K-SEC 041: Fusing Equipment
K-SEC 041: Fusing Equipment
Electrical Apparatus
2
CONNECTORS/ TABLE 1
Connector/Bracket Options
BRACKETS
The Type L cutout includes a Catalog
Number
tin-plated bronze parallel-groove
5th Digit 6th Digit Cutout Connector/Bracket Description
connector as standard. The parallel-
groove connector fits a conductor P 0 Includes parallel groove connector; deletes crossarm mounting
bracket
range of #8 solid (.128" diameter) to
250 MCM (.575" diameter). Tin P 1 Includes parallel groove connector and NEMA Type B
plated bronze eyebolt and large crossarm mounting bracket
eyebolt connector options are also P 3 Includes parallel groove connector and extended crossarm
available. The eyebolt connector fits mounting bracket
a conductor range of #8 solid (.128" E 0 Includes eyebolt connector; deletes crossarm mounting bracket
diameter) to 2/0 standard (.418" diam-
eter) and the large eyebolt connector E 1 Includes eyebolt connector and NEMA Type B crossarm mounting
bracket
fits a conductor range of #8 solid
(.128" diameter) to 250 MCM (.575" E 3 Includes eyebolt connector and extended crossarm mounting bracket
diameter). L 0 Includes large eyebolt connector; deletes crossarm mounting bracket
The Type L crossarm mounting L 1 Includes large eyebolt connector and NEMA Type B crossarm
includes a heavy-duty NEMA Type mounting bracket
B crossarm mounting bracket to L 3 Includes large eyebolt connector and extended crossarm mounting
withstand the mechanical forces bracket
generated during fault current inter-
ruptions when using an expulsion
fuse link. An extended crossarm
mounting bracket option is also TABLE 2
available. Type L cutouts are also Electrical Ratings
available without crossarm mounting Impulse
brackets. Maximum Withstand Voltage Minimum 60 Hz Minimum 60 Hz
Design (BIL) on 1.2 x 50 1 min. Dry 10 sec Wet
To specify the appropriate connector Rating Microsecond Withstand Value Withstand Value Creepage Distance
and bracket options, simply change kV Wave kV, crest* kV, rms* kV, rms* inches (mm)
the fifth and sixth digits of the catalog 15 110 35 30 8.5 (216)
number as shown in Table 1. (Exam- 27 125 42 36 11 (279)
ple: L4B1E1A will include an eyebolt 27 150 70 60 17 (432)
connector and the NEMA Type B *In accordance with ANSI Standard C37.42.
bracket.) Consult your Cooper
Power Systems representative for
other connector/bracket options. TABLE 3
Type L Cutouts Dimensional Data (refer to Figure 6)
Figure 4.
Parallel-groove connector.
Figure 5.
Eyebolt connector.
3
K-SEC 041
ELECTRICAL RATINGS
5.00" (127 mm) AND DIMENSIONS
Electrical ratings for the Type L
B
cutouts are shown in Table 2. Dimen-
sional data is listed in Table 3. Figure 6
shows an outline drawing of the Type L
cutout.
4.13" (105 mm)
to
5.16" (131 mm)
ORDERING
INFORMATION
To order a complete Type L cutout
with a fuseholder or disconnect blade
choose the appropriate part number
from Tables 4, 5, or 6.
20°
To order an individual fuseholder,
disconnect blade or the cutout mount-
ing frame, refer to Tables 7 or 8.
C A
Figure 6.
Type L cutout assembly.
TABLE 4
15 kV, 110 kV BIL Type L Interchangeable Cutout with Fuseholder or Disconnect Blade
4
K-SEC 041
TABLE 5
27 kV, 125 kV BIL Type L Interchangeable Cutout with Fuseholder or Disconnect Blade
Interrupting Rating Creepage Approximate
Catalog Maximum Design Continuous A-rms Distance Weight
Number* Voltage kV Current A-rms Symmetrical Asymmetrical Inches (mm) lbs. (kg)
L9C1P1A 27 100 5,300 8,000 11.0 (279) 16.7 (7.5)
L9CAP1A** 27 100 8,000 12,000 11.0 (279) 16.8 (7.6)
L9C2P1A 15 200 7,100 10,000 11.0 (279) 17.2 (7.8)
L9C3P1A 27 300 Disconnect† Disconnect† 11.0 (279) 16.2 (7.3)
Notes:
* Standard unit includes tin plated bronze parallel-groove connector and NEMA crossarm mounting bracket. See Table 1 “Connector/Bracket
Options” for optional connectors and brackets.
