Professional Documents
Culture Documents
Revision: 1
Model(s) PCC 3100, PCC 3200, PCC 3201, PCC 3300 (PC 3.x)
Background/Description:
When a paralleling system consists of different models of PCC3xxx genset controls, some
adjustments may be necessary in order to insure transparent load sharing performance.
These adjustments are NOT necessary if the controls are all identical control model.
Corrective Actions:
To ensure proper paralleling capability, refer to the below table as it relates to the system's
equipment configuration.
PCC3201
(Full PCC3201
Authority (Two-Box PCC3300
PCC3100 (1) PCC3200 Application) Application) (PC3.x)
Change Change Change Change Change
Parameter Default To Default To Default To Default To Default To
Reactive
- - - - - - - -
Power Scale (2) 695 820
Load Share No
kW Gain (3) 6 5 1.0 2.21 1.0 2.21 1.0 1.15 1.0 change
Notes:
1. For optimal compatibility with other PCC3xxx controls, the PCC3100 code version
should be greater than or equal to that listed in the below “PCC3100 Minimum Code
Version” table.
When should one be concerned with checking and adjusting the V/Hz slope so
they are the same across gensets?
One should consider this when any one of the following are true:
system has kW load steps in excess of 50-75% of online capacity
system has genset kW ratings that cover more than a 2:1 range
system has a reverse kVAR time delay setting that is less than 10 seconds (default
setting is 10 sec)
What symptom would one see if the V/Hz Slope setting was an issue?
If the V/Hz slope settings are too different from one genset to another, kVAR sharing will be
unbalanced during load transients that depress the bus frequency by more than 1Hz below
nominal. Then, if there is very little kVAR load, it may result in reverse kVAR flowing into
one or more generators for the duration of the transient. In very extreme cases of a long
duration transient (heavy load step) and significant V/Hz setting difference, genset(s) could
shut down on a reverse kVAR fault.
System Example:
To demonstrate the method, consider a system consisting of 3 gensets: one with PCC3100,
one with PCC3201, and one with PCC3300 genset controllers.
1. From the PCC3100 HMI, the “REG VHZ” number was found to be 8.
2. Using the formula for PCC3100 V/Hz slope (from section below): = 76 / 8 = 9.5 %
V/Hz
3. From the PCC3201 InPower connection, the “V/Hz Rollof Table” was found to be:
The +/- marking for the kW and kVAR load sharing signals are backwards on the PCC3100
in relation to all other PCC3xxx controls. The correct connections are shown in the table
below. If any connections are reversed, when multiple gensets are online, reverse kW or
reverse kVAR shutdowns will likely occur. If just one genset is online, it may show a speed
or voltage droop at no load.
For reference, here are what the published drawings show. PCC3100 is the only one that
has the polarity marked backwards on the drawing.
Contact:
Further questions or concerns regarding this notification or the information stated above,
please contact in the following order: