Toshiba - Inverter Air Con
Toshiba - Inverter Air Con
Notice: Toshiba is committed to continuously improving its products to ensure the highest quality and reliability standards, and to for Light Commercial Use
meet local regulations and market requirements. All features and specifications are subject to change without prior notice.
SDIDI200801-ID(1)
Toshiba can help you create a comfortable office while
also caring for the environment.
01 02
SDI Super Digital Inverter
Comfort
DI Digital Inverter
Comfort
DI Digital Inverter
0.0
NEW
Equipped with a newly developed eco-driving
2 HP 3 HP 4 HP 5 HP DC twin rotary compressor
DI / New 4-way cassette A low minimum speed of 10 rps has been achieved.
(EER)
This has further improved the operating efficiency when the
load is low (the minimum in Series 2 was 15 rps).
5.0
Rotor with slit The structure and shape of each
compressor component has been
4.0 optimised. The area of the rotor magnet has
been increased and a slit introduced to the
3.21 3.21 3.22 3.22 design. These improvements have further
3.0 Large-area magnet enhanced efficiency and reduced noise.
2.0
10 rps Operation Verification Test
Building Layout To compare operating efficiency under low load operating conditions,
1.0
field tests were performed where the outdoor temperature was
Office Room approximately 24°C. This is about the same as when the air
conditioning is set to room temperature. Measurements were taken
0.0
that demonstrated that the energy consumption of the new model was
2 HP 3 HP 4 HP 5 HP Air Conditioner Temperature 30% less than the current model (equivalent to the areas enclosed by
the energy consumption curves along the time axis).
Comparison of Measurement Results
(data taken from operating periods with similar outdoor temperatures)
time
Outdoor Temperature (Current Model) Outdoor Temperature (New Model)
Power Consumption (Current Model) Power Consumption (New Model) * Data compiled in Japan, July 2007
05 06
Excellent Energy Efficiency Ratio New SDI Series 4
SDI / New 4-way cassette New Models with Enhanced Energy Efficiency (RAV-SP1104AT-E, -SP1404AT-E)
(EER) Has excellent efficiency, not only under rated EER conditions, but also during
5.0 partial load, which is the larger part of actual operating conditions.
4.52
4.0 3.96 In addition to achieving a top ranking
3.68 during 100% load (rated) conditions...
3.46 100%
4.52
3.0 LOAD For most of the year, the air conditioner (cooler) operates
while the outdoor temperature is less than 30°C.
At this time, the air conditioner load is approximately
2.0 partial 50%, and at this level the EER is significantly greater
5.9
LOAD than during rated conditions. This indicates energy
efficiency in a way that that cannot be expressed using
1.0 EER just the rated energy consumption rate.
0.0
NEW
Equipped with a newly developed eco-driving
2 HP 3 HP 4 HP 5 HP DC twin rotary compressor
DI / New 4-way cassette A low minimum speed of 10 rps has been achieved.
(EER)
This has further improved the operating efficiency when the
load is low (the minimum in Series 2 was 15 rps).
5.0
Rotor with slit The structure and shape of each
compressor component has been
4.0 optimised. The area of the rotor magnet has
been increased and a slit introduced to the
3.21 3.21 3.22 3.22 design. These improvements have further
3.0 Large-area magnet enhanced efficiency and reduced noise.
2.0
10 rps Operation Verification Test
Building Layout To compare operating efficiency under low load operating conditions,
1.0
field tests were performed where the outdoor temperature was
Office Room approximately 24°C. This is about the same as when the air
conditioning is set to room temperature. Measurements were taken
0.0
that demonstrated that the energy consumption of the new model was
2 HP 3 HP 4 HP 5 HP Air Conditioner Temperature 30% less than the current model (equivalent to the areas enclosed by
the energy consumption curves along the time axis).
Comparison of Measurement Results
(data taken from operating periods with similar outdoor temperatures)
time
Outdoor Temperature (Current Model) Outdoor Temperature (New Model)
Power Consumption (Current Model) Power Consumption (New Model) * Data compiled in Japan, July 2007
05 06
Line up Available Indoor Units
SDI
NEW NEW
series
RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E
High-wall 4-way
RAV-SM562KRT-E RAV-SM802KRT-E Cassette Duct
Type
Type Type
Ceiling High-wall
Type Type
2HP 3HP 4HP 5HP
DI
series
RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E
High-wall
RAV-SM562KRT-E RAV-SM802KRT-E
Type
07 08
Line up Available Indoor Units
SDI
NEW NEW
series
RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E
High-wall 4-way
RAV-SM562KRT-E RAV-SM802KRT-E Cassette Duct
Type
Type Type
Ceiling High-wall
Type Type
2HP 3HP 4HP 5HP
DI
series
RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E
High-wall
RAV-SM562KRT-E RAV-SM802KRT-E
Type
07 08
SDI Twin SDI
1. This compact unit (575x575) fits perfectly into ceilings and matches Heating capacity kW 5.6 11.2
Heating capacity, min-max kW 2.2-7.0 2.4-13.0
standard architectural modules, without the need to cut ceiling tiles.
Power input, heating kW 1.54 2.67
2. The compact & stylish panel design is ideal for fashionable COP W/W 3.64 4.19
restaurants, shops and offices. Energy efficiency class, heating A A
Power supply V-ph-Hz 220/240-1-50 220/240-1-50
3. The flaps fold tightly against the ceiling when operation stops so that
the ceiling is affected only slightly even if air-conditioning is installed. DI Twin DI
Outdoor unit RAV-SM563AT-E RAV-SM1103AT-E
Indoor unit RAV-SM562MUT-E RAV-SM562MUT-E
Designed for simple & easy installation Cooling capacity, min-max kW 1.5-5.6 3.0-11.2
RAV-SM562MUT-E Power input, cooling kW 1.61 3.52
and maintenance EER W/W 3.11 2.84
Energy efficiency class, cooling B C
Panel 1. The slim design is only 268 mm in height even when an electrical Annual energy consumption kWh 805 1760
Heating capacity kW 5.6 11.2
RBC-UM11PG(W)-E box is located inside the unit. Heating capacity, min-max kW 1.5-6.3 3.0-13.0
2. Easy access to electrical box is achieved by simply removing the Power input, heating kW 1.61 3.14
suction grill. COP W/W 3.48 3.57
Energy efficiency class, heating B B
The ceiling type offers easy installation and maintenance, since the
Power supply V-ph-Hz 220/240-1-50 220/240-1-50
electrical box is located inside the unit.