** These units include an arc shortening rod and must be used with removable buttonhead fuse links.
† 300 A short time current ratings: 12 kA (Asym) momentary, 8 kA (Sym) 15-Cycle.
TABLE 6
27 kV, 150 kV BIL Type L Interchangeable Cutout with Fuseholder or Disconnect Blade
Interrupting Rating Creepage Approximate
Catalog Maximum Design Continuous A-rms Distance Weight
Number* Voltage kV Current A-rms Symmetrical Asymmetrical Inches (mm) lbs. (kg)
L9D1P1A 27 100 5,300 8,000 17.0 (432) 22.5 (10.2)
L9DAP1A** 27 100 8,000 12,000 17.0 (432) 22.6 (10.3)
L9D2P1A 15 200 7,100 10,000 17.0 (432) 23.0 (10.4)
L9D3P1A 27 300 Disconnect† Disconnect† 17.0 (432) 22.0 (10.0)
Notes:
* Standard unit includes tin plated bronze parallel-groove connector and NEMA crossarm mounting bracket. See Table 1 “Connector/Bracket
Options” for optional connectors and brackets.
** These units include an arc shortening rod and must be used with removable buttonhead fuse links.
† 300 A short time current ratings: 12 kA (Asym) momentary, 8 kA (Sym) 15-Cycle.
TABLE 7
Fuseholders and Disconnect Blades Only
Approximate
Fuseholder Approximate
Catalog Maximum Design Continuous Interrupting Rating Length Weight
Number Voltage kV Current A-rms A-rms Asym Inches (mm) lbs. (kg)
For 15 kV, 110 kV BIL Cutouts
LDB100A 15 100 10,000 11.32 (288) 1.9 (.86)
LDBA00A† 15 100 16,000 11.32 (288) 2.0 (.91)
LDB200A 7.8 200 12,000 11.32 (288) 2.4 (1.1)
LDB300A 15 300 Disconnect** 11.32 (288) 1.4 (.64)
For 27 kV, 125 kV BIL Cutouts
LDC100A 27 100 8,000 14.74 (374) 2.1 (.95)
LDCA00A† 27 100 12,000 14.74 (374) 2.2 (1.0)
LDC200A 15 200 10,000 14.74 (374) 2.6 (1.2)
LDC300A 27 300 Disconnect** 14.74 (374) 1.6 (.73)
For 27 kV, 150 kV BIL Cutouts
LDC100A 27 100 8,000 14.74 (374) 2.1 (.95)
LDCA00A† 27 100 12,000 14.74 (374) 2.2 (1.0)
LDC200A 15 200 10,000 14.74 (374) 2.6 (1.2)
LDC300A 27 300 Disconnect** 14.74 (374) 1.6 (.73)
Notes:
† These fuseholders include an arc shortening rod and must be used with removable buttonhead fuse links.
** 300 A short time current ratings: 12 kA (Asym) momentary, 8 kA (Sym) 15-Cycle.
TABLE 8
Type L Open Cutout Mounting Frames Only (Without Fuseholder or Disconnect Blade)
Dimensions Inches (mm) Porcelain Approximate
Catalog Voltage Creepage Weight lbs. (kg)
Number* Rating kV BIL kV B C Inches (mm) (Frame only)
L4B0P1A 15 110 13.50 (343) 8.15 (207) 8.5 (216) 12.6 (5.7)
L9C0P1A 27 125 14.09 (358) 10.12 (257) 11.0 (279) 14.6 (6.6)
L9D0P1A 27 150 14.29 (362) 10.12 (257) 17.0 (432) 20.4 (9.3)
Notes:
* Standard unit includes tin plated bronze parallel-groove connector and crossarm mounting bracket. See Table 1 “Connector/Bracket Options” for optional connectors
and brackets.
5
Open Distribution Cutout - Type L
ADDITIONAL
INFORMATION
Refer to the following reference
literature for more information:
■ K-SEC 041S Type L Open
Distribution Cutout Installation
Instructions
■ 235-26 Surge Arrester/Type L
Fuse Cutout Combination
Catalog
■ CP-9618 Type L Open
Distribution Cutout Certified
Test Report
■ K-SEC 100 Edison® Links
Catalog
Contact your Cooper Power Systems
representative for further information.