IS : 1742- 1993
( Reaffirmed 1996 )
Indian Standard
CODE OF PRACTICE FOR
BUILDING DRAINAGE
( Second Revision )
I
)I.
% .-
..“.
Indian Standard
CODE OF PRACTICE FOR
BUILDING DRAINAGE
( Second Revision )
Water Supply and Sanitation Sectional Committee, BDC 24
Chairman Representing
SHRI J. D’CRUZ Water Supply and Sewage Disposal Undertaking,
New Delhi
Members
CHIEB ENQINEER ( CIVIL I ) ( Alternate to
Shri J. D’Cruz )
ADVISER ( PHE ) Ministry of Works and Housing, New Delhi
DEPUTY ADVISER ( PHE ) (Alternate )
SHBI N. S. BHAIRAVAN Public Health Engineering Department, Govern-
ment of Kerala, Trivandrum
SUPEBINTENDINQENGINEER ( Alternate )
SHRI I. CHANDBA Public Works Department, Public Health Branch,
Government of Haryana, Chandigarh
SHRI K. K. GANDHI ( Alternate)
CHIEF ENGINEER ( CONSTKUCTION) Uttar Pradesh Jal Nigam, Lucknow
SUPERINTENDINOEYQINEER ( Alternate )
Snnr R. C. P. CHAUD~ARY Engineers India Ltd, New Delhi
SHRI H. V. RAO ( Alternate )
SHRI S. K. DAS~~PTA Calcutta Metropolitan Development Authority,
Calcutta
SHRI S. R. MUKHERJEE ( Alternate )
PROF.J. M. DAVE Institution of Engineers ( India ), Calcutta
SHRI S. G. DEOLALIKA~~. In personal capacity ( Flat No. 403, Savitri Cinema
Commerical Complex, .New Delhi )
SHRI B. R. N. GUPTA Ministry of Defence, Engineer-in-Chief’s Branch,
Army Headquarters
SHRI K. V. KI~ISHNA~CJHTHY
( Alternale )
HYDRAULIC E~GISEER Municipal Corporation of Greater Bombay,
Bombay
CHIEP EKGINEEK ( SEWERAGE
PROJECTS:) ( Alfcrt&e )
( Continued on page 2 )
0 Copyright 1984
BUREAU OF INDIAN STANDARDS
This publication is protected under the Itzdinn Copyright Act ( XIV of 1957 ) and
reproduction in whole or in part by any means except with written permission of the
publisher shall be deemed to be an infringement of copyright under the said Act.
I
( Continwd from page1 )
Members Representing
SEW R. A. KHANN~ Public Health Department, Government of
Madhva Pradesh. Bhonal
SHRI D. K. MITRA ( Alternate I )
SERI I. S. BAWEJA ( Alternate II )
SEBI P. KRISHNAN Central Public Works Department, New Delhi
SUIWEYOR OF WORKS-~ ( NDZ ) ( Alternate )
SHIZI M. Y. MADAN The Hindustan Construction Co Ltd, Bombay
SHRI C. E. S. RAO ( Alternate )
SERI S. L. MAINI Public Works Department, Public Health Branch,
Government of Puniab. Patiala
SHRI R. NATARAJAN Hindustan Dorr-Oliver-L&l, Bombay
SHRI B. M. RAHUL ( Alternate )
PBOB K. J. NATH All India Institute of Hygiene and Public Health,
Calcutta
SHRI D. GUIN ( Alternate )
PBO~ V. RAMAN National Environmental Engineering Research
Institute ( CSIR ), Nagpur
SHRI S. R. KSRIRSA~AR ( AIlernotc )
SHRI RANJIT SIN~H Ministry of Railways
DR A. V. R. RAO National Buildings Organization, New Delhi
SHRI 0. P. RATRA ( Alternate )
SECRETARY Indian Water Works Association, Bombay
SECRETARY GENERAL Institution of Public Health Engineers India,
Calcutta
SHRI R. N. BANERJEE ( Alternate )
SHRI L. R. SEH~AL L. R. Sehgal & Co, New Delhi
SHRI S. K. SHAKMA Central Building Research Institute ( CSIR ),
Roorkee
SHRI B. N. THYA~ARAJA Bangalore Water Supply and Sewerage Board,
Bangalore
SERI H. S. PUTTA~EXPANNA ( Alternate )
SHRIV.VARADARAJAN Madras Metropolitan Water Supply and Sewerage
Board. Madras
SHRI S. DAIVAXANI ( Alternate)
SHR~ G. RAMAN. Director General, IS1 ( Ex-o$icio Member )
Director ( Civ’Engg )
Secretary
SHRI A. K. AVASTHY
Assistant Director ( Civ Engg ), IS1
2
II
Indian Standard
CODE OF PRACTICE FOR
BUILDING DRAINAGE
( Second Revision )
0. FOREWORD
0.1 The Indian Standard ( Second Revision ) was adopted by the Indian
Standards Institution on 30 November 1983, after the draft finalized by
the Water Supply and Sanitation Sectional Committee had been approved
by the Civil Engineering Division Council.
0.2 This standard, published in 1960 and subsequently revised in 1972 was
intended to bring out a long felt uniformity in the variety of drainage
practices followed by various Municipal Corporation, Municipalities and
other bodies in the country in efficient drainage of surface and subsoil
water and sewage from buildings to public sewers. It is being revised to
incorporate improvements found necessary in the light of the usage of the
standard.
0.3 This code of practice represents a standard of good przctice and, there-
fore, takes the form of recommendations.
1. SCOPE
1.1 This code gives recommendations for the design, layout, construction
and maintenance of drains for waste water, surface water and subsoil
water and sewage together with all ancilliary works, like connections,
manholes, inspection chambers, etc, used within the building and from the
building to the connection to a public sewer or to treatment works, a
cesspool, a soakaway or a water course.
3
IS:1742 - 1985
2. TJUUWINOLOGY
2.0 For the purpose of this standard, the following definitions shall apply.
2.6 Channel - The open waterway through which sewage, storm water
or other liquid waste Aow at the invert of a manhole or an inspection
chamber.
2.7 Cleaning Eye - An access opening in a pipe or pipe fitting arranged
to facilitate the clearing or obstructions and fitted with removable cover.
2.9 Cover -
a) A removable plate for permitting access to a pire to a fitting
vessel or appliance.
b) The vertical distance between the top of the barrel of a buried
pipe or other construction and the surface of the ground.
2.18 Depth of Manhole - The vertical distance from the top of the
manhole cover to the outgoing invert of the main drain channel.
4
lSt1742-1983
2.27 Manhole - An opening by which a man may enter oi- leave a drain,
a sewer or other closed structure for inspection, cleaning and other main-
tenance operations, fitted with a suitable cover.
5
228 Manhole Chamber - A chamber constructed on a drain or sewer
so as to provide access thereto for inspection, testing or the clearance- of
obstruction.
2.29 Pipe Systems - The pipe systems as defined in IS : 5329-1983*.
2.30 Rest Rexad or Dack-Foot Bend - A bend, having a foot formed
integrally in its base, used to receive a vertical pipe.
2.31 Saddle - A purpose made fitting, so shaped as to fit over a hole cut
in a sewer or drain and used to form connections.
2.32 Sewer - A pipe or conduit, generally closed, but normally not flow-
ing full for carrying sewage or other waste liquids.
2.33 Soak-away - A pit, dug into permeable ground lined to form a
covered perforated chamber or filled with hard-core, to which liquid is led,
and from which it may soak away into the ground.
2.34 Slop Hopper ( Slop Sink ) - A hopper-shaped sink, with a flush-
ing rim and outlet similar to those of a WC pan, for the reception and
discharge of human excreta.
2.35 SoflGt - The highest point of the internal surface of a.sewer or
culvert at any cross section.
2.36 Soil Waste - The discharge from water closets, urinals, slop sinks,
stable or cowshed gullies and similar appliances.
2.37 Soil Pipe
a) In plumbing, a pipe that conveys the discharge of water closets
or fixtures having similar functions, with or without the discharges
from other fixtures.
b) A standard type of bell-and-spigot cast iron pipe of limited
strength.
2.38 Subsoil Water - Water occurring naturally in the subsoil.
2.39 Subsoil Water Drain
a) A drain intended to collect and carry away subsoil water.
b) A drain intended to dssperse into the subsoil the effluent from a
septic tank.
2.40 Surface Water Drain - A drain conveyiig surface water including
storm water.
2.41 Systems of Drainage
2.41.1 Combined System - A system of drains or sewers in which foul
water and surface ‘water are conveyed by the same pipes.
*Code of practice for sanitary pipe work above ground for buildin@ (JirJt revirion),
6
IS f 1742 - 1983
2.43 Vent Pipe - An open ended pipe, in a hot water apparatus, for the
escape of air and for the safe discharge of any steam generated.
2.44 Ventilating Pipe - A pipe in a sanitary pipework system which
facilitates the circulation of air within the system and protects trap seaIs
from excessive pressure fluctuation.
2.45 Waste Water ( Sullage ) - The discharge from wash basins, sinks
and similar appliances which does not contain human excreta.
2.46 Waste Pipe - In plumbing, any pipe that receives the discharge of
any fixtures, except water closets or similar fixtures and conveys the same
to the house drain or soil or waste stack. When such pipe does not connect
directly with a house drain or soil stack, it is called an indirect waste pipe.
2.47 Puff Ventilation - The ventilation provided for waste traps in two-
pipe system, in order to preserve the water seal.
3.1 Standards - All materials and fittings used in the construction of any
of the works or any of the appliances described in this code shall conform
to the latest editions of the relevant Indian Standard specifications where
available in so far as these standards are applicable. Where no such
standards exist, the materials, fittings and appliances shall be of the best
quality and workmanship, and shall be open to inspection by the purchaser
at the manufacturer’s works before despatch.
4. DESIGN CONSIDERATION
4.1.1 To achieve this aim, a drainage system shall satisfy the following
requirements:
*Equivalent metric units for scales, dimensions and quantities in general construction
work ( revised).
8
IS : 1742- x983
9
15:1742- 1983
10
IS:1742 -1983
*Toierance limits~for sewage effluents dirchargcd into inland surfacr waters (firsi
rmision) .
tMe?hods of sampling and test for sewage elfluenrs iJr -t rerision ).
11
IS : 1742 - 1983
4.2.3.4 The general subsoil water level and the subsoil conditions
shall be ascertained including the absorptive capacity of the soil.
4.2.4 Disposal of Surface and Subsoil Water - All information which may
influence the choice of methods of disposal or surface and/or subsoil waters
shall be obtained. In the absence of surface water drainage system and
if practicable and permissible, disposal into a natural water course or
soakaway may be adopted. The location and flood levels of the water
course as aiso the requirements of the authority controlling the river or the
waterway shall be ascertained.
4.3 Layout
4.3.1 General - Generally, rain water shall be dealt with separately
from sewage and sullage. Sewage and sullage shall be connected to sewers.
Storm water from courtyard may be connected to the sewer where it is not
possible to drain otherwtse after obtaining permission of the authority.
4.3.1.1 The layout shall be as simple and direct as practicable.
Considerations shall be given to alternative layouts so as to ensure that the
most economical and practical solution is adopted. The possibility of
alterations shall be avoided by exercising due care and forethought.
*Code of basic requirements for water supply, drainage and sanitation ( third
revision).
12
Is:1742-1993
*Code of practice for sanitary pipe work above ground for buildings ( jint revision ).
tSpecification for centrifugally cast ( spun ) iron pressure pipes for water, gas and
sewage ( second revision ).
JSpecification for vertically cast iron pressure pipes for water, gas and sewage
( first rcuision ).
