Testing The Insulation Resistance of Photovolale Panels - IAA = Industial Automation
automatian es
Testing The Insulation Resistance of Photovoltaic
Panels
by Industrial Automation Asia | Sep 5, 2018 | Instrumentation & Measurement
The implementation of solar power systems globally has continued to increase in the
past decade, presenting new opportunities for measuring the insulation resistance of
those systems in the course of their maintenance and management.
By Masao Higuchi, Application Engineer, Field Design Department, Hioki E.E.
Corporation.
The implementation of solar power systems globally has continued to increase in the past
decade, presenting new opportunities for measuring the insulation resistance of those systems
in the course of their maintenance and management. This situation has led to the ongoing
development of maintenance inspection guidelines that govern how insulation resistance
testing is carried out.
19sisi202
Testing The Insulation Resistance of Photovoltaic Panels - WA = Indust Automation
1EC62446-1 is the international standard for PV generation systems, and is divided into three
categories: “Category 1", required for all systems, and “Category 2" and “Additional Tests",
required for larger or more complex systems. Despite the additional time and costs required,
however, in order to obtain optimal performance, “Category 2° and “Additional Tests” are
recommended even for small or simple PV systems.
Within Category 1 testing, insulation resistance testing is required assure electrical safety by
showing sufficient insulation between electricity-conducting components and the PV panel's
frame, or between the PV module and the external environment. Improper insulation can lead
to electric shocks and other hazards.
There are two methods to test insulation resistance, one of which is to short circuit the positive
and negative electrodes of the PV string before measuring the insulation resistance between
the shorting point and earth, The other is to measure the insulation resistance between the
positive electrode and earth, and then between the negative electrode and earth separately
without short-circuiting. Both methods are described in IEC62446-1 standard, so either can be
used. However, for each method, there are several issues to consider.
‘APV module is considered a constant current source, so electrically tis not a problem to short-
circuit the positive and negative electrodes. Once the electrodes are shorted, the insulation
resistance can be measured correctly using general standard insulation resistance testers.
However, careful attention must be paid on how to short-circuit the electrodes, To short the
positive and negative electrodes, a large switch with sufficient integrity to shut down the
discharge voltage and short-circuit current must be used. If a short is performed without using
such a switch, a DC arc may be generated, which may lead to fire and/or electrical shock. As
‘such, be sure to arrange an appropriate switch to short the two electrodes. This method
presents an accurate, but still unsafe way to test for insulation resistance, with the only
alternative when using the short-circuit method is to measure during the night when the PV
panels are offline and not generating any energy.
‘The second method of testing insulation resistance is to test without shorting the electrodes.
With this method, risk of electrical shock will be minimised, but in turn, you risk the possibility of
obtaining incorrect measurement values due to the testing method used by general insulation
ting in the PV module. General
insulation resistance testers are designed to measure an object that has no electric potential
resistance testers. This is caused by the electric potential e
When electric potential is present, the measured value can be higher or lower than the actual
value depending on the measurement conditions.
hitps:wwaasiaontino.com/testing the insulation-esistance-ot-photoveltac-pancls! 219sisi202
hitps:wwaasiaontino.com/testing the insulation-esistance-ot-photoveltac-pancls!
Testing The Insulation Resistance of Photovoltaic Panels - IAA - Industrial Automation
Generated
Current.
Figure 1: Insulation resistance testing without short-crcuiting electrodes with neutral connect
tothe earth faut,
Figure 1 illustrates an insulation resistance test without short-circuiting the electrodes using a
tester that can output negative test voltage. The insulation resistance is tested between the
positive electrode and earth while the negative electrode of the PV module is connected to the
earth fault, The diode circled on the left is the PV module, while the diode not circled is the
bypass diode. Because the negative electrode is connected to the earth fault, when the
insulation resistance tester is connected between the positive electrode and the earth, this in
tum connects the earth fault to the tester,
‘Subsequently, a closed loop is created to flow the current generated by the PV module, and this
current flows to the insulation tester. Since the insulation resistance tester outputs a negative
test voltage, the direction of the measured current and PV generated current will be the same.
The tester will detect a higher current due to the additional current generated by the PV module
and calculate a lower insulation resistance than the actual value, resulting in a false negative.
3sisi202
Testing The Insulation Resistance of Photovoliaic Panels - IAA = Industrial Automation
P NL
Generated,
Current /
irom PV
Measurement
OWL Current from
InsulationTester
Figure 2. Insulation resistance testing without short-circuiting electrodes with positive connect
to the earth faut.
Figure 2 shows a situation opposite of the previous example, where there is an attempt to
measure the insulation resistance of the negative electrode while the positive electrode is
connected to the earth fault. A closed loop to flow the current generated by the PV panel is
‘once again created by the meter and the earth fault resistance, causing the PV-generated
Current to flow to the insulation resistance meter. However, in this case, the directions of the
measured current and PV-generated current are opposite one another, causing some of the
measured current to cancel out. As a result, the calculated insulation resistance is higher than
the actual value through the detection of the lower current, resulting in a false positive. In the
worst case, the insulation resistance can be incorrectly displayed as ‘infinity’, or maximum
resistance, despite the earth fault.
hitps:wwwaasiaontino.com/testing the insulation-esistance-ot-photoveltac-pancls!
