You are on page 1of 11

1 2 3 4 5 6 7 8 9 10 11 12

PHOTOVOLTAIC MODULO TSM-DD14A 365W


LEGEND / LEYENDA
947 TRACKER NCLAVE 370Wp 2Vx29 MODULES
992 473.5
40
TRACKER NCLAVE 370Wp 2Vx43+1 MODULES

TRACKER NCLAVE 365Wp 2Vx43+1 MODULES

MV STATION

1200
A O&M BUILDING
CENTRO DE CONTROL
A
MT NUEVA: 480m

1960
PATH WIDTH 4,0m
CAMINO ANCHO 4,0 m

PERIMETRAL CHANNEL (THIS IS A PRELIMINARY


DESIGN IN THE ABSENCE OF HYDROLOGICAL STUDY)

Camino
PERIMETER FENCE
VALLADO PERIMETRAL

GATE ACCESS
PUERTA DE ACCESO

Princip
PROPERTY BOUNDARIES

TRACKER CONTROL UNIT (TCU)

al
ANEMOMETER & NETWORK CONTROL UNIT (NCU)

AC BOX

INVERTER
INVERSOR

45x60 ELECTRICAL TRENCH (LV)


Peak Power Watts Pmax (Wp) / 365
Open Circuit Voltage Voc (V) / 48.0 40x80 ELECTRICAL TRENCH (LV)
Canal
B Short Circuit Current Isc (A) / Corriente de cortocircuito Isc (A)
Module Efficiency (%) /
9.77
18.8
60x95 ELECTRICAL AND COMMUNICATION TRENCH (LV) B
Canal Maximum Power Voltage Vmpp (V) / 39.3 70x200 ELECTRICAL AND CANAL CROSS TRENCH (LV)
Maximum Power Current Impp (A) / 9.30
LMT Planta Solar 60x100 ELECTRICAL AND COMMUNICATION TRENCH (MV)

PR-L1 40x60 ELECTRICAL AND COMMUNICATION TRENCH


S-2
MANHOLE 100x100x100 (LV)
ARQUETA 100x100x100 (BT)

10.7 PR-L2 MANHOLE CANAL CROSS 90x90x200 (LV)


ARQUETA DE CRUCE DE CANAL 90x90x200 (BT)

MANHOLE 80x80x120 (MV)


ARQUETA 80x80x120 (MT)

MANHOLE 200x200x120 (MV)


ARQUETA 200x200x120 (MT)

SECURITY MANHOLE 45x45x45

Canal
ARQUETA PARA SEGURIDAD 45x45x45

Canal
MASS CONCRETE FOOTING FOR SECURITY SYSTEM

WEATHER STATION

PHOTOVOLTAIC MODULO TSM-DD14A 370W


C NOMENCLATURE / NOMENCLATURA C
947 ACBOX-XX AC BOX = AC COMBINER BOX /
992 473.5 XX = ACBOX NUMBER /
40
INV-XX-YY
INV-XX-YY INV = INVERTER / INVERSOR
ESTACIONAMIENTOS INV-XX-YY
XX = ACBOX NUMBER /
YY = INVERTER NUMBER /

1200
TCU = TRACKER CONTROL UNIT (TCU)

1960
TEMPORARY TCU-XX-YY UNIDAD DE CONTROL DEL TRACKER (TCU)
FACILITIES XX = ACBOX TO WHICH BELONGS
LIRIOS

AC.BOX-9
YY = TCU NUMBER /

INV-9-2
INV-10-1

INV-9-1
SEC-3 XX = ACBOX TO WHICH BELONGS
PR-L5 S-XX-ZZ-TT
Acceso a Planta Solar SEC-2 ZZ = INVERTER TO WHICH BELONGS
INVERSOR AL QUE PERTENECE
SEC-1 TT = STRING NUMBER / G

Track. = TRACKER

4
INTERNAL PATH
AA = TRACKER NUMBER /

INV-6-1

AC.BOX-5

INV-5-2
INV-7-1

AC.BOX-6
D D

INV-6-2
INV-8-2
SEC-3

INV-7-2
AC.BOX-7
INV-8-1
AC.BOX-8
INV-10-2
AC.BOX-12

AC.BOX-11

INV-11-2
INV-11-1
INV-12-2
DRAWING DATA / DATOS DE PROYECTO
INV-12-1
Camino interno provisorio

Peak Power Watts Pmax (Wp) / 370


Open Circuit Voltage Voc (V) / 48.3 DRAWING DATA: LIRIO DE CAMPO
DATOS DE PROYECTO

INV-5-1
Short Circuit Current Isc (A) / Corriente de cortocircuito Isc (A) 9.83
Total Power : 2.990,19 kWp
Module Efficiency (%) / 19.0 Potencia total
Maximum Power Voltage Vmpp (V) / 39.7 Total Power AC : 2.700 kWac
Potenica total AC
Maximum Power Current Impp (A) / 9.33 Ratio AC/DC : 1,1074
Ratio AC/DC
Modules:

INV-4-2
AC.BOX-4
Strings:
24 strings (modules TSM-DD14A 365Wp)

INV-4-1
255 strings (modules TSM-DD14A 370Wp)
29 modules per string

Estructure: SP160 NCLAVE GROUP 1500Vdc


Estructura
Canal

Configuration 1: 0 trackers 2Vx29


2 strings per tracker
E 0 total strings
Configuration 2: 8 trackers 2Vx43+1
E
3 strings per tracker
24 total strings

Configuration 1: 18 trackers 2Vx29


2 strings per tracker
SMART STRING INVERTER SUN2000-105KTL-H1 36 total strings
INVERSOR SUN2000-105KTL-H1 Configuration 2: 73 trackers 2Vx43+1
3 strings per tracker
INPUT RATINGS / VALORES DE ENTRADA (DC) 219 total strings
Maximum current per MPPT / 25 A
Maximum Input voltage / 1500 V Pitch: 10,70 m (E-W)
0,3 m (N-S)
MPPT Operating Voltage Range / 600... 1500 V
Number of MPP Trackers / 6 24 Smart String Inverter:

OUTPUT RATINGS / VALORES DE SALIDA (AC) 18 Inverters: Huawei SUN2000-105KTL-H1 (1500V).


12 strings per inverter
Rated Output Voltage / 800 V, 3W + PE
Rated AC Grid Frequency / Frecuencia nominal 50/60 Hz 3 Inverters: Huawei SUN2000-105KTL-H1 (1500V).
11 strings per inverter
116 kW
3 Inverters: Huawei SUN2000-105KTL-H1 (1500V).
Max. Output Current / 84.6 A 10 strings per inverter
Camin

Power Factor Range / Rango de Factor de Potencia 0.8 LG...0.8 LD (AJUST.)


AC COMBINER BOX :
o inter

EFFICIENCY / RENDIMIENTO
F Max. Efficiency / 99.0% F
no pro

12 AC BOX : Huawei ACBox-2/1-D-C


European Efficiency / Euroeficiencia 98.8% 2 Inverter per ACBox
visorio

MECHANICAL DATA /
Dimensions (WxHxD) / Dimensiones (A x B x H) 1075x605x310 mm 1 MV Station: 2.800 kVA
1
Weight (with mounting plate) / Peso 79 kg
AC.BOX-1

AC.BOX-2

1 Transformer: 2.800 kVA


INV-3-1 AC.BOX-3

AMBIENT CONDITIONS / CONDICIONES DE AMBIENTE


INV-1-1 INV-1-2

INV-2-2 INV-2-1

Canal 1 TRANSFORMADOR
Operating Temperature Range 0,8 / 13,2 kV
10.7 Temperatura de funcionamiento 6,5 Ucc %
INV-3-2

o provisorio
Camino intern

LEGEND / LEYENDA
1

Canal
STRING CABLE PV TOPSOLAR ZZ-F / H1X2X2-K 1.8 kVdc CU 1x6 mm2
PR-L4 Cable String PV TOPSOLAR ZZ-F / H1X2X2-K1.8 kVdc Cu 1x6 mm2

AC-LV CABLE AC BOX TO MV-STATION


AC-BT Cable AC Box a Transformador
AC-LV CABLE AC BOX TO MV-STATION
AC-BT Cable AC Box a Transformador
G G
AC-MT Cable Transformador a POI

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.
Acceso a Planta Solar

6 2019/12/31 LYNK LYNK


5 2019/12/10 LYNK LYNK
PR-L3 4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

Ca
na
l 10.7

Project:
LIRIO DE CAMPO SOLAR PARK 2,9902 Mwp
Subject:
H NAIAD PROJECTS H
Canal
Para ser impreso en formato A1 (840x597mm)
To be printed in A1 size (840x597mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia GENERAL LAYOUT

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR 1:1000 1/11 2019/12/31
757-PV-ELE-DRW-AMET-010 LV-DC_AC SLD
757-PV-ELE-DRW-AMET-011 Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase:

757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 A1 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
ZONA A

PHOTOVOLTAIC MODULO TSM-DD14A 365W


LEGEND / LEYENDA
947 TRACKER NCLAVE 370Wp 2Vx29 MODULES
992 473.5
40
TRACKER NCLAVE 370Wp 2Vx43+1 MODULES

Canal TRACKER NCLAVE 365Wp 2Vx43+1 MODULES

MV STATION

1200
A O&M BUILDING
CENTRO DE CONTROL
A

1960
PATH WIDTH 4,0m
CAMINO ANCHO 4,0 m

Canal PERIMETRAL CHANNEL (THIS IS A PRELIMINARY


DESIGN IN THE ABSENCE OF HYDROLOGICAL STUDY)

LMT Planta Solar PERIMETER FENCE


VALLADO PERIMETRAL

GATE ACCESS

PR-L1 PUERTA DE ACCESO

PROPERTY BOUNDARIES
S-2
TRACKER CONTROL UNIT (TCU)

ANEMOMETER & NETWORK CONTROL UNIT (NCU)

AC BOX

10.7 PR-L2 INVERTER


INVERSOR

45x60 ELECTRICAL TRENCH (LV)


Peak Power Watts Pmax (Wp) / 365
Open Circuit Voltage Voc (V) / 48.0 40x80 ELECTRICAL TRENCH (LV)

B Short Circuit Current Isc (A) / Corriente de cortocircuito Isc (A)


Module Efficiency (%) /
9.77
18.8
60x95 ELECTRICAL AND COMMUNICATION TRENCH (LV) B
Maximum Power Voltage Vmpp (V) / 39.3 70x200 ELECTRICAL AND CANAL CROSS TRENCH (LV)
Maximum Power Current Impp (A) / 9.30
60x100 ELECTRICAL AND COMMUNICATION TRENCH (MV)

40x60 ELECTRICAL AND COMMUNICATION TRENCH


Canal

MANHOLE 100x100x100 (LV)


Canal

ARQUETA 100x100x100 (BT)

MANHOLE CANAL CROSS 90x90x200 (LV)


ARQUETA DE CRUCE DE CANAL 90x90x200 (BT)

MANHOLE 80x80x120 (MV)


ARQUETA 80x80x120 (MT)

MANHOLE 200x200x120 (MV)


ARQUETA 200x200x120 (MT)

SECURITY MANHOLE 45x45x45


ARQUETA PARA SEGURIDAD 45x45x45

MASS CONCRETE FOOTING FOR SECURITY SYSTEM

WEATHER STATION

PHOTOVOLTAIC MODULO TSM-DD14A 370W


C NOMENCLATURE / NOMENCLATURA C
947 ACBOX-XX AC BOX = AC COMBINER BOX /
992 473.5 XX = ACBOX NUMBER /
40
INV-XX-YY
INV-XX-YY INV = INVERTER / INVERSOR
INV-XX-YY
XX = ACBOX NUMBER /
YY = INVERTER NUMBER /

1200
ESTACIONAMIENTOS TCU = TRACKER CONTROL UNIT (TCU)

1960
TCU-XX-YY UNIDAD DE CONTROL DEL TRACKER (TCU)
XX = ACBOX TO WHICH BELONGS

YY = TCU NUMBER /

XX = ACBOX TO WHICH BELONGS


S-XX-ZZ-TT
ZZ = INVERTER TO WHICH BELONGS
INVERSOR AL QUE PERTENECE
TT = STRING NUMBER / G

TEMPORARY Track. = TRACKER


AA = TRACKER NUMBER /
FACILITIES
D LIRIOS D

AC.BOX-9

INV-9-2
INV-10-1

INV-9-1
DRAWING DATA / DATOS DE PROYECTO
SEC-3 Peak Power Watts Pmax (Wp) / 370
PR-L5 Open Circuit Voltage Voc (V) / 48.3 DRAWING DATA: LIRIO DE CAMPO
DATOS DE PROYECTO
Acceso a Planta Solar SEC-2 Short Circuit Current Isc (A) / Corriente de cortocircuito Isc (A) 9.83
Module Efficiency (%) / 19.0 Total Power : 2.990,19 kWp
Potencia total
Maximum Power Voltage Vmpp (V) / 39.7 Total Power AC : 2.700 kWac
SEC-1 Maximum Power Current Impp (A) / 9.33
Potenica total AC
Ratio AC/DC : 1,1074
Ratio AC/DC
Modules:

Strings:
4
INTERNAL PATH 24 strings (modules TSM-DD14A 365Wp)
255 strings (modules TSM-DD14A 370Wp)
29 modules per string

INV-6-1

AC.BOX-5
Estructure: SP160 NCLAVE GROUP 1500Vdc
Estructura

INV-5-2
INV-7-1

AC.BOX-6

INV-6-2
Configuration 1: 0 trackers 2Vx29

INV-8-2
SEC-3

INV-7-2
AC.BOX-7
2 strings per tracker
E 0 total strings
Configuration 2: 8 trackers 2Vx43+1
E

INV-8-1
AC.BOX-8
3 strings per tracker

INV-10-2
AC.BOX-12

AC.BOX-11

24 total strings
INV-11-2
INV-11-1

Configuration 1: 18 trackers 2Vx29


2 strings per tracker
SMART STRING INVERTER SUN2000-105KTL-H1
INV-12-2

36 total strings
INVERSOR SUN2000-105KTL-H1 Configuration 2: 73 trackers 2Vx43+1
INV-12-1

INPUT RATINGS / VALORES DE ENTRADA (DC) 3 strings per tracker


219 total strings
Camino interno provisorio

Maximum current per MPPT / 25 A


Maximum Input voltage / 1500 V Pitch: 10,70 m (E-W)
MPPT Operating Voltage Range / 600... 1500 V 0,3 m (N-S)

Number of MPP Trackers / 6 24 Smart String Inverter:

OUTPUT RATINGS / VALORES DE SALIDA (AC) 18 Inverters: Huawei SUN2000-105KTL-H1 (1500V).

INV-5-1
12 strings per inverter
Rated Output Voltage / 800 V, 3W + PE
Rated AC Grid Frequency / Frecuencia nominal 50/60 Hz 3 Inverters: Huawei SUN2000-105KTL-H1 (1500V).
11 strings per inverter
116 kW
3 Inverters: Huawei SUN2000-105KTL-H1 (1500V).
Max. Output Current / 84.6 A
10 strings per inverter
Power Factor Range / Rango de Factor de Potencia 0.8 LG...0.8 LD (AJUST.)

EFFICIENCY / RENDIMIENTO AC COMBINER BOX :

F Max. Efficiency / 99.0% F


European Efficiency / Euroeficiencia 98.8% 12 AC BOX : Huawei ACBox-2/1-D-C
2 Inverter per ACBox
MECHANICAL DATA /
Dimensions (WxHxD) / Dimensiones (A x B x H) 1075x605x310 mm 1 MV Station: 2.800 kVA

INV-4-2
1
Weight (with mounting plate) / Peso 79 kg

AC.BOX-4
AMBIENT CONDITIONS / CONDICIONES DE AMBIENTE 1 Transformer: 2.800 kVA
1 TRANSFORMADOR
Operating Temperature Range 0,8 / 13,2 kV

INV-4-1
Temperatura de funcionamiento 6,5 Ucc %

LEGEND / LEYENDA
STRING CABLE PV TOPSOLAR ZZ-F / H1X2X2-K 1.8 kVdc CU 1x6 mm2
Canal

Cable String PV TOPSOLAR ZZ-F / H1X2X2-K1.8 kVdc Cu 1x6 mm2

AC-LV CABLE AC BOX TO MV-STATION


AC-BT Cable AC Box a Transformador
AC-LV CABLE AC BOX TO MV-STATION
AC-BT Cable AC Box a Transformador
G G
AC-MT Cable Transformador a POI