13
4.3.4.5 Surcharge of sewers (precautzons ) -Where there is a risk of
the sewer becoming surcharged under storm conditions all gullies and
sanitary fittings shall be located above the level of maximum surcharge
of the sewer. Where this is not practicable, an anti-flood valve shall be
provided in the manhole nearest to the junction of the drain and sewer.
Parts exposed to wear in anti-flood valves shall be of non-corrodable
metal and easily accessible. The cross-sectional area of flow through the
valve shall not be less than that of the pipe connected. In extreme cases,
pumping may have to be considered.
4.3.4.6 The distance between inspection chamber and gully chamber
shall not exceed 6 m.
ColouY
Sewers Red
Waste water pipes and Blue
rain-water pipes
Existing work Black
14
Provided that in the case of an alteration or addition to an exis-
ting building this clause ‘shall be deemed to be satisfied if the
plans as furnished convey sufficient information for the proposals
to be readily identified with the previous sanctioned plans and
provided that the location of tanks and other fittings are consis-
tent with the structural safety of the building.
c3 the invert level of the municipal sewer, the road level, and the
connection level of the proposed drain connecting the building in
relation to the sewer;
4 the angle at which the drain from the building joins the sewer;
and
e>the alignment,
surface drains;
sizes, and gradients
if any.
of all drains and also of
4.5.1.1 For any fixtures not covered under Table 1, Table 2 may be
referred to for deciding their fixture unit rating depending on their drain
or trap size.
15
TABLE 1 FIXTURE UNITS Fgg;RzENT SANITARY APPLIANCE
( ckruss4.5.1 )
16
CSl.3 For convertin4 the total load in fixture units to the peak flow
in Iitres per minute, Fig. 1 M to be used.
1A Estimate Curves
FIXlURE UNITS
( CImrsc4.5.1.4 )
DIAMETER GRADIENT
Or PIPE ~~~~_~~_~~~~~~ _--h-_-__--__-_____-~
mm l/200 l/100 l/50 l/25
100 - 180 216 250
150 - 700 840 1 000
200 1 400 1 600 1 920 2 300
250 2 500 2 900 3 500 4200
300 3 900 4 600 5 600 6 700
375 7 000 8 300 10 000 12 000
19
IS: 1742-1983
4.7.1 Salt Glazed Stoneware Pi’es - For all sewers and drains in all solids,
except where supports are required as in made-up ground, glazed stone-
ware pipe shall be used as far as possible in preference to other type of
pipes, they are particularly suitable where acid effluents or acid subsoil
conditions are likely to be encounterd. Salt glazed stoneware pipes shall
conform to IS : 651-1980* or IS : 30C6-1979t.
4.7.2 Cement Concrete Pipes - When properly ventilated, cement concrete
pipes with spigot and socket or collar joints present as alternative to
glazed ware sewers over 150 mm diameter. These shall not be used to
carry acid effluents or sewage under condition favourable for the produc-
tion of hydrogen sulphide and shall not be laid in those subsoils which are
l;kely to affect adversely the quality or strength of concrete. Cement
concrete pipes may be used for surface water drains in all diameters.
These pipes shall conform to IS : 45&1971$. Where so desired the life of
cement concrete pipe may be increased by lining inside of the pipe by
suitable coatings like epoxy/polyester resin, etc.
4.7.3 Cast Iron Pipes - Cast iron pipes ( see IS : 1536-19769 and +S :
1537-19767 ) shall b e used in the following situations:
a) In bad or unstable ground where soil movement is expected;
b) In made-up or tipped ground;
c) To provide for increased strength where a sewer is laid at insuffi-
cient depth, where it is exposed or where it has to be carried on
piers or above ground;
d) Under buildings and where pipes are suspended in basements and
like situations;
e) In reaches where the velocity is more than 2.4 m/set; and
f) For crossings of water courses.
--
*Specification for salt-glazed stoneware pipes and fittings (fourth rmision ).
tspecification for chemically resistant glazed stoneware pipes and fittings (jirst
revision t.
fspecification for concrete pipes ( with and without reinforcements ) ( sccnnd rcuikm).
