Outdoor Intergrated Power Supply System for BTS includes
2 sets: Equiptment & Power Supply Cabinet and Battery | J
Cabinet.
* Equiptment & Power Supply Cabinet: Able to hot-plug 04 |]
Rectifiers HE and 08 Solar Chargers, transfer automatically |
between grid power and generator power (ATS). System is |
monitored remotely via RS485/USB/ Ethernet port. System is
cooled by Heat Exchanger and have smoke sensor and
opening-door status sensor.
* Battery Cabinet: Able to set 02 battery strings (2Vx-
300Ah) or 03 battery strings (12Vx150Ah). Cabinet is
cooled by mini DC Air-conditioner.
VIETTEL GROUP.
MI COMMUNICATION COMPANYHMA TECHNICAL SPECIFICAT CN
AC Input from Grid/Generator
AC Output for Light
Socket
DC Inputs from Solar panels
DC Outputs for Priority/Non
Priority Load
Circuit Breaker for Battery
Monitor and Control module
pso2
Digital nput/Digital Output
Control Genset
‘Communication
Input Voltage range
DC Output Voltage Range
Rated output Power
Max output current
Peak Efficency
Input Voltage range
DC Output Voltage Range
Rated Output Power
Max output current
Peak Eificency
Technology
Operating temperature range
Operating humidity range
Electromagnetic compatibility
EMC
Safety Standard
Equiptment & Power Supply
Cabinet
Battery Cabinet
VIETTEL GROUP.
M1 COMMUNICATION COMPANY
02 CB, 63A, 3P+N, IEC 60898/EC 60947-2
01 MCB, 1 cyc 1A
OlSocket : 16A/220Vac
08 CB, 32A tai 220VDC, IEC 6089BNEC 60947-2
03 CB 32, 03 CB I0A for Priority Load
03 CB 32A, 03 CB 16A for Non-priority Load
06 CB 125A
LCD Graphic 128x64
Able to set parameters by 04 buttons on module
‘or by computer at site or from remote Server.
16 DY 16 DO
Based on DC Low and Block time.
LAN, RS485,Modbus RTU,
RS485 for fuel sensor.
80-295V AC; frequency 45 to 65 Hz
-42 to -58V DC (Adjustable)
3100W @ Ude = 48V DC
704
= 9654
58-150VDC.
~42 to -5BV DC (Adjustable)
3000W @ Ude = 48V DC
65A
97.8%
Switching technology intergrated Maximum
Power Point Tracking Algorithm (MPPT).
=10 to 65°C
5 to 95x (non-condense)
EN 55022, EN 61000-4-2, EN 61000-4-3,
EN 61000-4-6
TCVN 7326-1/
QCYN 22:20 10/8TTTT
WxDxH: 924 x 750 x 1986 mm (include support rack),
outdoor class B environment, IP55.
WxDxH 1123 x 1004 x1800 mm (include support rack),
‘outdoor class B environment, IPSS.