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


5 2019/12/10 LYNK LYNK
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

Project:
LIRIO DE CAMPO SOLAR PARK 2,9902 Mwp
Subject:
H NAIAD PROJECTS H
Para ser impreso en formato A1 (840x597mm)
To be printed in A1 size (840x597mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia GENERAL LAYOUT: ZONE A

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR 1:500 2/11 2019/12/31
757-PV-ELE-DRW-AMET-010 LV-DC_AC SLD
757-PV-ELE-DRW-AMET-011 Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase:

757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (1) A1 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8 9 10 11 12
AC.BO
AC.BOX-
INV-8-1
AC.BOX-8
INV-10-2
AC.BOX-12

AC.BOX-11

INV-11-2
1 2 3 4 5 6 7 8 9 10 11 12

INV-11-1
INV-12-2
INV-12-1
PHOTOVOLTAIC MODULO TSM-DD14A 365W
LEGEND / LEYENDA

Camino interno provisorio


947 TRACKER NCLAVE 370Wp 2Vx29 MODULES
992 473.5
40
TRACKER NCLAVE 370Wp 2Vx43+1 MODULES

INV-5-1
TRACKER NCLAVE 365Wp 2Vx43+1 MODULES

MV STATION

1200
A O&M BUILDING
CENTRO DE CONTROL
A

1960
PATH WIDTH 4,0m
CAMINO ANCHO 4,0 m

PERIMETRAL CHANNEL (THIS IS A PRELIMINARY


DESIGN IN THE ABSENCE OF HYDROLOGICAL STUDY)

PERIMETER FENCE
VALLADO PERIMETRAL

GATE ACCESS
PUERTA DE ACCESO

INV-4-2
AC.BOX-4
PROPERTY BOUNDARIES

TRACKER CONTROL UNIT (TCU)

INV-4-1
ANEMOMETER & NETWORK CONTROL UNIT (NCU)

AC BOX

INVERTER
INVERSOR

45x60 ELECTRICAL TRENCH (LV)


Peak Power Watts Pmax (Wp) / 365
Open Circuit Voltage Voc (V) / 48.0 40x80 ELECTRICAL TRENCH (LV)
Canal

B Short Circuit Current Isc (A) / Corriente de cortocircuito Isc (A)


Module Efficiency (%) /
9.77
18.8
60x95 ELECTRICAL AND COMMUNICATION TRENCH (LV) B
Maximum Power Voltage Vmpp (V) / 39.3 70x200 ELECTRICAL AND CANAL CROSS TRENCH (LV)
Maximum Power Current Impp (A) / 9.30
60x100 ELECTRICAL AND COMMUNICATION TRENCH (MV)

40x60 ELECTRICAL AND COMMUNICATION TRENCH

MANHOLE 100x100x100 (LV)


ARQUETA 100x100x100 (BT)

MANHOLE CANAL CROSS 90x90x200 (LV)


ARQUETA DE CRUCE DE CANAL 90x90x200 (BT)

MANHOLE 80x80x120 (MV)


ARQUETA 80x80x120 (MT)

MANHOLE 200x200x120 (MV)


ARQUETA 200x200x120 (MT)

SECURITY MANHOLE 45x45x45


ARQUETA PARA SEGURIDAD 45x45x45

MASS CONCRETE FOOTING FOR SECURITY SYSTEM

WEATHER STATION

PHOTOVOLTAIC MODULO TSM-DD14A 370W


C NOMENCLATURE / NOMENCLATURA C
947 ACBOX-XX AC BOX = AC COMBINER BOX /
992 473.5 XX = ACBOX NUMBER /
40
INV-XX-YY
INV-XX-YY INV = INVERTER / INVERSOR
INV-XX-YY
XX = ACBOX NUMBER /
YY = INVERTER NUMBER /

1200
TCU = TRACKER CONTROL UNIT (TCU)

1960
TCU-XX-YY UNIDAD DE CONTROL DEL TRACKER (TCU)
XX = ACBOX TO WHICH BELONGS

YY = TCU NUMBER /

XX = ACBOX TO WHICH BELONGS


S-XX-ZZ-TT
ZZ = INVERTER TO WHICH BELONGS
INVERSOR AL QUE PERTENECE
TT = STRING NUMBER / G

Track. = TRACKER
AA = TRACKER NUMBER /
Camin

D D
o inter

DRAWING DATA / DATOS DE PROYECTO


Peak Power Watts Pmax (Wp) / 370
no pro

Open Circuit Voltage Voc (V) / 48.3 DRAWING DATA: LIRIO DE CAMPO
DATOS DE PROYECTO
Short Circuit Current Isc (A) / Corriente de cortocircuito Isc (A) 9.83
Module Efficiency (%) / 19.0 Total Power : 2.990,19 kWp
Potencia total
visorio

Maximum Power Voltage Vmpp (V) / 39.7 Total Power AC : 2.700 kWac
Potenica total AC
Maximum Power Current Impp (A) / 9.33
Ratio AC/DC : 1,1074
Ratio AC/DC
Modules:

Strings:
24 strings (modules TSM-DD14A 365Wp)

AC.BOX-1

AC.BOX-2
INV-3-1 AC.BOX-3 255 strings (modules TSM-DD14A 370Wp)
29 modules per string