Indoor unit RAV-SM562MUT-E
3. Easy installation can also be achieved using the panel adjust pocket.
Air Flow m3/h 798
Use the “gadjust pocket” function for fine adjustments after installation. Sound pressure level (H-M-L) dB(A) 43/34
4. The drain up height is 850 mm. Correspondence is possible even if Sound power level (H-M-L) dB(A) 58/49
Dimensions (HxWxD) mm 268×575×575
installation conditions are severe.
Weight kg 17
5. Available for ceilings up to 3.5 m. Panel model name RBC-UM11PG(W)-E
6. The drain-checking hole makes it possible to check the drain pan Panel dimensions (HxWxD) mm 27×700×700
Panel weight kg 3
through the side case.
SDI
Outdoor unit RAV-SP562AT-E
Air Flow m3/h 3420
3.5 m Sound pressure level, heating/cooling dB(A) 47/46
Sound power level, heating/cooling dB(A) 64/63
Dimensions (HxWxD) mm 795×900×320
Weight kg 55
Drain-checking hole Available up to Compressor type DC Twin Rotary
Refrigerant type R410A
Pipe connections Gas/Liquid mm 12.7/6.4
Comfort Operativity Installation Pipe length, min m 5
Pipe length, max m 50
Inverter Long-life Filter Filter Sign Cooler Compatible with an Outdoor
Allows step-less regulation of the air- Built-in long-life filter makes maintenance Automatic displays on the remote Temperature of -15°C Pipe length, precharge m 20
conditioner’s power, which reduces energy easier. controller say when to perform Stable cooler operation is possible when
Maximum height difference m 30
consumption and improves comfort. maintenance for the indoor unit filter. the outdoor temperature is as low as -15°C.
Operating range, cooling °C -15–43
Operating range, heating °C -15–15
Auto-turn Louvres Hot Start Limit Timer Built-in Drain Pump
Air outlet grilles move automatically to fill When using the heater for preheating or Uses a 168-hour timer with three modes The built-in drain pump makes draining
every corner of the room with warm or defrosting, stops the indoor fan to prevent —“ON timer”, “OFF timer” and “Repeat easier. (In the ceiling cassette type, it is DI
cool air. cold air from being blown into the room. OFF timer”. built in to the main unit.) Outdoor unit RAV-SM563AT-E
Air Flow m3/h 2400
Automatic Air Volume Control Automatic Cooling/Heating Sound pressure level, heating/cooling dB(A) 48/46
Depending on the difference between the Automatically switches between cooling Sound power level, heating/cooling dB(A) 65/63
room temperature and the set temperature, and heating mode.
switches automatically between High, Low Dimensions (HxWxD) mm 550×780×290
and Very Low. Weight kg 38
Compressor type DC Twin Rotary
Dry
Gradually dehumidifies the room to create Refrigerant type R410A
even greater comfort. Pipe connections Gas/Liquid mm 12.7/6.4
Pipe length, min m 5
Pipe length, max m 30
Pipe length, precharge m 20
Maximum height difference m 30
Operating range, cooling °C -15–43
Operating range, heating °C -15–15
09 10
SDI Twin SDI
1. This compact unit (575x575) fits perfectly into ceilings and matches Heating capacity kW 5.6 11.2
Heating capacity, min-max kW 2.2-7.0 2.4-13.0
standard architectural modules, without the need to cut ceiling tiles.
Power input, heating kW 1.54 2.67
2. The compact & stylish panel design is ideal for fashionable COP W/W 3.64 4.19
restaurants, shops and offices. Energy efficiency class, heating A A
Power supply V-ph-Hz 220/240-1-50 220/240-1-50
3. The flaps fold tightly against the ceiling when operation stops so that
the ceiling is affected only slightly even if air-conditioning is installed. DI Twin DI
Outdoor unit RAV-SM563AT-E RAV-SM1103AT-E
Indoor unit RAV-SM562MUT-E RAV-SM562MUT-E
Designed for simple & easy installation Cooling capacity, min-max kW 1.5-5.6 3.0-11.2
RAV-SM562MUT-E Power input, cooling kW 1.61 3.52
and maintenance EER W/W 3.11 2.84
Energy efficiency class, cooling B C
Panel 1. The slim design is only 268 mm in height even when an electrical Annual energy consumption kWh 805 1760
Heating capacity kW 5.6 11.2
RBC-UM11PG(W)-E box is located inside the unit. Heating capacity, min-max kW 1.5-6.3 3.0-13.0
2. Easy access to electrical box is achieved by simply removing the Power input, heating kW 1.61 3.14
suction grill. COP W/W 3.48 3.57
Energy efficiency class, heating B B
The ceiling type offers easy installation and maintenance, since the
Power supply V-ph-Hz 220/240-1-50 220/240-1-50
electrical box is located inside the unit.
Indoor unit RAV-SM562MUT-E
3. Easy installation can also be achieved using the panel adjust pocket.
Air Flow m3/h 798
Use the “gadjust pocket” function for fine adjustments after installation. Sound pressure level (H-M-L) dB(A) 43/34
4. The drain up height is 850 mm. Correspondence is possible even if Sound power level (H-M-L) dB(A) 58/49
Dimensions (HxWxD) mm 268×575×575
installation conditions are severe.
