Professional Documents
Culture Documents
Power Harmonics
Basic troubleshooting using
multimeters and current clamps
ously affected by voltage neutral conductor. In systems SINGLE FREE CAPTURE MIN MAX TRIGGER
RECURRENT RUN 10 20 DIV on A at 50%
harmonics. with many single-phase non-
Power correction capaci- linear loads, the neutral current Figure 3A. Single phase non-linear load
tors can form a resonant cir- can actually exceed the phase current waveform
cuit with the inductive parts current. The danger here is ex-
of a power distribution sys- cessive overheating because A 100mV DC B 1V OFF
2ms/DIV SINGLE Trig:A! -1 DIV
tem. If the resonant fre- there is no circuit breaker in the
quency is near that of the neutral conductor to limit the
harmonic voltage, the re- current as there are in the
sultant harmonic current phase conductors.
can increase substantially, Excessive current in the
overloading the capacitors neutral conductor can also
and blowing the capacitor cause higher than normal volt- a!
Classification of harmonics
Each harmonic has a name, frequency and sequence. The sequence refers to
phasor rotation with respect to the fundamental (F), i.e., in an induction motor,
a positive sequence harmonic would generate a magnetic field that rotated in
the same direction as the fundamental. A negative sequence harmonic would
rotate in the reverse direction. The first nine harmonics along with their effects
are listed below:
The following are some sugges- Derating transformers that involves several straightfor-
tions of ways to address some ward measurements that you
typical harmonics problems. One way to protect a trans- can get with commonly avail-
Before taking any such mea- former from harmonics is to limit able test equipment. It appears
sures you should call a power the amount of load placed on it. to give reasonable results for
quality expert to analyze the This is called “derating” the 208/120 Y receptacle transform-
problem and design a plan transformer. The most rigorous ers that supply low frequency
tailored to your specific derating method is described in odd harmonics (3rd, 5th, 7th)
situation. ANSI/IEEE standard C57.110- commonly generated by com-
1986. This method is somewhat puters and office machines
In overloaded neutrals impractical because it requires operating from single phase
extensive loss data from the branch circuits.
In a 3-phase 4-wire system, transformer manufacturer plus a The test equipment you use
the 60 Hz portion of the neutral complete harmonic spectrum of must be capable of taking both
current can be minimized by the load current. the true-rms phase current, and
balancing the loads in each The Computer & Business the instantaneous peak phase
phase. The triplen harmonic Equipment Manufacturers Asso- current for each phase of the
neutral current can be reduced ciation (CBEMA), recently rec- secondary.
by adding harmonic filters at ommended a second method
the load. If neither of these
solutions are practical, you can
pull in extra neutrals—ideally
one neutral for each phase. Or Derating factor
you can install an oversized
To determine the derating factor for the transformer, take the peak and
neutral shared by three phase
true-rms current measurements for the three phase conductors. If the
conductors.
phases are not balanced, average the three measurements and plug that
In new construction, under-
value into the following formula:
carpet wiring and modular
office partitions wiring should
HDF = Harmonic Derating Factor
be specified with individual
neutrals and possibly an iso- = (1.414)(true-rms Phase Current)
lated ground separate from the (Instantaneous Peak Phase Current)
safety ground. (Reference FIPS
Pub 94, Guideline on Electrical This formula generates a value between 0 and 1.0, typically
Power for ADP Installations,* between 0.5 and 0.9. If the phase currents are purely sinusoidal
and 1990 NEC Article 250-74 (undistorted) the instantaneous peaks are 1.414 times the
exception No. 4.) true-rms value and the derating factor is 1.0. If that is the case
no derating is required.
*Copies of this publication are for sale
by the National Technical Information However, with harmonics present the transformer rating is the product of
Service, U.S. Dept. of Commerce, the nameplate kVA rating times the HDF.
Springfield, VA 22161. When ordering,
refer to Federal Information Processing kVA derated = (HDF) x (kVA nameplate)
Standards Publication 94 and give title.
For example: 208/120 Y transformer rated at 225 kVA:
Note: National Electrical Code and NEC
are registered trademarks of the Conductor True-rms Instantaneous
National Fire Protection Association. Name Current Amps Peak Current
Load currents were measured
with a Fluke Model 87 and an 01 410A 804A
80i-600 ac current probe to 02 445A 892A
produce the following results: 03 435A 828A
The results indicate that with the level of harmonics present the transformer
should be derated to 72.3% of its rating to prevent overheating.
Average
True-rms responding Instantaneous
Conductor multimeter multimeter peak current
name (amps) (amps) (amps)
25 7.8 3.75V
Neutral 27 9.7 4.00V
conductor Current 29 13.5 8.05V
number (amps)
Table 3. Phase currents and neutral-to-ground voltage for neutral #06
01 5.0
02 11.3
03 5.0
04 13.1
05 12.4
06 15.0*
07 1.8
08 11.7
09 4.5
10 11.8
11 9.6
12 11.5
13 11.3
14 6.7
15 7.0
16 2.3
17 2.6
® 39 POWER METER
® 41B POWER HARMONICS
ANALYZER
100ms AVG H
CAT 600V
600A
76 TRUE RMS MULTIMETER 1000A
k
0 1 2 3 4 5 6 7 8 9 0
40
Hz
0 200 400 600 800 1000 MAX
200 A
REL Hz OFF VH 600 A
1000 A
PEAK MIN MAX
Hz 200
mV
200 V
mA V H
V A 600 V
OFF
V A mV H A ZERO DC / AC
OFF
A 40 PRESS
RANGE 36 CLAMP METER
AUTORANGE, 40 1 SEC
( TOUCH HOLD ) 2 SEC
A mA A COM V
40 V DC
mA
400mA MAX
FUSED TRUE RMS
10A MAX 1000V MAX
FUSED 10A CAT
600V COM
!
600V
FUSED
COM V
33
TRUE RMS CLAMP METER
RECORD MAX
H SMOOTH
AUTO
A RMS
0 1 2 3 40 A
MIN SMOOTH ON
MAX CREST Hz RANGE OFF
Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
U.S.A. (800) 443-5853 or
Fax (425) 356-5116
Europe/M-East (31 40) 2 678 200 or
Fax (31 40) 2 678 222
Canada (905) 890-7600 or
Fax (905) 890-6866
Other countries (425) 356-5500 or
Fax (425) 356-5116
Web access: http://www.fluke.com
©1997 Fluke Corporation. All rights reserved.
Windows is a registered trademark of Microsoft
Corporation.
Printed in U.S.A. 8/97 B0221UEN Rev F
Printed on recycled paper.