wind power generation, and for the backup
Container power supply of UPS and emergency
illumination. Their designed life for
standby usage is 15 years
Normal Voltage 2V
Attain certificate:
Capacity 2000 Ah @ 10hr to 1.80V per cell @ 25℃(77℉)
ISO9001(03006Q10084R1M)
Weight Approx.125 kg (275 lbs)
Internal Resistance (full charged) Approx. 0.18mΩ@ 25℃(77℉) ISO14001(03004E1009R0M)
Maximum Discharge Current 12400A (5sec) ISO18001(03004E1009R0M)
Self Discharge @ 25℃ (77℉) No more than 3 % after 30 days storage
UL (MH28466)
Discharge: -40℃~50℃(-40℉~122℉)
Operating Temperature Range Charge: -20℃~45℃(-4℉~113℉) CE(ED/2007/30041C)
Storage: -20℃~40℃(4℉~104℉)
Russia telecom
Recommended Operating Temperature 15℃~25℃(59℉~77℉)
Conforms to the standard:
Maximum Charging Current Limited 200A
GB/T 19638.2-2005
Float: 2.23 V, Temps coefficient -3 mV/℃
Charging Voltage @ 25℃(77℉) YD/T799-2002
Cycle: 2.30 V
Contain Materials ABS JISC8704-2:1999
105 % @ 40℃
Capacity Affected by Temperature 85 % @ 0℃
60 % @ -20℃
Current Voltage
(I10A) (V) Capacity
Voltage(V)
2.40 (%)
1.2
charge voltage
2.30 charge current
1.0 100
battery capacity
2.20
0.8 75
2.10
0.6 50 8I10 1I10
50% discharge 2I10
2.00 100% discharge
7I10 5I4I 10 3I10
6I10 10
0.4 25
9I10
1.90 10I10
0.2 0
1.80
0
0 4 8 12 16 24 32 40 48 Discharge time(h)
(Hours)
120
Discharge capacity(%C10)
100
10
100 80
20
80 60
40 30
60 40
40 20
20 0 3 6 9 12 15 18 21 24
-40 -20 0 20 40 60
Temperature( ) Storage Time (months)
2011-05