Weight kg 17
5. Available for ceilings up to 3.5 m. Panel model name RBC-UM11PG(W)-E
6. The drain-checking hole makes it possible to check the drain pan Panel dimensions (HxWxD) mm 27×700×700
Panel weight kg 3
through the side case.
SDI
Outdoor unit RAV-SP562AT-E
Air Flow m3/h 3420
3.5 m Sound pressure level, heating/cooling dB(A) 47/46
Sound power level, heating/cooling dB(A) 64/63
Dimensions (HxWxD) mm 795×900×320
Weight kg 55
Drain-checking hole Available up to Compressor type DC Twin Rotary
Refrigerant type R410A
Pipe connections Gas/Liquid mm 12.7/6.4
Comfort Operativity Installation Pipe length, min m 5
Pipe length, max m 50
Inverter Long-life Filter Filter Sign Cooler Compatible with an Outdoor
Allows step-less regulation of the air- Built-in long-life filter makes maintenance Automatic displays on the remote Temperature of -15°C Pipe length, precharge m 20
conditioner’s power, which reduces energy easier. controller say when to perform Stable cooler operation is possible when
Maximum height difference m 30
consumption and improves comfort. maintenance for the indoor unit filter. the outdoor temperature is as low as -15°C.
Operating range, cooling °C -15–43
Operating range, heating °C -15–15
Auto-turn Louvres Hot Start Limit Timer Built-in Drain Pump
Air outlet grilles move automatically to fill When using the heater for preheating or Uses a 168-hour timer with three modes The built-in drain pump makes draining
every corner of the room with warm or defrosting, stops the indoor fan to prevent —“ON timer”, “OFF timer” and “Repeat easier. (In the ceiling cassette type, it is DI
cool air. cold air from being blown into the room. OFF timer”. built in to the main unit.) Outdoor unit RAV-SM563AT-E
Air Flow m3/h 2400
Automatic Air Volume Control Automatic Cooling/Heating Sound pressure level, heating/cooling dB(A) 48/46
Depending on the difference between the Automatically switches between cooling Sound power level, heating/cooling dB(A) 65/63
room temperature and the set temperature, and heating mode.
switches automatically between High, Low Dimensions (HxWxD) mm 550×780×290
and Very Low. Weight kg 38
Compressor type DC Twin Rotary
Dry
Gradually dehumidifies the room to create Refrigerant type R410A
even greater comfort. Pipe connections Gas/Liquid mm 12.7/6.4
Pipe length, min m 5
Pipe length, max m 30
Pipe length, precharge m 20
Maximum height difference m 30
Operating range, cooling °C -15–43
Operating range, heating °C -15–15
09 10
SDI Twin SDI
Models 6,300 mm
DI Twin DI
Outdoor unit RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E RAV-SM1103AT-E RAV-SM1403AT-E
RAV-SM564UT-E Indoor unit RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM564UT-E RAV-SM804UT-E
4,500 mm Cooling capacity kW 5.3 6.7 10.0 12.0 10.0 12.5
RAV-SM804UT-E
Cooling capacity, min-max kW 1.5-5.6 1.5-8.0 3.0-11.2 3.0-13.2 3.0-11.2 3.0-13.2
RAV-SM1104UT-E Power input, cooling kW 1.65 2.09 3.11 3.74 3.11 4.09
RAV-SM1404UT-E Vertical face EER W/W 3.21 3.21 3.22 3.21 3.22 3.06
Energy efficiency class, cooling A A A A A B
Annual energy consumption kWh 825 1045 1555 1870 1555 2045
Mode : cooling
Panels Louvre position : horizontal 23 28 Heating capacity kW 5.6 8.0 11.2 14.0 11.2 14.0
Fan speed : Hi (°C) Heating capacity, min-max kW 1.5-6.3 1.5-9.0 3.0-13.0 3.0-16.0 3.0-13.0 3.0-16.0
RBC-U31PG(W)-E Power input, heating kW 1.44 2.21 2.93 3.80 2.93 4.00
RBC-U31PGS(W)-E Individual Louvre Control COP
Energy efficiency class, heating
W/W 3.89
A
3.62
A
3.82
A
3.68
A
3.82
A
3.50
B
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
The angles of each of the four louvres can be set individually
⇒ Enables airflow to be chosen according to user preferences. Indoor unit RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E
Air Flow m3/h 1050 1230 2010 2100
Three louvre swing patterns Sound pressure level (H-M-L) dB(A) 32-29-28 35-31-28 43-38-33 44-38-34
Sound power level (H-M-L) dB(A) 47-44-43 50-46-43 58-53-48 59-53-49
(1) Standard swing (2) Diagonally (3) Turn-around
RBC-U31PG(W)-E RBC-U31PGS(W)-E opposite swing swing Dimensions (HxWxD) mm 256×840×840 256×840×840 319×840×840 319×840×840
Weight kg 20 20 24 24
Panel model name RBC-U31PG(W)-E RBC-U31PG(W)-E RBC-U31PG(W)-E RBC-U31PG(W)-E
