC at 50/60 Hz AC at 50/60 Hz
control circuit type

220 V AC 50/60 Hz 220 V AC 50/60 Hz


[Uc] control circuit voltage

1 NO + 1 NC 1 NO + 1 NC
auxiliary contact composition

8 kV conforming to IEC 60947 8 kV conforming to IEC 60947


[Uimp] rated impulse withstand voltage

III III
overvoltage category

10 A (at 60 °C) for signalling circuit 10 A (at 60 °C) for control circuit
[Ith] conventional free air thermal current 125 A (at 60 °C) for power circuit 80 A (at 60 °C) for power circuit
1100 A at 440 V AC for power circuit conforming to 1000 A at 440 V for power circuit conforming to IEC
Irms rated making capacity IEC 60947 60947
140 A AC for signalling circuit conforming to IEC 140 A AC for control circuit conforming to IEC 60947-
60947-5-1 5-1
250 A DC for signalling circuit conforming to IEC
60947-5-1

1100 A at 440 V for power circuit conforming to IEC 1000 A at 440 V for power circuit conforming to IEC
rated breaking capacity 60947 60947

100 A - 1 s for signalling circuit


[Icw] rated short-time withstand current 1100 A 40 °C - 1 s for power circuit
120 A - 500 ms for signalling circuit
135 A 40 °C - 10 min for power circuit
140 A - 100 ms for signalling circuit
400 A 40 °C - 1 min for power circuit
800 A 40 °C - 10 s for power circuit

10 A gG for signalling circuit conforming to IEC 10 A gG for control circuit conforming to IEC 60947-
associated fuse rating 60947-5-1 5-1
160 A gG at <= 690 V coordination type 2 for power 125 A gG at <= 690 V coordination type 1 for power
circuit circuit
200 A gG at <= 690 V coordination type 1 for power 125 A gG at <= 690 V coordination type 2 for power
circuit circuit

0.8 mOhm - Ith 125 A 50 Hz for power circuit


average impedance

Power circuit: 1000 V conforming to IEC 60947-4-1 Control circuit: 600 V CSA certified
[Ui] rated insulation voltage Power circuit: 600 V CSA certified Control circuit: 600 V UL certified
Power circuit: 600 V UL certified Control circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified Power circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified Power circuit: 600 V UL certified
Signalling circuit: 690 V conforming to IEC 60947-1 Power circuit: 690 V conforming to IEC 60947-1

1.2 Mcycles 95 A AC-3


electrical durability 1.3 Mcycles 125 A AC-1

12.5 W AC-1 4.2 W AC-3


power dissipation per pole 7.2 W AC-3 6.4 W AC-1

With With
Front cover

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Plate Plate
mounting support Rail Rail

CSA C22.2 No 60947-4-1


standards CSA C22.2 No 60947-5-1
EN/IEC 60947-1
EN/IEC 60947-4-1
EN/IEC 60947-5-1
GB/T 14048.4
UL 60947-4-1
UL 60947-5-1

BV BV
product certifications CCC CCC
CSA CSA
DNV-GL DNV
EAC GL
IECEE CB Scheme GOST
LROS (Lloyds register of shipping) LROS (Lloyds register of shipping)
RINA RINA
UL UL

Control circuit: screw clamp terminals 1 cable(s) Control circuit: screw clamp terminals 1 cable(s)
connections - terminals 1…2.5 mm²flexible with cable end 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) Control circuit: screw clamp terminals 1 cable(s)
1…4 mm²flexible without cable end 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) Control circuit: screw clamp terminals 1 cable(s)
1…4 mm²solid without cable end 1…4 mm²rigid
Control circuit: screw clamp terminals 2 cable(s) Control circuit: screw clamp terminals 2 cable(s)
1…2.5 mm²flexible with cable end 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) Control circuit: screw clamp terminals 2 cable(s)
1…4 mm²flexible without cable end 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) Control circuit: screw clamp terminals 2 cable(s)
1…4 mm²solid without cable end 1…4 mm²rigid
Power circuit: connector 1 cable(s) 4…50 mm²flexible Power circuit: screw terminals 1 cable(s)
with cable end 2.5…25 mm²flexible with cable end
Power circuit: connector 1 cable(s) 4…50 mm²flexible Power circuit: screw terminals 1 cable(s)
without cable end 2.5…25 mm²flexible without cable end
Power circuit: connector 1 cable(s) 4…50 mm²solid Power circuit: screw terminals 1 cable(s)
without cable end 2.5…25 mm²rigid
Power circuit: connector 2 cable(s) 4…16 mm²flexible Power circuit: screw terminals 2 cable(s)
with cable end 2.5…10 mm²flexible with cable end
Power circuit: connector 2 cable(s) 4…25 mm²flexible Power circuit: screw terminals 2 cable(s)
without cable end 2.5…16 mm²flexible without cable end
Power circuit: connector 2 cable(s) 4…25 mm²solid Power circuit: screw terminals 2 cable(s)
without cable end 2.5…16 mm²rigid

Control circuit: 1.2 N.m - on screw clamp terminals - Control circuit: 1.2 N.m - on screw clamp terminal -
tightening torque with screwdriver Philips No 2 with screwdriver Philips No 2
Control circuit: 1.2 N.m - on screw clamp terminals - Control circuit: 1.2 N.m - on screw clamp terminal -
with screwdriver flat Ø 6 mm with screwdriver flat Ø 6 mm
Power circuit: 12 N.m - on connector - with Power circuit: 5 N.m - on screw terminal - with
screwdriver flat Ø 6 to Ø 8 mm screwdriver flat Ø 6 to Ø 8 mm
Power circuit: 12 N.m - on connector hexagonal
screw head 4 mm