INV-1-1 INV-1-2

INV-2-2 INV-2-1
Estructure: SP160 NCLAVE GROUP 1500Vdc
Estructura

Configuration 1: 0 trackers 2Vx29

E 10.7 2 strings per tracker


0 total strings E
Configuration 2: 8 trackers 2Vx43+1
INV-3-2

3 strings per tracker

o inter no pr ovisorio 24 total strings

Camin Configuration 1: 18 trackers 2Vx29


2 strings per tracker
SMART STRING INVERTER SUN2000-105KTL-H1 36 total strings
INVERSOR SUN2000-105KTL-H1 Configuration 2: 73 trackers 2Vx43+1
INPUT RATINGS / VALORES DE ENTRADA (DC) 3 strings per tracker
219 total strings
Maximum current per MPPT / 25 A
1

Maximum Input voltage / 1500 V Pitch: 10,70 m (E-W)

Canal
MPPT Operating Voltage Range / 600... 1500 V 0,3 m (N-S)

Number of MPP Trackers / 6 24 Smart String Inverter:

OUTPUT RATINGS / VALORES DE SALIDA (AC) 18 Inverters: Huawei SUN2000-105KTL-H1 (1500V).

PR-L4 Rated Output Voltage /


Rated AC Grid Frequency / Frecuencia nominal
800 V, 3W + PE
50/60 Hz 3 Inverters:
12 strings per inverter

Huawei SUN2000-105KTL-H1 (1500V).


11 strings per inverter
116 kW
3 Inverters: Huawei SUN2000-105KTL-H1 (1500V).
Max. Output Current / 84.6 A
10 strings per inverter
Power Factor Range / Rango de Factor de Potencia 0.8 LG...0.8 LD (AJUST.)

EFFICIENCY / RENDIMIENTO AC COMBINER BOX :

F Max. Efficiency / 99.0% F


European Efficiency / Euroeficiencia 98.8% 12 AC BOX : Huawei ACBox-2/1-D-C
2 Inverter per ACBox
MECHANICAL DATA /
Dimensions (WxHxD) / Dimensiones (A x B x H) 1075x605x310 mm 1 MV Station: 2.800 kVA
1
Weight (with mounting plate) / Peso 79 kg
AMBIENT CONDITIONS / CONDICIONES DE AMBIENTE 1 Transformer: 2.800 kVA
1 TRANSFORMADOR
Operating Temperature Range 0,8 / 13,2 kV
Temperatura de funcionamiento 6,5 Ucc %

LEGEND / LEYENDA
STRING CABLE PV TOPSOLAR ZZ-F / H1X2X2-K 1.8 kVdc CU 1x6 mm2
Cable String PV TOPSOLAR ZZ-F / H1X2X2-K1.8 kVdc Cu 1x6 mm2
Acceso a Planta Solar
ZONA B AC-LV CABLE AC BOX TO MV-STATION
AC-BT Cable AC Box a Transformador
AC-LV CABLE AC BOX TO MV-STATION
AC-BT Cable AC Box a Transformador
G G
AC-MT Cable Transformador a POI

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


5 2019/12/10 LYNK LYNK
4 2019/11/28 LYNK LYNK

Ca Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

na
l 10.7
Project:
LIRIO DE CAMPO SOLAR PARK 2,9902 Mwp
Subject:
H NAIAD PROJECTS H
Para ser impreso en formato A1 (840x597mm)
To be printed in A1 size (840x597mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia GENERAL LAYOUT: ZONE B
Canal

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR 1:500 3/11 2019/12/31
757-PV-ELE-DRW-AMET-010 LV-DC_AC SLD
757-PV-ELE-DRW-AMET-011 Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase:

757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (2) A1 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8

Ondaplast HF-UV, or similar


STRING CABLES INSTALLATION DETAIL 2Vx43+1 MODULES. BACK VIEW Ondaplast HF-UV, o equivalente
2 string: 29 serial Modules 1 string: 29 serial Modules
DETALLE DE INSTALACION DE CABLES. VISTA TRASERA

6 cables
of 3 strings

Max. 10-15cm
A M.21 M.10 M.22 M.9 M.23 M.1 M.2 M.29 M.3 M.28 M.4 M.27 M.5 M.26 M.6 M.25 M.7 M.24 M.8 M.23 M.9 M.22 M.10 M.21 M.11 M.20 M.12 M.19 M.13 M.18 M.14 M.17 M.15 M.16 M.16 M.15 M.17 M.14 M.18 M.13 M.19 M.12 M.20 M.11 M.21 M.10 M.22 M.9
M.23
A
M.25 M.7 M.24 M.8 M.1 M.2 M.29 M.3 M.28 M.4 M.27 M.5 M.26 M.6 M.25 M.7 M.24 M.8 M.23 M.9 M.22 M.10 M.21 M.11 M.20 M.12 M.19 M.13 M.18 M.14 M.17 M.15 M.16 M.1 M.2 M.29 M.3 M.28 M.4 M.27 M.5 M.26 M.6 M.25 M.7 M.24 M.8

TRACKER 1 TRACKER 2

STRING CABLES INSTALLATION DETAIL 2Vx29 MODULES. BACK VIEW STRING CABLES DETAIL
DETALLE DE INSTALACION DE CABLES. VISTA TRASERA Ondaplast HF-UV, or similar STRING CABLES DETAIL / DETALLE DE CABLEADO DE STRING DETALLE DE CABLEADO DE STRING

