You are on page 1of 12

In Tune with

Power Harmonics
Basic troubleshooting using
multimeters and current clamps

New technology introduces


Application Note
new challenges
What’s all the noise Harmonics are the by-products of
about harmonics? modern electronics. They are es- A 100V DC PROBE*10 B 1V OFF
5ms/DIV SINGLE Trig:A! -1 DIV
pecially prevalent wherever there
A mystery is occurring in are large numbers of personal
today’s office buildings computers, adjustable speed
and manufacturing plants. drives and other types of equip-
Transformers supplying ment that draw current in short A
seemingly average loads pulses.
are overheating. Neutral This equipment is designed to a!
conductors in balanced draw current only during a con-
circuits are overheating trolled portion of the incoming
from excessive loads. voltage waveform. While this dra- @ZOOM
Circuit breakers are matically improves efficiency, it
tripping for no apparent SCOPE:
causes harmonics in the load cur-
reason. SINGLE FREE CAPTURE MIN MAX TRIGGER
rent. And that causes overheated RECURRENT RUN 10 20 DIV on A at 50%
Yet the standard transformers and neutrals, and
troubleshooting proce- tripped circuit breakers. Figure 1. Near sine wave
dures show everything to If you were to listen to an ordi-
be normal. So what’s the nary 60 cycle power line, you’d A 100mV DC B 1V OFF
problem? hear a monotone hum. When har-
2ms/DIV SINGLE Trig:A! -1 DIV
In one word—harmonics. monics are present, you hear a
different tune, rich with high
notes.
The problem is even more evi-
dent when you look at the wave
form. A normal 60 cycle power a!

line voltage appears on the oscil- A


loscope as a near sine wave
(Figure 1) When harmonics are @ZOOM
present, the waveform is distorted
(Figure 2A and 2B). These waves SCOPE:
SINGLE FREE CAPTURE MIN MAX TRIGGER
are described as non-sinusoidal. RECURRENT RUN 10 20 DIV on A at 50%
The voltage and current wave- Figure 2A. Distorted current waveform
forms are no longer simply
related—hence the term
“non-linear.” A 200V DC PROBE*10 B 1V OFF
2ms/DIV SINGLE Trig:A!

Getting to the root


of the problem
Finding the problem is relatively
easy once you know what to look a!
for and where to look. Harmonics A
symptoms are usually anything
but subtle. This application note
will give you some basic pointers @ZOOM
on how to find harmonics and
some suggestions of ways to ad- SCOPE:
SINGLE FREE CAPTURE MIN MAX TRIGGER
dress the problem. However, you RECURRENT RUN 10 20 DIV on A at 50%

should call a consultant to ana- Figure 2B. Distorted voltage waveform


lyze your operation and design a
plan for your specific situation.
In Tune with Power Harmonics Fluke Corporation 1
Work Safely Sources of Harmonics

