3.7.

1 PER UNIT DATA CALCULATION

Data Formula Result(pu)


Base
MVAbase =500

Source
MVAbase =500 MVAbase
MVASC =500 Zpu = ------------ = 1.000
X/R =7.5 MVASC
Rpu = Zpu cos (tan-1X/R) = 0.132

Xpu = Zpu sin (tan-1X/R) = 0.991

Cable No. 1

MVAbase =500 R xL MVAbase


V =13800 Rpu = -------- x -------- = 0.147
Size mm2 =150mm² 1000 x Set V2
Type =XLPE
Set =1
R (Ω/km) =0.16000 X xL MVAbase
X (Ω/km) =0.11500 Xpu = -------- x -------- = 0.106
2
Length(m) =349.80 1000 x Set V

Cable No. 2

MVAbase =500 R xL MVAbase


V =13800 Rpu = -------- x -------- = 0.007
Size mm2 =150mm² 1000 x Set V2
Type =XLPE
Set =1
R (Ω/km) =0.16000 X xL MVAbase
X (Ω/km) =0.11500 Xpu = -------- x -------- = 0.005
2
Length(m) =14.74 1000 x Set V
TRANSFO TR-1
MVAbase =500 MVAbase
MVA =1.5 Zpu = Z X --------- = 19.167
Z% =5.75 MVATR
X/R =7
Rpu = Zpu cos (tan-1X/R) = 2.711

Xpu = Zpu sin (tan-1X/R) = 18.974

Cable No. 3

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 0.955
2
Size mm2 =250 305 x Set V
Type =THWN2
Set =8
R(Ω/305m) =0.027 X xL MVAbase
X(Ω/305m) =0.048 Xpu = -------- x -------- = 1.698
Length(m) =27.61 305 x Set V2

Genset EDG-1

MVAbase =500 Xd" VG2 MVAbase


kVA Load =600 Xpu =---- X -----X ------ = 97.750
2
% Load =100% 100 VS MVAm
p.f. =1
Σhp (kVA) =600 Xpu
Vg =400 Rpu =--------------- = 4.250
Vs =400 X/R
Xd" =11.73
X/R =23
Cable No. 5

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 1.384
2
Size mm2 =250 305 x Set V
Type =THWN2
Set =4
R(Ω/305m) =0.027 X xL MVAbase
X(Ω/305m) =0.048 Xpu = -------- x -------- = 2.460
2
Length(m) =20 305 x Set V

Cable No. 4

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 1.111
2
Size mm2 =250 305 x Set V
Type =THWN2
Set =4
R(Ω/305m) =0.027 X xL MVAbase
X(Ω/305m) =0.048 Xpu = -------- x -------- = 1.975
Length(m) =16.06 305 x Set V2

Cable No. 6

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 6.999
2
Size mm2 =325 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.023 X xL MVAbase
X(Ω/305m) =0.048 Xpu = -------- x -------- = 14.607
Length(m) =29.7 305 x Set V2
Lump Load: MDP-ADM

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =198.4 Xpu =---- X -----X ------ = 1385.001
2
% Motor =55% 100 VS MVAm
p.f. =0.85
Σhp (kVA) =92.752 Xpu
Vm =400 Rpu =--------------- = 581.933
Vs =400 X/R
Xd" =25.6923
X/R =2.38
( hp=kVA)

Cable No. 7

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 38.153
2
Size mm2 =100 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.062 X xL MVAbase
X(Ω/305m) =0.051 Xpu = -------- x -------- = 31.384
Length(m) =60.06 305 x Set V2

Cable No. 8

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 19.679
2
Size mm2 =250 305 x Set V
Type =THWN2
Set =3
R(Ω/305m) =0.027 X xL MVAbase
X(Ω/305m) =0.048 Xpu = -------- x -------- = 34.984
Length(m) =213.4 305 x Set V2
Lump Load: MDP-WH

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =209.3 Xpu =---- X -----X ------ = 1146.158
2
% Motor =63% 100 VS MVAm
p.f. =0.85
Σhp (kVA) =112.08 Xpu
Vm =400 Rpu =--------------- = 481.579
Vs =400 X/R
Xd" =25.6923
X/R =2.38
( hp=kVA)

Cable No. 9

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 105.481
2
Size mm2 =14 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.49 X xL MVAbase
X(Ω/305m) =0.064 Xpu = -------- x -------- = 13.778
Length(m) =21.01 305 x Set V2

Lump Load: MDP-PR

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =35.82 Xpu =---- X -----X ------ = 20091.493
2
% Motor =21% 100 VS MVAm
p.f. =0.85
Σhp (kVA) =6.394 Xpu
Vm =400 Rpu =--------------- = 8441.804
Vs =400 X/R
Xd" =25.693
X/R =2.38
( hp=kVA)
Cable No. 14

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 820.492
2
Size mm2 =3.5 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =2 X xL MVAbase
X(Ω/305m) =0.068 Xpu = -------- x -------- = 27.897
2
Length(m) =40.04 305 x Set V