20...35 ms closing 12...26 ms closing


operating time 6...20 ms opening 4...19 ms opening
B10d = 1.3 Mcycles contactor with nominal load B10d = 1369863 cycles contactor with nominal load
safety reliability level conforming to EN/ISO 13849-1 conforming to EN/ISO 13849-1
B10d = 20 Mcycles contactor with mechanical load B10d = 20000000 cycles contactor with mechanical
conforming to EN/ISO 13849-1 load conforming to EN/ISO 13849-1

4 Mcycles 6000000 cycles
mechanical durability

3600 cyc/h 60 °C 3600 cyc/h 60 °C


maximum operating rate

Without built-in suppressor module Without built-in bidirectional peak limiting diode
coil technology suppressor

0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz


control circuit voltage limits 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz
0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz
1...1.1 Uc (55…70 °C):operational AC 50/60 Hz

245 VA 50 Hz cos phi 0.75 (at 20 °C) 140 VA cos phi 0.75 (at 20 °C)
inrush power in VA 245 VA 60 Hz cos phi 0.75 (at 20 °C) 160 VA cos phi 0.75 (at 20 °C)

26 VA 50 Hz cos phi 0.3 (at 20 °C) 13 VA 60 Hz cos phi 0.3 (at 20 °C)
hold-in power consumption in VA 26 VA 60 Hz cos phi 0.3 (at 20 °C) 15 VA 50 Hz cos phi 0.3 (at 20 °C)

6…10 W at 50/60 Hz
heat dissipation

type mechanically linked 1 NO + 1 NC conforming to type mechanically linked 1 NO + 1 NC conforming to


auxiliary contacts type IEC 60947-5-1 IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4- type mirror contact 1 NC conforming to IEC 60947-4-
1 1

25...400 Hz
signalling circuit frequency

5 mA for signalling circuit 5 mA for control circuit


minimum switching current

17 V for signalling circuit 17 V for control circuit


minimum switching voltage

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
1.5 ms on de-energisation between NC and NO 1.5 ms on de-energisation between NC and NO
non-overlap time contact contacts
1.5 ms on energisation between NC and NO contact 1.5 ms on energisation between NC and NO contacts

> 10 MOhm for signalling circuit > 10 MOhm for control circuit
insulation resistance

M11
contact compatibility

LC1D LC1D
compatibility code

15…25 kW at 200…240 V 3 phases


motor power range 30…50 kW at 380…440 V 3 phases
30…50 kW at 480…500 V 3 phases
55…100 kW at 480…500 V 3 phases

Direct on-line contactor


motor starter type

220 V AC standard
contactor coil voltage

IP20 front face conforming to IEC 60529


IP degree of protection

TH conforming to IEC 60068-2-30


protective treatment

3
pollution degree

-40…60 °C
ambient air temperature for operation 60…70 °C with derating

-60…80 °C -60…80 °C
ambient air temperature for storage

0...3000 m 3000 m without derating


operating altitude

850 °C conforming to IEC 60695-2-1 850 °C conforming to IEC 60695-2-1


fire resistance

V1 conforming to UL 94 V1 conforming to UL 94
flame retardance

Shocks contactor closed: 10 Gn for 11 ms


mechanical robustness Shocks contactor open: 8 Gn for 11 ms
Vibrations contactor closed: 3 Gn, 5...300 Hz
Vibrations contactor open: 2 Gn, 5...300 Hz

127 mm 127 mm
height
85 mm 75 mm
width

130 mm 119 mm
depth

1.61 kg 1.4 kg
net weight

PCE PCE
Unit Type of Package 1

1 1
Number of Units in Package 1

1.556 kg 1.447 kg
Package 1 Weight

9.5 cm 9.5 cm
Package 1 Height

13.5 cm 13.2 cm
Package 1 width

14 cm 14 cm
Package 1 Length

S02 S02
Unit Type of Package 2

5 5
Number of Units in Package 2

8.09 kg 7.566 kg
Package 2 Weight

15 cm 15 cm
Package 2 Height

30 cm 30 cm
Package 2 width

40 cm 40 cm
Package 2 Length

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
P06
Unit Type of Package 3

80
Number of Units in Package 3

140.26 kg
Package 3 Weight

80 cm
Package 3 Height

80 cm
Package 3 width

60 cm
Package 3 Length

Green Premium product Green Premium product


Sustainable offer status

REACh Declaration REACh Declaration


REACh Regulation

Yes Yes
REACh free of SVHC

Compliant EU RoHS Declaration Compliant EU RoHS Declaration


EU RoHS Directive

Yes Yes
Toxic heavy metal free

Yes Yes
Mercury free

Yes Yes
RoHS exemption information

China RoHS declaration China RoHS declaration


China RoHS Regulation

Product Environmental Profile Product Environmental Profile


Environmental Disclosure

The product must be disposed on European Union The product must be disposed on European Union
WEEE markets following specific waste collection and never markets following specific waste collection and never
end up in rubbish bins end up in rubbish bins

Yes Yes
PVC free

12 months 18 months
Warranty
(13-14)NO
terminals description ISO n°1 (21-22)NC
(A1-A2)CO

CSA C22.2 No 14
standards EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508

IP2x conforming to IEC 60529


IP degree of protection IP2x conforming to VDE 0106

10 gn contactor opened
shock resistance 15 gn contactor closed

2 gn 5…300 Hz contactor opened


vibration resistance 4 gn 5…300 Hz contactor closed

4…5 W at 50/60 Hz for control circuit


heat dissipation

End of Life Information


Circularity Profile

This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.