11 12
SDI Twin SDI
Models 6,300 mm
DI Twin DI
Outdoor unit RAV-SM563AT-E RAV-SM803AT-E RAV-SM1103AT-E RAV-SM1403AT-E RAV-SM1103AT-E RAV-SM1403AT-E
RAV-SM564UT-E Indoor unit RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E RAV-SM564UT-E RAV-SM804UT-E
4,500 mm Cooling capacity kW 5.3 6.7 10.0 12.0 10.0 12.5
RAV-SM804UT-E
Cooling capacity, min-max kW 1.5-5.6 1.5-8.0 3.0-11.2 3.0-13.2 3.0-11.2 3.0-13.2
RAV-SM1104UT-E Power input, cooling kW 1.65 2.09 3.11 3.74 3.11 4.09
RAV-SM1404UT-E Vertical face EER W/W 3.21 3.21 3.22 3.21 3.22 3.06
Energy efficiency class, cooling A A A A A B
Annual energy consumption kWh 825 1045 1555 1870 1555 2045
Mode : cooling
Panels Louvre position : horizontal 23 28 Heating capacity kW 5.6 8.0 11.2 14.0 11.2 14.0
Fan speed : Hi (°C) Heating capacity, min-max kW 1.5-6.3 1.5-9.0 3.0-13.0 3.0-16.0 3.0-13.0 3.0-16.0
RBC-U31PG(W)-E Power input, heating kW 1.44 2.21 2.93 3.80 2.93 4.00
RBC-U31PGS(W)-E Individual Louvre Control COP
Energy efficiency class, heating
W/W 3.89
A
3.62
A
3.82
A
3.68
A
3.82
A
3.50
B
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
The angles of each of the four louvres can be set individually
⇒ Enables airflow to be chosen according to user preferences. Indoor unit RAV-SM564UT-E RAV-SM804UT-E RAV-SM1104UT-E RAV-SM1404UT-E
Air Flow m3/h 1050 1230 2010 2100
Three louvre swing patterns Sound pressure level (H-M-L) dB(A) 32-29-28 35-31-28 43-38-33 44-38-34
Sound power level (H-M-L) dB(A) 47-44-43 50-46-43 58-53-48 59-53-49
(1) Standard swing (2) Diagonally (3) Turn-around
RBC-U31PG(W)-E RBC-U31PGS(W)-E opposite swing swing Dimensions (HxWxD) mm 256×840×840 256×840×840 319×840×840 319×840×840
Weight kg 20 20 24 24
Panel model name RBC-U31PG(W)-E RBC-U31PG(W)-E RBC-U31PG(W)-E RBC-U31PG(W)-E
11 12
SDI Twin SDI
Versatile and Clever Outdoor unit RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E RAV-SP1104AT-E RAV-SP1404AT-E
RAV-SM1102BT-E Power input, cooling kW 1.78 2.53 3.56 4.42 3.56 4.42
EER W/W 2.81 2.81 2.81 2.83 2.81 2.83
RAV-SM1402BT-E
Energy efficiency class, cooling C C C C C C
Annual energy consumption kWh 890 1265 1780 2210 1780 2210
Heating capacity kW 5.6 8.0 11.2 14.0 11.2 14.0
Heating capacity, min-max kW 1.5-6.3 1.5-9.0 3.0-12.5 3.0-16.0 3.0-12.5 3.0-16.0
Polygonal rooms Narrow rooms Rooms with fixtures Power input, heating kW 1.71 2.41 3.14 4.03 3.14 4.03
and obstacles COP W/W 3.27 3.32 3.57 3.47 3.57 3.47
Energy efficiency class, heating C C B B B B
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
High static pressure
Indoor unit RAV-SM562BT-E RAV-SM802BT-E RAV-SM1102BT-E RAV-SM1402BT-E
External static pressure can be raised as high as 98 Pa, so that all Air Flow m3/h 780 1140 1620 1980
areas of the room can be reached for even temperature distribution, no Sound pressure level (H-M-L) dB(A) 40-37-33 40-37-34 42-39-36 44-41-38
Sound power level (H-M-L) dB(A) 55-52-48 55-52-49 57-54-51 59-56-53
matter how complex the layout.
Dimensions (HxWxD) mm 320×700×800 320×1000×800 320×1350×800 320×1350×800
Weight kg 30 39 54 54
13 14
SDI Twin SDI
Versatile and Clever Outdoor unit RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E RAV-SP1104AT-E RAV-SP1404AT-E
RAV-SM1102BT-E Power input, cooling kW 1.78 2.53 3.56 4.42 3.56 4.42
EER W/W 2.81 2.81 2.81 2.83 2.81 2.83
RAV-SM1402BT-E
Energy efficiency class, cooling C C C C C C
Annual energy consumption kWh 890 1265 1780 2210 1780 2210
Heating capacity kW 5.6 8.0 11.2 14.0 11.2 14.0
Heating capacity, min-max kW 1.5-6.3 1.5-9.0 3.0-12.5 3.0-16.0 3.0-12.5 3.0-16.0
Polygonal rooms Narrow rooms Rooms with fixtures Power input, heating kW 1.71 2.41 3.14 4.03 3.14 4.03
and obstacles COP W/W 3.27 3.32 3.57 3.47 3.57 3.47
Energy efficiency class, heating C C B B B B
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
High static pressure
Indoor unit RAV-SM562BT-E RAV-SM802BT-E RAV-SM1102BT-E RAV-SM1402BT-E
External static pressure can be raised as high as 98 Pa, so that all Air Flow m3/h 780 1140 1620 1980
areas of the room can be reached for even temperature distribution, no Sound pressure level (H-M-L) dB(A) 40-37-33 40-37-34 42-39-36 44-41-38
Sound power level (H-M-L) dB(A) 55-52-48 55-52-49 57-54-51 59-56-53
matter how complex the layout.