Defining the problem


Work safely Harmonics are currents or volt-
ages with frequencies that are
The high voltages and currents • Read and understand all of integer multiples of the funda-
present in electrical power sys- the applicable manuals be- mental power frequency. For
tems can cause serious injury or fore using the application in- example if the fundamental fre-
death by electrocution. Conse- formation in this application quency is 60 Hz, then the sec-
quently, testing and modifica- note. Take special note of all ond harmonic is 120 Hz, the
tion of electrical systems should safety precautions and warn- third is 180 Hz, etc.
be performed by only trained, ings in the instruction Harmonics are created by
experienced electricians who manuals. non-linear loads that draw cur-
have knowledge of electrical This application note is a gen- rent in abrupt pulses rather
systems in general and the eral guide to understanding than in a smooth sinusoidal
equipment under test. harmonics. It is not intended to manner. These pulses cause dis-
Fluke cannot anticipate all substitute for the services of a torted current wave shapes
possible precautions that you professional electrical systems which in turn cause harmonic
must take when performing the consultant. Before you take any currents to flow back into other
measurements described in this measures to diagnose or ad- parts of the power system.
application note. At a minimum, dress your potential harmonics
however, you should: problems you should have your The inside story
• Use appropriate safety equip- operation thoroughly analyzed
This phenomenon is especially
ment such as safety glasses, by a professional.
insulating gloves, insulating This application note is not prevalent with equipment that
mats, etc. intended as a tutorial on electri- has diode-capacitor input
• Be sure that all power has cal theory. It assumes basic power supplies, i.e., personal
been turned off, locked out, electrical and electronic knowl- computers, printers and medical
and tagged in any situation edge on the part of the reader. test equipment.
where you will be in direct Electrically what happens is
contact with circuit compo- the incoming ac voltage is diode
nents, and be certain that the rectified and is then used to
power can’t be turned on by charge a large capacitor. After a
anyone but you. few cycles, the capacitor is
charged to the peak voltage of
the sine wave (e.g. 170V for a
120V ac line). The electronic
equipment then draws current
from this high dc voltage to
power the rest of the circuit.
The equipment can draw the
current down to a regulated
lower limit. Typically, before
reaching that limit, the capacitor
is recharged to the peak in the
next half cycle of the sine wave.
This process is repeated over
and over. The capacitor basi-
cally draws a pulse of current
only during the peak of the
wave. During the rest of the
wave, when the voltage is be-
low the capacitor residual, the
capacitor draws no current.
The diode/capacitor power
supplies found in office equip-
ment are typically single phase
non-linear loads. In industrial
plants the most common causes
of harmonic currents are three-
phase non-linear loads which
include electronic motor drives,
and uninterruptible power sup-
plies (UPS).

2 Fluke Corporation In Tune with Power Harmonics


Voltage harmonics Effects of Harmonic Currents
The power line itself can be
an indirect source of voltage
harmonics. Office buildings and Circuit breakers
The harmonic current plants—harmonics
drawn by non-linear loads Common thermal-magnetic cir-
acts in an Ohm’s law rela- are on the rise cuit breakers use a bi-metallic
tionship with the source im- Symptoms of harmonics usually trip mechanism which responds
pedance of the supplying show up in the power distribu- to the heating effect of the cir-
transformer to produce volt- tion equipment that supports cuit current. It is designed to
age harmonics. Source im- the non-linear loads. There are respond to the true-rms value of
pedance includes the sup- two basic types of non-linear the current waveform and
plying transformer and loads—single-phase and three- therefore will trip when it gets
branch circuit components. phase. Single-phase non-linear too hot. This type of breaker has
For example, a 10A har- loads are prevalent in offices, a better chance of protecting
monic current being drawn while three-phase loads are against harmonic current
from a source impedance of widespread in industrial plants. overloads.
0.1Ω will generate a Each component of the A peak sensing electronic trip
harmonic voltage of 1.0V. power distribution system circuit breaker responds to the
Any loads sharing a manifests the effects of harmon- peak of current waveform. As a
transformer or a branch cir- ics a little differently. Yet all are result it won’t always respond
cuit with a heavy harmonic subject to damage and ineffi- properly to harmonic currents.
load can be affected by the cient performance. Since the peak of the harmonic
voltage harmonics gener- current is usually higher than
ated. Neutral conductors normal this type of circuit
The personal computer breaker may trip prematurely at
can be affected by voltage In a 3-phase, 4-wire system, a low current. If the peak is
harmonics. The performance neutral conductors can be lower than normal the breaker
of the diode/capacitor severely affected by non-linear may fail to trip when it should.
power supply is critically loads connected to the 120V
dependent on the magni- branch circuits. Under normal
A 5mV DC B 1V OFF
tude of the peak voltage. conditions for a balanced linear 5ms/DIV Trig:A! -1 DIV