49sisi202 Testing The Insulation Resistance of Potovoliic Panels - IAA - Industrial Automation
eo
Measurement
Current from.
IngulationTester
Figure 3. Insulation resistance testing without a closed loop, with positive connected to the
earth fault.
Measurement
Gurrent from
InsulationTester
Figure 4. Insulation resistance testing without a closed loop, with neutral connected to the
earth fault.
Figures 3 and 4 illustrate ways to measure insulation resistance accurately using a general
insulation resistance tester. As you can see, in both examples, there is no closed loop to allow
the flow of current generated by the PV panel. Since the current has no path to flow to the
hitps:wwaasiaontino.com/testing the insulation-esistance-ot-photoveltac-pancls! 59sisi202
Testing The Insulation Resistance of Photovoltaic Panels - WA = Indust Automation
tester, the insulation resistance can be accurately measured even when there is an earth fault.
Naturally, good insulation resistance can also be tested accurately when there is no earth fault
These differences and problems exist because general insulation resistance testers are not,
designed to measure objects containing electric potential. However, PV modules by design are
always charged with electric potential as long as there is sunlight, so this problem has always
been evident; yet, it not addressed in the IEC 62446-1 standard. To resolve those issues, Hioki
has developed an insulation resistance tester thal features a special function for when
performing PV maintenance.
Models IR4053 Insulation Resistance Meter features a PV resistance mode in addition to the,
standard insulation resistance measurement function. By using PV resistance mode, the
insulation resistance can be measured without the effect of the PV-generated current, resutting
in accurate measurement under any system conditions. The IR4053 achieves this by
measuring the voltage and current produced by the PV module as it generates electricity, and
then subtracting those values from the measured current before dividing it by the applied
voltage V, minus the PV-generated voltage, to calculate the resistance.
Measuring the insulation resistance of photovoltaic systems while they are continuing to
generate electricity from the sun pose potential hazards if the short-circuit method is used. On.
the other hand, using the non-short-circuit method stipulated by the IEC 62446-1 standard
leads to inaccurate results due to the additional energy introduced into the measurement
system by the PV panels themselves. The Hioki IR4053 Insulation Resistance Meter provides a
solution by taking into consideration that very energy into the calculation of resistance to deliver
the correct insulation resistance value of PV panels, ensuring safety both during measurement
and handling of the PV panels upon proper testing,
READ MORE INSTRUMENTATION & MEASUREMENT
WANT MORE INSIDER NEWS? SUBSCRIBE TO IAA NOW!
‘CHECK OUT IAA’S CURRENT AND PAST ISSUES: DIGITAL MAGAZINE
(Bent Take the Leap of Faith Learn Electrical Hazards In Industrial
About DDRé to Prepare for DDRS Work Environment
Related Articles:
hitps:wwaasiaontino.com/testing the insulation-esistance-ot-photoveltac-pancls! aessi2021 Testing The Insulation Resistance of Photovolale Panels - IAA = Industial Automation
The Game-Changing _Trungnam Group Launches Smarter Oil And Gas
Technology OfRFID The Largest Solar Farm in Operations Begin With
Vietnam Amid Renewables Quality Data
Drive
Four Ways Machine
Leaming is Powering The
Mobily Revolution
* ARE
YOU 7
Enter your email
Register Now: Create Your Own Industry 4.0 High-End Controller
Ransomware And The Industrial Internet Of Things
‘The Digital Supply Chain
6G: New Generations Of Wireless And The Impact On Measurement
Lubrication Optimisation: Extending Bearing Lifespans
hitps:wwiaasiaontino.com/testing the insulation-esistance-ot-photoveltac-pancls! 19sisi202
Testing The Insulation Resistance of Photovoltaic Panels - IAA = Industrial Automation
Network Resilience In Times Of Crisis,
Post-Coronavirus Supply Chain Recovery
ABOUT IAA
Established since 2001, Industrial Automation Asia (IAA) has emerged as the frontrunner
in it's industry. Our many achievements include being the first BPA audited automation
publication in the region, Backed by a dedicated team of experienced professionals, IAA
is committed to providing quality content for our readership of 33,000 registered
professionals per issue, for both print and online.
FEATURED
INDUSTRY NEWS.
LATEST TECHNOLOGY
ENERGY
SECTOR SPOTLIGHT
SOFTWARE & NETWORKS
PROCESS CONTROL
ISSUES AND INSIGHTS
INSTRUMENTATION & MEASUREMENTS,
PRODUCT HIGHLIGHTS,
EVENTS
MAGAZINE
CONTACT US,
SIGN UP FOR OUR NEWSLETTERFOLLOW OUR SOCIALS!
finve
Enter name
Enter your email