Dimensions (HxWxD) mm 320×700×800 320×1000×800 320×1350×800 320×1350×800
Weight kg 30 39 54 54
13 14
SDI Twin SDI
Quiet and Comfortable Outdoor unit RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E RAV-SP1104AT-E RAV-SP1404AT-E
controller kit swings between 4 swings between 4 Heating capacity, min-max kW 1.5-6.3 1.5-9.0 3.0-12.5 3.0-16.0 3.0-12.5 3.0-16.0
the top three 5 all five positions. 5 Power input, heating kW 1.64 2.47 3.20 4.14 3.20 4.14
RBC-AX22CE2 positions. COP W/W 3.41 3.24 3.50 3.38 3.50 3.38
Energy efficiency class, heating B C B C B C
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
Inverter Hot Start Cooler Compatible with an Outdoor Dimensions (HxWxD) mm 795×900×320 795×900×320 1340×900×320 1340×900×320
Filter Sign
Allows step-less regulation of the air- When using the heater for preheating or Automatic displays on the remote Temperature of -15°C Weight kg 55 62 93 93
conditioner’s power, which reduces energy defrosting, stops the indoor fan to prevent controller say when to perform Stable cooler operation is possible when
consumption and improves comfort. cold air from being blown into the room. maintenance for the indoor unit filter. the outdoor temperature is as low as -15°C. Compressor type DC Twin Rotary DC Twin Rotary DC Twin Rotary DC Twin Rotary
Refrigerant type R410A R410A R410A R410A
Pipe connections Gas/Liquid mm 12.7/6.4 15.9/9.5 15.9/9.5 15.9/9.5
Auto-turn Louvres Automatic Cooling/Heating Limit Timer Built-in Drain Pump
Air outlet grilles move automatically to fill Automatically switches between cooling Uses a 168-hour timer with three modes The built-in drain pump makes draining Pipe length, min m 5 5 3 3
every corner of the room with warm or and heating mode. —“ON timer”, “OFF timer” and “Repeat easier. (In the ceiling cassette type, it is
cool air. OFF timer”. built in to the main unit.) Pipe length, max m 50 50 75 75
15 16
SDI Twin SDI
Quiet and Comfortable Outdoor unit RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E RAV-SP1104AT-E RAV-SP1404AT-E
controller kit swings between 4 swings between 4 Heating capacity, min-max kW 1.5-6.3 1.5-9.0 3.0-12.5 3.0-16.0 3.0-12.5 3.0-16.0
the top three 5 all five positions. 5 Power input, heating kW 1.64 2.47 3.20 4.14 3.20 4.14
RBC-AX22CE2 positions. COP W/W 3.41 3.24 3.50 3.38 3.50 3.38
Energy efficiency class, heating B C B C B C
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
Inverter Hot Start Cooler Compatible with an Outdoor Dimensions (HxWxD) mm 795×900×320 795×900×320 1340×900×320 1340×900×320
Filter Sign
Allows step-less regulation of the air- When using the heater for preheating or Automatic displays on the remote Temperature of -15°C Weight kg 55 62 93 93
conditioner’s power, which reduces energy defrosting, stops the indoor fan to prevent controller say when to perform Stable cooler operation is possible when
consumption and improves comfort. cold air from being blown into the room. maintenance for the indoor unit filter. the outdoor temperature is as low as -15°C. Compressor type DC Twin Rotary DC Twin Rotary DC Twin Rotary DC Twin Rotary
Refrigerant type R410A R410A R410A R410A
Pipe connections Gas/Liquid mm 12.7/6.4 15.9/9.5 15.9/9.5 15.9/9.5
Auto-turn Louvres Automatic Cooling/Heating Limit Timer Built-in Drain Pump
Air outlet grilles move automatically to fill Automatically switches between cooling Uses a 168-hour timer with three modes The built-in drain pump makes draining Pipe length, min m 5 5 3 3
every corner of the room with warm or and heating mode. —“ON timer”, “OFF timer” and “Repeat easier. (In the ceiling cassette type, it is
cool air. OFF timer”. built in to the main unit.) Pipe length, max m 50 50 75 75
15 16
SDI Twin SDI
Outdoor unit RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E
With its attractive, slim-line design, this unit is best suited for restaurants Heating capacity, min-max kW 2.2-7.0 2.2-9.5 2.4-13.0 2.4-16.5
Power input, heating kW 1.55 2.40 2.80 3.83
and other applications where elegance is required. The filtration system
COP W/W 3.61 3.33 4.00 3.66
further improves the indoor air quality benefits of this high-wall unit. Energy efficiency class, heating A C A A
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
A wireless controller is included. Power input, heating kW 1.70 2.67 3.14 4.24
COP W/W 3.29 3.00 3.57 3.30
A TCC Link remote control is optional. Energy efficiency class, heating C D B C
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
Inverter Hot Start On/Off Timer Cooler Compatible with an Outdoor Dimensions (HxWxD) mm 298×998×221 298×998×221
Allows step-less regulation of the air- When using the heater for preheating or The operation start and stop times can be Temperature of -15°C Weight kg 12 12
conditioner’s power, which reduces energy defrosting, stops the indoor fan to prevent set with a digital clock. Stable cooler operation is possible when
consumption and improves comfort. cold air from being blown into the room. the outdoor temperature is as low as -15°C.
SDI
Outdoor unit RAV-SP562AT-E RAV-SP802AT-E
Auto-turn Louvres Automatic Cooling/Heating
Air outlet grilles move automatically to fill Automatically switches between cooling Air Flow m3/h 3420 3420
every corner of the room with warm or and heating mode. Sound pressure level, heating/cooling dB(A) 47/46 49/47
cool air.