Voltage harmonics can load, the fundamental 60 Hz


cause “flat topping” of the portion of the phase currents
voltage waveform lowering will cancel in the neutral
the peak voltage (see Figure conductor.
2B). In severe cases, the In a 4-wire system with
computer may reset due to single-phase non-linear loads, a! A
insufficient peak voltage. certain odd-numbered harmon-
In the industrial environ- ics called triplens—odd multi-
ment, the induction motor ples of the third harmonic: 3rd,
@ZOOM
and power factor correction 9th, 15th etc.— do not cancel,
capacitors can also be seri- but rather add together in the SCOPE:

ously affected by voltage neutral conductor. In systems SINGLE FREE CAPTURE MIN MAX TRIGGER
RECURRENT RUN 10 20 DIV on A at 50%
harmonics. with many single-phase non-
Power correction capaci- linear loads, the neutral current Figure 3A. Single phase non-linear load
tors can form a resonant cir- can actually exceed the phase current waveform

cuit with the inductive parts current. The danger here is ex-
of a power distribution sys- cessive overheating because A 100mV DC B 1V OFF
2ms/DIV SINGLE Trig:A! -1 DIV
tem. If the resonant fre- there is no circuit breaker in the
quency is near that of the neutral conductor to limit the
harmonic voltage, the re- current as there are in the
sultant harmonic current phase conductors.
can increase substantially, Excessive current in the
overloading the capacitors neutral conductor can also
and blowing the capacitor cause higher than normal volt- a!

fuses. Fortunately, the ca- age drops between the neutral


A
pacitor failure detunes the conductor and ground at the
circuit and the resonance 120V outlet. @ZOOM
disappears.
SCOPE:
SINGLE FREE CAPTURE MIN MAX TRIGGER
RECURRENT RUN 10 20 DIV on A at 50%

Figure 3B. Three phase non-linear load


current waveform

In Tune with Power Harmonics Fluke Corporation 3


Effects of Harmonic Currents

Bus bars and Telecommunications Another transformer problem


connecting lugs results from core loss and cop-
Telecommunications systems per loss. Transformers are nor-
often give you the first clue to a
Neutral bus bars and connecting mally rated for a 60 Hz phase
harmonics problem. Telecom-
lugs are sized to carry the full current load only. Higher fre-
value of the rated phase cur- munications cable is commonly quency harmonic currents cause
rent. They can become over- run right next to power cables. increased core loss due to eddy
loaded when the neutral con- To minimize the inductive inter- currents and hysteresis, result-
ference from phase current,
ductors are overloaded with the ing in more heating than would
additional sum of the triplen telecommunications cables are occur at the same 60 Hz current.
harmonics. run closer to the neutral wire. These heating effects demand
Triplens in the neutral conduc- that transformers be derated for
Electrical panels tor commonly cause inductive harmonic loads or replaced with
interference which can be specially designed transformers.
Harmonics in electrical panels heard on a phone line. This is
can play a lively tune. Panels often the first indication of a
that are designed to carry 60 Hz harmonics problem and gives Generators
currents can become mechani- you a head start in detecting Standby generators are subject
cally resonant to the magnetic the problem before it causes to the same kind of overheating
fields generated by higher major damage. problems as transformers. Be-
frequency harmonic currents. cause they provide emergency
When this happens, the panel Transformer backup for harmonic producing
vibrates and emits a buzzing loads such as data processing
sound at the harmonic Commercial buildings commonly equipment they are often even
frequencies. have a 208/120 volt transformer more vulnerable. In addition to
in a delta-wye configuration. overheating, certain types of
These transformers commonly harmonics produce distortion at
208/480 Volt Transformer feed receptacles in a commer-
A the zero crossing of the current
cial building. Single phase non- waveform which causes inter-
120V Branch Circuits

B linear loads connected to the ference and instability for the


01 receptacles produce triplen har- generator’s control circuits.
monics which algebraically add
02 Primary Secondary up in the neutral. When this
neutral current reaches the
03 transformer it is reflected into
C
the delta primary winding
where it causes overheating
Neutral and transformer failures.