$Specification for centrifugally cast ( spun ) iron pressllre pipes for water, gas and
sewage ( second reuision).
aSpecification for vertically cast iron presstIre pipes for water, gas and sewage (first
. evision ).
20
Is:174!2-f98!3
*Specification for asbestos cement building pipes and pipe fittings, gutters and
gutter fittings and roofing fittings: Part 1 Pipes and pipe fittings (,firsf revision ).
tspecification for asbestos cement pressure pipe ( second mision ).
SSpecification for Lead pipes: Part 1 for other than chemical purposes ( second
rrvision ) .
$Spe&fication for unplasticized PVC pipes for potable water supplies (first revision ).
IlSpecificationfor high density polythylene pipes for potable water,supplies sewage
and industrial effluents ( second revision ).
21
i&:1742-1983
4.8.2 All vertical soil, waste ventilating and anti-siphonage pipes shall
be covered on top with a copper or heavily galvanized iron wire dome OT
cast iron terminal guards. All cast iron pipes which are to be painted
periodically shall be fixed suitably to the wall to give a minimum clearance
of 50 mm.
NOTE - Asbestos cement cowls may be used in case asbestos cement pipes are
used as soil pipes.
4.9.1 Where the diameter of the drain is increased, the crown of the
pipe shall be fixed at the same level and necessary slope given in the invert
of the manhole chamber. In exceptional cases and where unavoidable, the
crown of the branch sewer may be fixed at a lower level but in such cases
the peak flow level of the two sewers should be kept the same.
*Code of practice for sanitary pipe work above ground for buildings (Jirsf revision).
$&cle of practice for ancillary structures in sewerage system: Part 1 Manholes. _
rs:r74!2-1983
23
IS t 1742- 1989
RENDERING WITH
CEMENT MORTAR I:2
rSLOPE J IN 6
DETAIL OF BENCHING
SECTION XX SECTION YY
NOTE - Wall thicknesseshave been inalcated in brick lengths to provide for use
of modular bricks [ see IS : 1077-1966 ‘ Specification for common burnt clay building
bricks (first revision ).’ ] or traditional bricks. In the figure, B = one brick length,
1’5 B = one and a half brick length, etc.
RENDERING WITH
CEMENT MORTAR I:2
SLOPE I IN 6
DETAIL OF BENCHING ’
i*_-__ ___‘_________J
I---Y
SECTIONAL PLAN AT ZZ.
SOcmi-
-_CI
SECTION XX SECTION YY
NOTE- Wall thicknesses have been indicated in brick lengths to provide for use
of modular bricks [ see IS : 1077- 1966 ‘ Specification for common burnt clay building
bricks (Jirst revision ) ’ ] or traditional bricks. In the figure, B = one brick length,
1’5 B = one and a half brick length, etc.
25
its:1742-1983
RENDERING WITH
CEMENT MORTAR 1:2
DETAIL OF BENCHING
I-Y
SECTIONAL PLAN AT ZZ
SECTION XX SECTION YY
NOTE-Wall thicknesses have been indicated in brick lengths to provide for use
of modular bricks [ SCLIS : 1077-1966‘ Specification for common burnt clay building
bricks (prst w&ion ) ’ ] or traditional bricks. In the figure, B = one brick length,
1.5 B = on; and a half brick length, etc.
26
L ______ ________ _______ J
t- Y
SECTIONAL PLAN AT ZZ
SECTION XX SECTION YY ’ ’
NOTE - Wall thicknesses have been indicated in brick lengths to provide for use
of modular bricks [ JCLIS : 1077-1966 ‘ Specification for common burnt clay building
bricka (jrst revision) ’ ] or traditional bricks. In the figure, B = one brick length,
1’5 B = one and a half brick length, etc.