Sound power level, heating/cooling dB(A) 64/63 66/64
Dimensions (HxWxD) mm 795×900×320 795×900×320
Automatic Air Volume Control Dry
Depending on the difference between the Gradually dehumidifies the room to create Weight kg 55 62
room temperature and the set temperature, even greater comfort. Compressor type DC Twin Rotary DC Twin Rotary
switches automatically between High, Low
and Very Low. Refrigerant type R410A R410A
Pipe connections Gas/Liquid mm 12.7/6.4 15.9/9.5
Pipe length, min m 5 5
Pipe length, max m 50 50
Pipe length, precharge m 20 30
Maximum height difference m 30 30
Operating range, cooling °C -15–43 -15–43
Operating range, heating °C -15–15 -15–15
DI
Outdoor unit RAV-SM563AT-E RAV-SM803AT-E
Air Flow m3/h 2400 2700
Sound pressure level, heating/cooling dB(A) 48/46 50/48
Sound power level, heating/cooling dB(A) 65/63 67/65
Dimensions (HxWxD) mm 550×780×290 550×780×290
Weight kg 38 42
Compressor type DC Twin Rotary DC Twin Rotary
Refrigerant type R410A R410A
Pipe connections Gas/Liquid mm 12.7/6.4 15.9/9.5
Pipe length, min m 5 5
Pipe length, max m 30 30
Pipe length, precharge m 20 20
Maximum height difference m 30 30
Operating range, cooling °C -15–43 -15–43
Operating range, heating °C -15–15 -15–15
17 18
SDI Twin SDI
Outdoor unit RAV-SP562AT-E RAV-SP802AT-E RAV-SP1104AT-E RAV-SP1404AT-E
With its attractive, slim-line design, this unit is best suited for restaurants Heating capacity, min-max kW 2.2-7.0 2.2-9.5 2.4-13.0 2.4-16.5
Power input, heating kW 1.55 2.40 2.80 3.83
and other applications where elegance is required. The filtration system
COP W/W 3.61 3.33 4.00 3.66
further improves the indoor air quality benefits of this high-wall unit. Energy efficiency class, heating A C A A
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
A wireless controller is included. Power input, heating kW 1.70 2.67 3.14 4.24
COP W/W 3.29 3.00 3.57 3.30
A TCC Link remote control is optional. Energy efficiency class, heating C D B C
Power supply V-ph-Hz 220/240-1-50 220/240-1-50 220/240-1-50 220/240-1-50
Inverter Hot Start On/Off Timer Cooler Compatible with an Outdoor Dimensions (HxWxD) mm 298×998×221 298×998×221
Allows step-less regulation of the air- When using the heater for preheating or The operation start and stop times can be Temperature of -15°C Weight kg 12 12
conditioner’s power, which reduces energy defrosting, stops the indoor fan to prevent set with a digital clock. Stable cooler operation is possible when
consumption and improves comfort. cold air from being blown into the room. the outdoor temperature is as low as -15°C.
SDI
Outdoor unit RAV-SP562AT-E RAV-SP802AT-E
Auto-turn Louvres Automatic Cooling/Heating
Air outlet grilles move automatically to fill Automatically switches between cooling Air Flow m3/h 3420 3420
every corner of the room with warm or and heating mode. Sound pressure level, heating/cooling dB(A) 47/46 49/47
cool air.
Sound power level, heating/cooling dB(A) 64/63 66/64
Dimensions (HxWxD) mm 795×900×320 795×900×320
Automatic Air Volume Control Dry
Depending on the difference between the Gradually dehumidifies the room to create Weight kg 55 62
room temperature and the set temperature, even greater comfort. Compressor type DC Twin Rotary DC Twin Rotary
switches automatically between High, Low
and Very Low. Refrigerant type R410A R410A
Pipe connections Gas/Liquid mm 12.7/6.4 15.9/9.5
Pipe length, min m 5 5
Pipe length, max m 50 50
Pipe length, precharge m 20 30
Maximum height difference m 30 30
Operating range, cooling °C -15–43 -15–43
Operating range, heating °C -15–15 -15–15
DI
Outdoor unit RAV-SM563AT-E RAV-SM803AT-E
Air Flow m3/h 2400 2700
Sound pressure level, heating/cooling dB(A) 48/46 50/48
Sound power level, heating/cooling dB(A) 65/63 67/65
Dimensions (HxWxD) mm 550×780×290 550×780×290
Weight kg 38 42
Compressor type DC Twin Rotary DC Twin Rotary
Refrigerant type R410A R410A
Pipe connections Gas/Liquid mm 12.7/6.4 15.9/9.5
Pipe length, min m 5 5
Pipe length, max m 30 30
Pipe length, precharge m 20 20
Maximum height difference m 30 30
Operating range, cooling °C -15–43 -15–43
Operating range, heating °C -15–15 -15–15
17 18
Remote Controllers
Toshiba Digital Inverters & Super Digital Inverters are operated
with an easy-to-use remote controller.
Wired remote controller Simple wired remote controller
Appearance
Appearance
Combinations
Wired Wireless
RBC-AMT32E RBC-AS21E2 RBC-AX31U(W)-E RBC-AX22CE2 TCB-AX21E2
19 20
Remote Controllers
Toshiba Digital Inverters & Super Digital Inverters are operated
with an easy-to-use remote controller.
Wired remote controller Simple wired remote controller
Appearance
Appearance
Combinations
Wired Wireless
RBC-AMT32E RBC-AS21E2 RBC-AX31U(W)-E RBC-AX22CE2 TCB-AX21E2
19 20
Indoor units Unit: mm Outdoor units Unit: mm
61
32
28
54 B leg part 2-dia.11x14 U-shape cut-out
15 or more
780 Hanging bolt pitch
15 or more
.5
57
600 90
38 (for dia.8–10 anchor bolt)
7
2-dia.20x88 drain long hole
18
1000 or more 1000 or more 11 108 125
60
30
R15 54
Refrigerant pipe connecting port
64
5
15
(Gas side)
(Anchor bolt
1000 or more
269
(dia.6 hole
323
Bottom face
long hole
320
306
290
of ceiling