B 2 string: 29 serial Modules Ondaplast HF-UV, o equivalente B


CONNECTION BOX

4 cables
of 2 strings

M.1 M.2 M.29 M.3 M.28 M.4 M.27 M.5 M.26 M.6 M.25 M.7 M.24 M.8 M.23 M.9 M.22 M.10 M.21 M.11 M.20 M.12 M.19 M.13 M.18 M.14 M.17 M.15 M.16

M.1 M.2 M.29 M.3 M.28 M.4 M.27 M.5 M.26 M.6 M.25 M.7 M.24 M.8 M.23 M.9 M.22 M.10 M.21 M.11 M.20 M.12 M.19 M.13 M.18 M.14 M.17 M.15 M.16 FLANGES WILL BE INSTALLED AMONG MODULES
THE MAXIMUM ARROW OF
APPROXIMATELY EACH ONE METER
UNION BETWEEN STRING
MUST BE UV RESISTANT
SHOULD BE 10-15cm
APROXIMADAMENTE 1 POR METRO
DEBEN SER RESISTENTES A RAYOS UV
10-15cm

CONNECTOR DETAIL / DETALLE DE CONECTOR LEGEND / LEYENDA

FEMALE CONNECTOR
TRACKER NCLAVE 2Vx29 MODULES

CONECTOR HEMBRA
C CONNECTOR
CONECTOR
C
CONNECTION BOX

MALE CONNECTOR
CABLE PV ZZ-F

CONECTOR MACHO
CABLE PV ZZ-F

CONNECTORS INSTALLED BY FIELD WITH TWO CABLE PV ZZ-F


CABLE PV ZZ-F
DRIVERS TO COMBINE STRINGS
CONECTORES INSTALADOS POR CAMPO CON DOS 1 STRING: 29 SERIAL MODULES

CONNECTIONS DETAIL. SCALE 1/50 TRENCH LV STRING DETAIL. SCALE 1/50 CONDUCTORES PARA COMBINAR STRINGS
2 STRING: 29 SERIAL MODULES
DETALLE DE CONEXIONES. ESCALA 1/50 DETALLE DE ZANJAS BT STRING. ESCALA 1/50

POWER SUPPLY CABLE TO ENGINE


CABLE de TCU al motor

1m* TCU
Antenna CONNECTION DETAIL 1 / CONNECTION DETAIL 2 / CONNECTION DETAIL 1 /
AC-BOX INV. Antena
Ondaplast HF-UV, or similar OUTPUT-ACBOX / SALIDA ACBOX INPUT-ACBOX / ENTRADA ACBOX OUTPUT-ACBOX / SALIDA ACBOX
D Ondaplast HF-UV, o equivalente
D
INVERTER

String cables Fire-resistant polyurethane sealing foam Fire-resistant polyurethane sealing foam Fire-resistant polyurethane sealing foam
Fire-resistant and UV resistant polyurethane sealing foam

The excavation in this zone is done manually.


Conduit Conduit
Cable from Inv. to AC-BOX
CABLE de INV. al AC-BOX
Ondaplast HF-UV, or similar
Ondaplast HF-UV, o equivalente
From AC-BOX to MV Station
Del AC-BOX al CT
Bending radius 60cm Natural Soil Natural Soil Bending radius 60cm

From INV. to AC-BOX


Del Inversor al AC-BOX Natural Soil
Sand Sand
Natural Soil

Sand Sand

Natural Soil Natural Soil

*NOTE: MINIMUM LENGTH 1m FROM POLE TRACKER TO POLE INSTALLATION


NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
ACBOX AND INVERTER. TO SEE DETAIL INSTALLATION ACBOX AND INVERTER ON
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.
DRAWING 757-PV-MEC-DRW-AMET-302-00
*NOTA: DISTANCIA MINIMA DE 1 m DESDE EL POSTE DEL TRACKER HASTA EL POSTE DE

INVERSOR VER PLANO 757-PV-MEC-DRW-AMET-302-00 6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

CONNECTION DETAIL 1 /

OUTPUT-ACBOX / SALIDA ACBOX

Project:
LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
Subject:
Fire-resistant polyurethane sealing foam NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia STRING CABLES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR V.SCALES 4/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (3) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

STRING CABLES INSTALLATION SCHEDULE. INV-1-2, INV-5-2, INV-6-1, INV-6-2, INV-7-1, INV-7-2, INV-8-1, INV-8-2, INV-10-2, INV-11-1, INV-11-2
ESQUEMA DE INSTALACION DE CABLES
1 STRING: 29 SERIAL MODULES
LEGEND / LEYENDA
TRACKER NCLAVE 2Vx29 MODULES
1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1
CONNECTOR
CONECTOR
... ... ... ...
CONNECTION BOX

A CABLE PV ZZ-F
CABLE PV ZZ-F A
CABLE PV ZZ-F
CABLE PV ZZ-F
1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1
1 STRING: 29 SERIAL MODULES
... ... ... ...
2 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

DC
STRING INVERTER (INV-XX-YY)
12 STRINGS
AC

STRING CABLES INSTALLATION SCHEDULE. INV-5-1


B ESQUEMA DE INSTALACION DE CABLES B

1 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29
C ... ...
C

DC
STRING INVERTER (INV-XX-YY)
10 STRINGS
AC

D D

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

Project:
LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
Subject:
NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia STRING CABLES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR N/S 5/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (4) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
STRING CABLES INSTALLATION SCHEDULE. INV-1-2, INV-5-2, INV-6-1, INV-6-2, INV-7-1, INV-7-2, INV-8-1, INV-8-2, INV-10-2, INV-11-1, INV-11-2
ESQUEMA DE INSTALACION DE CABLES
1 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

A A
1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

DC
STRING INVERTER (INV-XX-YY)
12 STRINGS
AC
B STRING CABLES INSTALLATION SCHEDULE. INV-5-1
B
ESQUEMA DE INSTALACION DE CABLES

1 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

C C
1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29

... ...