FIG. 5 DROP MANHOLE
27
i$ I 1942- 1983
4.9.9 All brick work in manhole chamber and shaft shall be carefully
built in English bond. The jointing face of each brick being well buttered
with cement mortar before laying, so as to ensure a full joint. The
construction of walls in brick work shall be done in accordance with
IS : 2212-1962*. The.cement mortar used shall not be weaker than 1 part
of cement to 3 parts of sand ( sue IS : 2250-1981t ).
4.9.10 The wall shall be plastered ( 15 mm, Ma ) both inside and out-
side with cement mortar 1 : 3; where sub-soil water conditions exist, a
richer mix may be used for both masonry and plaster. All angles shall be
rounded to 7.5 cm radius and all rendered internal surfaces shall have hard
impervious finish obtained by using a steel trowel.
4.10 Storm Water Drainage - The object of the storm water drainage
is to collect and carry, for suitable disposal, the rain water collected within
the premises of the building.
4.10.1 Water Precipitation and Run-of--. Rainfall statistics for the areas
under consideration shall be studied to arrive at a suitable figure on the
basis of whic.h the storm water drains could be designed. Consideration
shall be given to the effects of special local conditions and to the intensity
and duration of rainfall.
28
IS : 1742 - 1983
29
fS:1742- 1983
4.10.3.9 The storm water shall be led off in a suitable open drain to
a water course. The open drain, if not of pucca masonry throughout,
shall be constructed in pucca masonry as at least where there is either a
change in direction or gradient.
30
I$ : 1742 - 1983
direction of the flow of subsoil water may usually be judged by the general
inclination of the land surface, and the main lines of the subsoil drains shall
f&x+ the natural falls wherever possible.
4.11.3 P7ecaution.f - Subsoil drains shall be sitted so as not to endanger
the stability of the buildings or earthwork. In some portions of the drain,
it may be necessary to use non-porous jointed pipes.
4.11.3.1 No field pipe shall be laid in such a manner or in such a
position as to communicate directly with any drain constructed or adapted
to be cased for conveying sewage except where absolutely unavoidable and
in that case a suitable efficient trap shall be provided between subsoil drain
and such sewer.
32
fS : 1742 - 1983
not available the subsoil drains may be connected, with the approval of
the authority, through an intercepting trap to the surface water drainage
system.
Nom - Care shall be taken that there is no backilow from subsurface drains
during heavy rains.
LEAD PIPE
/
WIPED
f- SOLDER
JOINT
BRASS OR
COPPER
/ THIMBLE
MOLTEN LE AD
JOINT WELL
CAULKED
YARN
Cl PIPE
33
IS:1742 -1983
/-WC TRAP
,CEMENT MORTAR
JOINT(l:l)
-YARN
-BRASS THiMBLE
WITH SOCKET
\WIPED SOLDER
JOINT
LEAD PIPE
5.4 Jointing Cast Iron Pipes with Stoneware Pipes ( see Fig. 8 ) -
Where any cast iron soil pipe, waste pipe, ventilating pipe or trap is con-
nected with a stoneware or semi-vitrified waste pipe or drain communicat-
ing with a sewer, the beaded spigot end of such cast iron soil pipe, waste
pipe, ventilating pipe, or trap shall be inserted into a socket of such stone-
ware of semi-vitrified ware pipe or drain and the joint made with mortar
consisting of one part of cement and one part of clean coarse sand after
placing a tarred gasket or hemp yarn soaked in neat cement slurry round
the joint and inserted in it by means of a caulking tool.
34
1s : 1742 - 1983
‘II
I
I
/-SW PIPE
5.4.1 Jointing Stoneware with Cast Iron Pipes - Where any water closet
pan or earthenware trap connected to such pan is to be jointed with a
cast iron soil pipe, the joint between the stoneware spigot and the cast iron
socket shall always be of a flexible ( non-rigid ) nature. Such joint shall be
made preferably with a mixture of bitumen and chopped asbestos fibre
( not dust ).
5.5 Jointing Lead Pipes - The joints in lead pipes shall be made as
wiped solder joints ( see Fig. 9 ). The minimum and the maximum length
of the wiped solder joints shall be 80 mm and 90 mm respectively. The
solders shall generally consist of two parts of lead and one part of tin.
5.6 Jointing Glazed Stoneware Pipes ( see Fig. 10 ) - Tarred gasket
or hemp yarn soaked in thick cement slurry shall first be placed round the
spigot of each pipe and the spigot shall then be placed well home into the
socket of the pipe previously laid. The pipe shall then be adjusted and
fixed in the correct position and the gasket caulked tightly home so as not
to fill more than l/4 of the total depth ( or 13 mm in depth ) of the socket.
5.6.1 The remainder of the socket shall be filled with a stiff mixture of
cement mortar in the proportion of one part cement and one part sharp
sand, When the socket is filled, a fillet shall be formed round the joint
with a trowel, forming an angle of 45” with the barrel of the pipe.
35
tS : 1742- 1983
WIPED
SOLDER
CEMENT MORTAR
TARRED GASKET OR
SPUN YARN SOAKED
IN NEAT CEMENT
36
I6 t 1742 - 1983
37
IS I 1742 - 1983 * .
.
W = D + 30 cm, where D is external diameter of, the pipe
T = ( 10 cm for pipes under 150 mm nominal dla,
I 15 cm for pipes of 150 mm nominal dii and over.
FIG. 11 BEDDING
5.9.2 Huunching - Concrete haunching ( see Fig. .12 ) shall consist ofi
4 A concrete bed as described for bedding ( ste 5.9.1 ).
b) The full width of the bed carried up to the level of the horizontal
diameter of the pipe; and
4 Splays from this revel carried up on both sides of the pipe, from
the full width of the bed to meeting the pipe barrel tangentially.
Flo. 12 HAUNCHING
38
. tS : 1742- 1983
l-l 5cm4
l------w+
W = D + 30 cm, where D isthe external diameter of the pipe.
Fro. 13 SURROUND OR ENCASING
5.9.4 Piers for Cast Iron Pipes - Where supporting piers are specified for
cast iron pipes, they shall be not less than 30 cm in length ( parallel to the
. axis of the pipe ) and at least equal in section to that described for haunch-
ing in 5.9.2. Pipes shall be built just behind the pipe sockets, intermediate
piers being provided where necessary.
5.9.5 Glazed Ware Pipes - The minimum support or protection for
glazed stoneware pipes shall be as follows:
a) When cover is less than 1 m below ground level and where pipes
are unavoidably exposed above ground surface, the pipes shall be
completely encased or surrounded with concrete;
b) Where the pipes are laid on a soft soil with the maximum water
table lying at the invert of the pipe, the pipe sewer shall be bedded
on concrete;
c) Where the pipes have to be laid in a soft soil with the maximum
water table rising above the invert of the pipe, but below the top
of the barrej, the pipe sewers shall be haunched;
d) Where the maximum water table is likely to rise above the top of
the barrel or wherever the pipe is laid in soft soil, the pipe
sewers shall be completely encased or surrounded with concrete;
and
39
1s: 1742A983
..
.
0: e) Where the sewers are to be laid adjacent to growing trees, the
pipe sewers shall be encased or surrounded with-concrete to. avoid
damage to the pipes likely to be caused by the roots of the trees.
40
IS :1742 - 1983
'.
41
&t 1742 - 1983
42
5.14 Back-Filling
5.14.1 Filling of the trench shall not be commenced until the length of
pipes therein has been tested and passed ( see 8.2 ).
5.14.2 All timber which may be withdrawn with safety shall be removed
as filling proceeds.
5.14.3 Where the pipes are unprotected by concrete haunching, the
first operation in filling shall be carefully done to hand-pack and temp
selected fine material around the lower half of the pipes so as to buttress
them to the sides of the trench.
5.14.4 The filling shall then be continued to 150 mm over the top of
the pipe using selected fine hand-packed material, watered and rammed
on both sides of the pipe with a wooden rammer. On no account shall
material be tipped into the trench until the first 150 mm of filling has been
completed. The process of filling and tamping shall proceed evenly so as
to maintain an equal pressure on both sides of the pipeline.