2-dia.6 hole Refrigerant pipe connecting port
pitch)
pitch)
30
R5
(Liquid side)
.5
Knockout for fresh
Detailed B leg part 8-dia.6 hole (for fixing outdoor unit)
air intake dia.150 Z ° 416.5
45 860 to 910 Ceiling open dimension
20
A leg part
690±20 Hanging bolt pitch
2-dia.6 hole 2-dia.11x14 long hole
For branch duct knockout square hole
Z view 950 Panel external dimension
(for dia.8–10 anchor bolt)
Hanging bolt M10 or 150 (diam.) (Also located on the back)
483 257
W3/8 local arrange
21
196.5 480 163.5 Drain discharge port 241.5 72 106.5 Refrigerant pipe connecting 69.5 147 108 157 79
R15
6
port (Gas side)
77 105 74 *(137)
223.5 256.5 263 157
*( ): 110–140 type
R5
384 105 351 337.5 105 397.5 Refrigerant pipe connecting 38
30 101 120 35
.5
21
port (Liquid side)
(183) 54
*(319)
256
*
189
172
129
132
145
112
300 or less Detailed A leg part
550
483
449
25
31 143
44
129
16.5 30 22
Ceiling panel (Sold separately)
Stand-up 850 or less
661 or less*
137
of ceiling For branch duct knockout square hole 150 (diam.) port
93
54
32 500 71 342
35
52
Drain-up standing-up size 780
827.5 or less
square hole dia.150 Knockout Drain hole (dia.20x88) Mounting bolt hole
17.5
300
Stand-up
dia.162 207 (for drain) (2-dia.12x17 U-shape cut-out)
29 90
850 or less
Bottom face of ceiling 175 191 20
Stand-up
Indoor unit
17.5
235 105 235 Knockout for flesh 149 Drain hole (dia.25)
40
Electric
Air inlet
21
575 unit external dimension air intake dia.100
parts box 29 64 Detailed B leg part
B leg part
(Anchor bolt
70
700 Panel external dimension
52 (47)
595 to 660 ceiling open dimension
200
Bottom face
43
40
575 unit external dimension
long hole
Mounting bolt hole
64 142
365
525 hanging bolt pitch
of ceiling
inlet
Air
Knock out
39
47
39
40
pitch)
Drain-up standing-up size Check port (2-dia.12x17 long hole)
17.5
( 450) (for drain)
40
A leg
21
17.5
Space required for installation 60 Air outlet part Detailed A leg part
368.5
26 36 (43) 43
320.5
331.5
150
15 or more
1000 or more
15 or more
1000 or more 1000 or more 95 95
600
MMU-AP0071MH
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
MMU-AP0181MH
Model name
314 270
Refrigerant pipe connecting port
101
220.5
268
190.5
(Gas side)
139.5
145.5
134
63
55
250
Wiring connection port 120
Bottom face of ceiling Knockout for
21 (Liquid side)
27
lower piping 86 7
565
158 142 Ceiling panel 150 or more
534
For branch duct knockout
795
Air inlet
square hole dia.150 B
7
C B 46
C
Air inlet
Z view
58
264
25
D
E
90
80
Duct
165
154
60 67
F-dia.200 75 800 300 or more
A ±7.5 Hanging bolt pitch Hanging bolt 4-M10 41 700 Hanging bolt pitch 59 (mm) Air outlet
300
60
60
Z 27 58 B C
89
local arrange 50 638 dia.125 knockout hole (backside) 150 or more
B Capacity class A B C 500 or more
Refrigerant pipe
498 (for fresh air intake) 254 60 27 F G
C1 C1 252 56 type 766 700 280 161
393 SDI: 80 type
41
connecting port 96
(Gas side)
80 type 1066 1000 290 518 307 400
50 131
174
Refrigerant pipe
connecting port
(Liquid side)
SDI / DI
Drain pipe connecting port
Long life filter RAV-SP1104AT-E∼RAV-SP1404AT-E Name 56–140 type
(Inner dia.32, VP25) Mounting bolt hole B Power supply wiring hole dia.38 knockout hole
dia.26 wiring connection port 5-drain hole (dia.20x88)
(dia.12x17 U-shape cut-out) C Piping drawing port
380 12
200 60 SDI
17.5
Drain hole (dia.25)
Air inlet
Ceiling High-wall
40
b leg part 56 type 80 type
Detailed b leg part
Z D 269
118 128
Air inlet
264
170
34
46
Upper piping extake port *
E 282
365
Mounting bolt hole
54
48
Power supply cable intake port * Piping extake port *
210
75
128 Remote controller 216 (dia.12x17 long hole)
Drain port VP20
84 piping intake port * 167
(Inner dia.62, hose supplied)
50
40
Air outlet
74
17.5
* : Knockout hole 383 70 39 Detailed a leg part
114
170
130
53
70
150 600 96
216 (Gas pipe) 141
(Hanging
position)
Refrigerant pipe (Gas side) Power supply Remote controller Refrigerant pipe connecting port
534
581
146
262 intake port * cable intake port * 53 or more 53 or more
Refrigerant pipe (Liquid side) 51 50 (Gas side)
7
84
90
32
92
145
171
50
655
1340
121
74
B Piping hole on the Air intake port dia.92 * Drain left piping Piping port from bottom sides *
wall (dia.100 hole) 75 56 998
(Duct sold separately) extake port *
763.5
Wireless sensor
mounting section Z view B
B
534
581
605
613
40
40
C C C
Space required for installation and servicing
95
360
24
Hanging bolt Ceiling
95
95
155
490
surface
85
Within 50
70
55
540
500 or
55
55
Refrigerant pipe connecting Refrigerant pipe connecting Knockout for 18 80
94
(mm) more more
(Front side to be port (Gas side) port (Liquid side) 60 178 178 178
Z 80 18 lower piping 83 7 12 64
Capacity class A B
positioned horizontally) 151
7
56 type 855 910 68 518 135
80 type 1125 1180 400
327
120 to 140 type 1540 1595 Z view
65
21 22
Indoor units Unit: mm Outdoor units Unit: mm
61
32
28
54 B leg part 2-dia.11x14 U-shape cut-out
15 or more
780 Hanging bolt pitch
15 or more
.5
57
600 90
38 (for dia.8–10 anchor bolt)
7
2-dia.20x88 drain long hole
18
1000 or more 1000 or more 11 108 125
60
30
R15 54
Refrigerant pipe connecting port
64
5
15
(Gas side)
(Anchor bolt
1000 or more
269
(dia.6 hole
323