DC
STRING INVERTER (INV-XX-YY)
10 STRINGS
AC

D D

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

LEGEND / LEYENDA
TRACKER NCLAVE 2Vx29 MODULES Project:
LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
CONNECTOR
CONECTOR Subject:
CONNECTION BOX NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

CABLE PV ZZ-F Location:


CABLE PV ZZ-F

CABLE PV ZZ-F
CABLE PV ZZ-F Drawing:
1 STRING: 29 SERIAL MODULES Reference Documents / Documentos de Referencia STRING CABLES INSTALLATION DETAILS

2 STRING: 29 SERIAL MODULES 757-PV-GEN-DRW-AMET-001


Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR N/S 6/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (5) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
STRING CABLES INSTALLATION SCHEDULE. INV-1-1, INV-2-1, INV-3-1
ESQUEMA DE INSTALACION DE CABLES
1 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...


LEGEND / LEYENDA
TRACKER NCLAVE 2Vx29 MODULES

CONNECTOR
CONECTOR

A CONNECTION BOX A
CABLE PV ZZ-F
1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1 CABLE PV ZZ-F

CABLE PV ZZ-F
CABLE PV ZZ-F
... ... ... ...
1 STRING: 29 SERIAL MODULES

2 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

(12 STRINGS FOR EACH TUBE)

B (12 STRINGS POR TUBO) B


DC
STRING CABLES INSTALLATION SCHEDULE. INV-2-2, INV-3-2 STRING INVERTER (INV-XX-YY)
ESQUEMA DE INSTALACION DE CABLES 12 STRINGS
1 STRING: 29 SERIAL MODULES AC

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1 29 28 27 5 4 3 2 1

... ... ... ...

C C

1 2 3 4 5 27 28 29 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1

... ... ...

(12 STRINGS FOR EACH TUBE)

(12 STRINGS POR TUBO)

DC
STRING INVERTER (INV-XX-YY)
11 STRINGS
D AC
D

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

Project:
LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
Subject:
NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia STRING CABLES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR N/S 7/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (6) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

STRING CABLES INSTALLATION SCHEDULE. INV-4-1 STRING CABLES INSTALLATION SCHEDULE. INV-4-2
ESQUEMA DE INSTALACION DE CABLES ESQUEMA DE INSTALACION DE CABLES

1 STRING: 29 SERIAL MODULES


1 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1
A 1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1
A
... ...
... ...

1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1

... ...

1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1

... ...
1 2 3 4 5 27 28 30 29 28 27 5 4 3 2 1

... ...

1 2 3 4 5 27 28 30 29 28 27 5 4 3 2 1

DC ... ...
STRING INVERTER (INV-XX-YY)
B (4 CIRCUITS FOR EACH TUBE)
10 STRINGS B
(4 CIRCUITOS POR TUBO) AC

1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1

... ...
1 2 3 4 5 27 28 30 29 28 27 5 4 3 2 1

... ...

1 2 3 4 5 27 28 30 30 28 27 5 4 3 2 1

... ...

DC
STRING INVERTER (INV-XX-YY)
(2 CIRCUITS FOR EACH TUBE)
10 STRINGS
(2 CIRCUITOS POR TUBO) AC

C 1 2 3 4 5 27 28 30 30 28 27 5 4 3 2 1 C
... ...

LEGEND / LEYENDA
D TRACKER NCLAVE 2Vx29 MODULES
D
CONNECTOR
CONECTOR

CONNECTION BOX

CABLE PV ZZ-F
CABLE PV ZZ-F

CABLE PV ZZ-F
CABLE PV ZZ-F

1 STRING: 29 SERIAL MODULES

2 STRING: 29 SERIAL MODULES

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

Project:
LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
Subject:
NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia STRING CABLES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR N/S 8/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (7) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
STRING CABLES INSTALLATION SCHEDULE. INV-12-2
ESQUEMA DE INSTALACION DE CABLES
1 STRING: 29 SERIAL MODULES

1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1

A ... ... A

1 2 3 4 5 27 28 29 29 28 27 5 4 3 2 1

... ...

1 2 3 4 5 27 28 30 29 28 27 5 4 3 2 1

... ...
B B

1 2 3 4 5 27 28 30 29 28 27 5 4 3 2 1

... ...

1 2 3 4 5 27 28 30

...
C C

DC
(3 CIRCUITS FOR EACH TUBE) STRING INVERTER (INV-XX-YY)
12 STRINGS
(3 CIRCUITOS POR TUBO) AC
30 28 27 5 4 3 2 1

1 2 3 4 5 27 28 30 ...

...
D D

1 2 3 4 5 27 28 30

...