Motor No. M1

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =2 Xpu =---- X -----X ------ = 75567.648
% Motor =100% 100 VS 2 MVAm
p.f. =0.85
Σhp (kVA) =1.7 Xpu

Vm =400 Rpu =--------------- = 75567.648


Vs =400 X/R
Xd" =25.693
X/R =1.00
( hp=kVA)
Cable No. 16

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 586.066
2
Size mm2 =3.5 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =2 X xL MVAbase
X(Ω/305m) =0.068 Xpu = -------- x -------- = 19.927
2
Length(m) =28.6 305 x Set V

Motor No. M3

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =2 Xpu =---- X -----X ------ = 75567.648
% Motor =100% 100 VS 2 MVAm
p.f. =0.85
Σhp (kVA) =1.7 Xpu

Vm =400 Rpu =--------------- = 75567.648


Vs =400 X/R
Xd" =25.693
X/R =1.00
( hp=kVA)

Cable No. 18

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 319.992
Size mm2 =8 305 x Set V2
Type =THWN2
Set =1
R(Ω/305m) =0.78 X xL MVAbase
X(Ω/305m) =0.065 Xpu = -------- x -------- = 26.666
Length(m) =40.04 305 x Set V2

Motor No. M5

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =13.5294 Xpu =---- X -----X ------ = 11170.870
% Motor =100% 100 VS 2 MVAm
p.f. =0.85
Σhp (kVA) =11.5 Xpu

Vm =400 Rpu =--------------- = 6361.543


Vs =400 X/R
Xd" =25.693
X/R =1.756
( hp=kVA)

Cable No. 10

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 9.299
Size mm2 =200 305 x Set V2
Type =THWN2
Set =1
R(Ω/305m) =0.033 X xL MVAbase
X(Ω/305m) =0.049 Xpu = -------- x -------- = 13.807
2
Length(m) =27.5 305 x Set V
Lump Load: EMDP-ADM

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =175.1 Xpu =---- X -----X ------ = 2332.801
2
% Motor =37% 100 VS MVAm
p.f. =0.85
Σhp (kVA) =55.069 Xpu
Vm =400 Rpu =--------------- = 2332.801
Vs =400 X/R
Xd" =25.693
X/R =1.00
( hp=kVA)

Cable No. 11

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 36.756
2
Size mm2 =100 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.062 X xL MVAbase
X(Ω/305m) =0.051 Xpu = -------- x -------- = 30.235
Length(m) =57.86 305 x Set V2

Cable No. 12

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 43.790
2
Size mm2 =100 305 x Set V
Type =THWN2
Set =3
R(Ω/305m) =0.062 X xL MVAbase
X(Ω/305m) =0.051 Xpu = -------- x -------- = 36.021
Length(m) =206.8 305 x Set V2
Lump Load: EMDP-WH

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =107.8 Xpu =---- X -----X ------ = 1820.752
2
% Motor =77% 100 VS MVAm
p.f. =0.85
Σhp (kVA) =70.556 Xpu
Vm =400 Rpu =--------------- = 1820.752
Vs =400 X/R
Xd" =25.693
X/R =1.00
( hp=kVA)

Cable No. 13

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 66.733
2
Size mm2 =22 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.31 X xL MVAbase
X(Ω/305m) =0.06 Xpu = -------- x -------- = 12.916
Length(m) =21.01 305 x Set V2

Lump Load: EMDP-PR

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =50.1 Xpu =---- X -----X ------ = 8872.505
2
% Motor =34% 100 VS MVAm
p.f. =0.85
Σhp (kVA) =14.479 Xpu
Vm =400 Rpu =--------------- = 8872.505
Vs =400 X/R
Xd" =25.693
X/R =1.00
( hp=kVA)
Cable No. 20

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 3.044
2
Size mm2 =250 305 x Set V
Type =THWN2
Set =2
R(Ω/305m) =0.027 X xL MVAbase
X(Ω/305m) =0.048 Xpu = -------- x -------- = 5.410
2
Length(m) =22 305 x Set V

Motor No. M8

Σ of Induction Motor 50HP below


MVAbase =500 Xd" VM2 MVAbase
kVA Load =30 Xpu =---- X -----X ------ = 5037.843
% Motor =100% 100 VS 2 MVAm
p.f. =0.85
Σhp (kVA) =25.5 Xpu

Vm =400 Rpu =--------------- = 2370.750


Vs =400 X/R
Xd" =25.693
X/R =2.13
( hp=kVA)
Cable No. 21

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 11.271
2
Size mm2 =150 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.044 X xL MVAbase
X(Ω/305m) =0.051 Xpu = -------- x -------- = 13.064
2
Length(m) =25.0 305 x Set V

Cable No. 22

MVAbase =500 R xL MVAbase


V =400 Rpu = -------- x -------- = 105.481
2
Size mm2 =14 305 x Set V
Type =THWN2
Set =1
R(Ω/305m) =0.49 X xL MVAbase
X(Ω/305m) =0.064 Xpu = -------- x -------- = 13.778
Length(m) =21.0 305 x Set V2