Bottom face
long hole
320
306
290
of ceiling
2-dia.6 hole Refrigerant pipe connecting port
pitch)
pitch)
30
R5
(Liquid side)
.5
Knockout for fresh
Detailed B leg part 8-dia.6 hole (for fixing outdoor unit)
air intake dia.150 Z ° 416.5
45 860 to 910 Ceiling open dimension
20
A leg part
690±20 Hanging bolt pitch
2-dia.6 hole 2-dia.11x14 long hole
For branch duct knockout square hole
Z view 950 Panel external dimension
(for dia.8–10 anchor bolt)
Hanging bolt M10 or 150 (diam.) (Also located on the back)
483 257
W3/8 local arrange
21
196.5 480 163.5 Drain discharge port 241.5 72 106.5 Refrigerant pipe connecting 69.5 147 108 157 79
R15
6
port (Gas side)
77 105 74 *(137)
223.5 256.5 263 157
*( ): 110–140 type
R5
384 105 351 337.5 105 397.5 Refrigerant pipe connecting 38
30 101 120 35
.5
21
port (Liquid side)
(183) 54
*(319)
256
*
189
172
129
132
145
112
300 or less Detailed A leg part
550
483
449
25
31 143
44
129
16.5 30 22
Ceiling panel (Sold separately)
Stand-up 850 or less
661 or less*
137
of ceiling For branch duct knockout square hole 150 (diam.) port
93
54
32 500 71 342
35
52
Drain-up standing-up size 780
827.5 or less
square hole dia.150 Knockout Drain hole (dia.20x88) Mounting bolt hole
17.5
300
Stand-up
dia.162 207 (for drain) (2-dia.12x17 U-shape cut-out)
29 90
850 or less
Bottom face of ceiling 175 191 20
Stand-up
Indoor unit
17.5
235 105 235 Knockout for flesh 149 Drain hole (dia.25)
40
Electric
Air inlet
21
575 unit external dimension air intake dia.100
parts box 29 64 Detailed B leg part
B leg part
(Anchor bolt
70
700 Panel external dimension
52 (47)
595 to 660 ceiling open dimension
200
Bottom face
43
40
575 unit external dimension
long hole
Mounting bolt hole
64 142
365
525 hanging bolt pitch
of ceiling
inlet
Air
Knock out
39
47
39
40
pitch)
Drain-up standing-up size Check port (2-dia.12x17 long hole)
17.5
( 450) (for drain)
40
A leg
21
17.5
Space required for installation 60 Air outlet part Detailed A leg part
368.5
26 36 (43) 43
320.5
331.5
150
15 or more
1000 or more
15 or more
1000 or more 1000 or more 95 95
600
MMU-AP0071MH
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
MMU-AP0181MH
Model name
314 270
Refrigerant pipe connecting port
101
220.5
268
190.5
(Gas side)
139.5
145.5
134
63
55
250
Wiring connection port 120
Bottom face of ceiling Knockout for
21 (Liquid side)
27
lower piping 86 7
565
158 142 Ceiling panel 150 or more
534
For branch duct knockout
795
Air inlet
square hole dia.150 B
7
C B 46
C
Air inlet
Z view
58
264
25
D
E
90
80
Duct
165
154
60 67
F-dia.200 75 800 300 or more
A ±7.5 Hanging bolt pitch Hanging bolt 4-M10 41 700 Hanging bolt pitch 59 (mm) Air outlet
300
60
60
Z 27 58 B C
89
local arrange 50 638 dia.125 knockout hole (backside) 150 or more
B Capacity class A B C 500 or more
Refrigerant pipe
498 (for fresh air intake) 254 60 27 F G
C1 C1 252 56 type 766 700 280 161
393 SDI: 80 type
41
connecting port 96
(Gas side)
80 type 1066 1000 290 518 307 400
50 131
174
Refrigerant pipe
connecting port
(Liquid side)
SDI / DI
Drain pipe connecting port
Long life filter RAV-SP1104AT-E∼RAV-SP1404AT-E Name 56–140 type
(Inner dia.32, VP25) Mounting bolt hole B Power supply wiring hole dia.38 knockout hole
dia.26 wiring connection port 5-drain hole (dia.20x88)
(dia.12x17 U-shape cut-out) C Piping drawing port
380 12
200 60 SDI
17.5
Drain hole (dia.25)
Air inlet
Ceiling High-wall
40
b leg part 56 type 80 type
Detailed b leg part
Z D 269
118 128
Air inlet
264
170
34
46
Upper piping extake port *
E 282
365
Mounting bolt hole
54
48
Power supply cable intake port * Piping extake port *
210
75
128 Remote controller 216 (dia.12x17 long hole)
Drain port VP20
84 piping intake port * 167
(Inner dia.62, hose supplied)
50
40
Air outlet
74
17.5
* : Knockout hole 383 70 39 Detailed a leg part
114
170
130
53
70
150 600 96
216 (Gas pipe) 141
(Hanging
position)
Refrigerant pipe (Gas side) Power supply Remote controller Refrigerant pipe connecting port
534
581
146
262 intake port * cable intake port * 53 or more 53 or more
Refrigerant pipe (Liquid side) 51 50 (Gas side)
7
84
90
32
92
145
171
50
655
1340
121
74
B Piping hole on the Air intake port dia.92 * Drain left piping Piping port from bottom sides *
wall (dia.100 hole) 75 56 998
(Duct sold separately) extake port *
763.5
Wireless sensor
mounting section Z view B
B
534
581
605
613
40
40
C C C
Space required for installation and servicing
95
360
24
Hanging bolt Ceiling
95
95
155
490
surface
85
Within 50
70
55
540
500 or
55
55
Refrigerant pipe connecting Refrigerant pipe connecting Knockout for 18 80
94
(mm) more more
(Front side to be port (Gas side) port (Liquid side) 60 178 178 178
Z 80 18 lower piping 83 7 12 64
Capacity class A B
positioned horizontally) 151
7
56 type 855 910 68 518 135
80 type 1125 1180 400
327
120 to 140 type 1540 1595 Z view
65
21 22
Inverter Air Conditioning
Notice: Toshiba is committed to continuously improving its products to ensure the highest quality and reliability standards, and to for Light Commercial Use
meet local regulations and market requirements. All features and specifications are subject to change without prior notice.
SDIDI200801-ID(1)