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
LEGEND / LEYENDA 4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.
TRACKER NCLAVE 2Vx29 MODULES

CONNECTOR
CONECTOR

CONNECTION BOX

CABLE PV ZZ-F
CABLE PV ZZ-F
Project:
CABLE PV ZZ-F LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
CABLE PV ZZ-F

1 STRING: 29 SERIAL MODULES Subject:


NAIAD PROJECTS
2 STRING: 29 SERIAL MODULES
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia STRING CABLES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR N/S 9/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (8) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

INVERTER AND AC-BOX INSTALLATION DETAIL. SCALE 1/30 U-shaped steel


DETALLE DE INSTALACION DEL INVERSOR Y AC-BOX. ESCALA 1/30 Inverter beam for intallation
INVERTER AND AC-BOX INSTALLATION DETAIL. SCALE 1/30 U-acero galvanizado
U-shaped steel Inverter beam for intallation DETALLE DE INSTALACION DEL INVERSOR Y AC-BOX. ESCALA 1/30 Barra invertida para instalacion
Auxiliar support pole* U-acero galvanizado. Barra invertida para instalacion Auxiliar support pole*
Poste de soporte auxiliar* Poste de soporte auxiliar*
Auxiliar support pole*
0.13 0.13 Auxiliar support pole*

0.60
Poste de soporte auxiliar*
Poste de soporte auxiliar*
0.13

0.60
0.23
Inverted Beam for

0.23
A Installation
Barra invertida para
A

1.00
instalacion

1.00
0.13 0.56 0.50 1.08 0.14

0.67
0.21 1.08 0.21

0.50

0.50

0.67
0.67
Ground level
Nivel del suelo
Ground level
2.40 Nivel del suelo

U-shaped steel
Inverted beam for installation
1.00

U-acero galvanizado
1.50

1.00
Barra invertida para instalacion
U-shaped steel
Inverter beam for intallation

0.60
U-acero galvanizado
Barra invertida para instalacion

0.60
0.23

0.23
B B
0.13 0.56 0.50 1.08 0.14
0.21 1.08 0.21
0.50

0.67
2.40

1.50

0.05
0.05
0.14 2.26 0.14 0.05
0.05 0.14 1.36 0.14
Remark: Available from the rack supplier
Nota: disponible desde el proveedor
Remark: Available from the rack supplier
Nota: disponible desde el proveedor

C C

INVERTER AND AC-BOX INSTALLATION DETAIL. SCALE 1/30


DETALLE DE INSTALACION DEL INVERSOR Y AC-BOX. ESCALA 1/30
U-shaped steel Inverter beam for intallation
Auxiliar support pole* U-acero galvanizado. Barra invertida para instalacion
Poste de soporte auxiliar* Auxiliar support pole*
Quadrate Bolt Clamp
Abrazadera de tornillo cuadrado 0.13 Poste de soporte auxiliar* 0.13
0.60

0.60

AC-BOX DETAIL. SCALE 1/20


DETALLE DE AC-BOX. ESCALA 1/20
0.23

0.56
Inverted Beam for Installation Inverted Beam for 0.52 0.21
Barra invertida para instalacion Installation
Barra invertida para
1.00

instalacion
1.08 0.15
0.50 0.56 0.50
0.67

0.50
0.50

Ground level
0.30

0.70

0.23
Nivel del suelo

D 2.00 2.00 D
U-shaped steel
Inverted beam for installation
1.00

U-acero galvanizado
Barra invertida para instalacion
0.60

IRM OUTLINE DIMENSION DETAIL. SCALE 1/15


DETALLE DE DIMENSIONES DEL CONTORNO IRM. ESCALA 1/15
1.05
0.23

0.02
0.02
0.04
0.14 1.08 0.50 0.56 0.50 1.08 0.14 1.05
NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.
0.50

0.42

0.23
6 2019/12/31 LYNK LYNK
E 0.01
5 2019/12/10 LYNK LYNK E
2.00 2.00 4 2019/11/28 LYNK LYNK
0.02
0.81 Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

0.87
0.97
0.05 0.05
0.14 1.93 1.93 0.14
Project:
Remark: Available from the rack supplier LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
Nota: disponible desde el proveedor
Subject:
NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia INVERTER AND AC-BOXES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR V.SCALES 10/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

STRUCTURE DETAIL. SCALE 1/50


DETALLE DE ESTRUCTURA. ESCALA 1/50
10.70
A A

9
3.9

3.80
0.13
0.4 0.4
2 4
2.00

1.99

1.99
1.00
B B

0.67
0.50

0.50
C C

D D

NOTE: The contractor is responsible for making the necessary changes during the construction and generating the "As-Built" documentation, the preparation of the
Operation and Maintenance Manual of the plant, delivery of detailed work execution schedule and making any missing plan or documentation that is required.

6 2019/12/31 LYNK LYNK


E 5 2019/12/10 LYNK LYNK E
4 2019/11/28 LYNK LYNK
Rev. Date (YYYY/MM/DD) Changes Drawn Eng.

Project:
LIRIO DE CAMPO SOLAR PARK 2,992 Mwp
Subject:
NAIAD PROJECTS
Para ser impreso en formato A2 (594x420mm)
To be printed in A2 size (594x420mm)

Location:

Drawing:
Reference Documents / Documentos de Referencia INVERTER AND AC-BOXES INSTALLATION DETAILS

757-PV-GEN-DRW-AMET-001
Drawn: Document Status: Scale: Sheet: Date:
757-PV-ELE-REP-AMET-007 CABLE SIZING AND ENERGY LOSSES CALCULATION LYNKA UR N/S 11/11 2019/12/31
F 757-PV-ELE-DRW-AMET-010
757-PV-ELE-DRW-AMET-011
LV-DC_AC SLD
Overall SLD (DC_LV-AC_MV_OH) Size: Rev: Phase: F
757-PV-CIV-DRW-AMET-015 Layout MV & LV Trench cross sections & details 757-PV-ELE-DRW-AMET-014 (10) A2 06 ENGINEERING FOR CONSTRUCTION

1 2 3 4 5 6 7 8

You might also like