5.14.5 Filling shall continue in layers not exceeding 150 mm in ’
thickness, each layer being watered and rammed.
*Specification for galvanized steel sheets ( plain and corrugated ) ( third rstision ).
43
IS : 1742 - 1983
closed with galvanized sheets not less than 1.25 mm in thickness, to fit the
section and made water-tight. Junctions with down-fall rain-water pipes
or leaders shall be made water-tight. Gutters shall have a general
minimum fall of 1 in 120.
44
IS 8 1742 - 1983
7.1.1.1 It is advisable to cover the pipes with clinker free from fine
ash, brick ballast or other suitable rubble, or a layer of inverted turf,
brush-wood or straw before refilling the trench, in order to prevent the
infiltration of silt through the open joints. Where the subsoil drain is also
to serve the purpose of collecting surface water, the rubble shall be carried
up to a suitable level and when required for a lawn or playing field, the
remainder of the trench shall be filled with previous topsoil. When
refilling the trenches, care shall be taken to prevent displacemet of pipes
in line of levels. When they pass near trees or through hedges, socket
pipes with cement or bitumen joints shall be used to prevent penetration
by roots.
8.1 Inspection
8.1.3 Cast iron pipes shall be carefully examined for damage to the
protective coating. Minor damage shall be made good by painting over
with hot tar or preferably bitumen. But if major defects in the coating
exists, the pipe shall not be used unless re-coated. Each pipe shall be
carefully re-examined for soundness before laying.
45
Mcl742-lam
8.2 Testing
a.2.2 Smoke Test ---All soil pipes, waste pipes, and vent pipes
and all other pipes when above ground shall be approved gas-tight by a
sm6ke test conducted under a pressure of 25 mm of water and maintained
for 15 minutes after all trap seals have been filled with water. The smoke
is produced by burning oily waste or tar paper or similar material in the
combustion chamber of a smoke machine. Chemical smokes are not
satisfactory.
8.2.3 Wder Test
8.2.3.1 For pipes other than cast iron - Glazed/stoneware and
concrete pipes shall be subjected to a test pressure of at least 1.5 m head
of water at the highest point of the section under test. The tolerance
figure of two litres per centimetre of diameter per kilometre may be allowed
during a period of ten minutes. The test shall be carried out by suitably
plugging the low end of drain and the ends of connections, if any, and
Wing the system with water. A kuncklebend shall temporarily be jointed in
at the top end and a sufficient length of the vertical pipe jointed to it so. as
to provide the required test head or the top end may be plugged with a
connection to a hose ending in a funnel which could be raised or lowered
till the required head is obtained and fixed suitably for observation.
Subsidence of the test water may be due to one or more of the following
causes:
a) Absorption by pipes and joints,
b) Sweating of pipes or joints,
c) Leakage at joints or from defective pipes, and
d) Trapped air.
Allowance shall be made for (a) by adding water until absorption
has ceased after which the test proper should commence. Any leakage
will be visible and the defective part of the work should be cut out and
made good. A slight amount of sweating which is uniform may be over-
looked, but excessive sweating from a particular pipe or joint shall be
watched for and taken as indicating a defect to be made good.
NOTE - This test will not be applicable to sanitary pipe work aboveground
level.
8.2.3.2 For cast iron pipes - Cast iron sewers and drains shall be
tested as for glazed stone ware and concrete pipes. The drain plugs shall be
suitably strutted to prevent their being forced out of the pipe during the
test.
46
f$ : 1742 - 1983
8.2.4 Tests for Straightness and Obstruction - The following tests shall be
carried out:
8.2.5 Test Records - Complete records shall be kept of all tests carried
out of sewers and drains both during construction and after being put into
service.
9. MAINTENANCE
9.1 General - Domestic drainage systems shall be inspected at regular
intervals. The system shall be thoroughly cleaned out at the same time
and any defects discovered shall be made good.