Classification of harmonics
Each harmonic has a name, frequency and sequence. The sequence refers to
phasor rotation with respect to the fundamental (F), i.e., in an induction motor,
a positive sequence harmonic would generate a magnetic field that rotated in
the same direction as the fundamental. A negative sequence harmonic would
rotate in the reverse direction. The first nine harmonics along with their effects
are listed below:

Name F 2nd* 3rd 4th* 5th 6th* 7th 8th* 9th


Frequency 60 120 180 240 300 360 420 480 540
Sequence + — 0 + — 0 + — 0
*Even harmonics disappear when waves are symmetrical (typical for electrical circuits)

Sequence Rotation Effects (from skin effect, eddy currents, etc.)


Positive Forward Heating of conductors, circuit breakers, etc.

Negative Reverse Heating as above + motor problems


Zero** None Heating, + add in neutral of 3-phase, 4-wire system
**Zero sequence harmonics (odd multiples of the 3rd) are called “Triplens” (3rd, 9th, 15th, 21st, etc.)

4 Fluke Corporation In Tune with Power Harmonics


Finding Harmonics

Survey the situation • Measure the frequency of


the neutral current. 180 Hz
A harmonic survey will give would be a typical reading 5
you a good idea whether or not for a neutral current con- 4
you have a harmonic problem sisting of mostly 3rd 3
True-rms
and where it is located. Here harmonic. 2
are a few guidelines to follow.
4. Sub-Panel Neutral Current 1
1. Load inventory—Make a Check—Survey the sub-pan- 0
walking tour of the facility els that feed harmonic loads. -1
and take a look at the types Measure the current in each -2
Average
of equipment in use. If you branch neutral and compare -3
have a lot of personal com- the measured value to the -4
puters and printers, adjust- rated capacity for the wire
able-speed motors, solid- -5
size used. Check the neutral 0 180 360
state heater controls and busbar and feeder connec-
certain types of fluorescent tions for heating or discolor-
lighting, there’s a good ation. A non-contact infrared
chance that harmonics are In search of harmonics
temperature probe is useful
present. for detecting excessive over- Here’s a simple way to determine
2. Transformer Heat Check— heating on busbars and the extent of harmonic distortion
Locate the transformers connections. caused by single phase non-linear
feeding those non-linear load input circuits:
5. Receptacle Neutral-to-
loads and check for exces- Ground Voltage Check—Neu-
sive heating. Also make sure Make two separate current
tral overloading in receptacle measurements:
the cooling vents are branch circuits can some-
unobstructed. times be detected by measur- 1. Using an average responding
3. Transformer Secondary ing the neutral-to-ground current clamp or meter with a
Current—Use a true-rms voltage at the receptacle. clamp-on, e.g. Fluke 27 and
meter to check transformer Measure the voltage when 80i-600.
currents. the loads are on. Two volts or 2. Using a true-rms current clamp
• Verify that the voltage rat- less is about normal. Higher meter, such as the Fluke 32, 33
ings for the test equipment voltages can indicate trouble or 36 or a true-rms meter with a
are adequate for the trans- depending on the length of clamp-on, e.g. Fluke 87 and
former being tested. the run, quality of connec- 80i-600.
• Measure and record the tions, etc. Measure the fre- Divide the results of the first mea-
transformer secondary quency. 180 Hz would sug- surement by the second measure-
currents in each phase gest a strong presence of ment. This gives you the A/R
and in the neutral (if used). harmonics. 60 Hz would sug- ratio. A ratio of 1.0 would indicate
• Calculate the kVA deliv- gest that the phases are out little or no harmonic distortion.
ered to the load and com- of balance. A ratio of 0.50 would indicate
pare it to the nameplate Pay special attention to under substantial harmonic distortion.
rating. carpet wiring and modular The A/R ratio method is not a
Note: If harmonic currents are office panels with integrated substitute for a harmonic analyzer,
present, the transformer can wiring that uses a neutral but it is a simple practical way to
overheat even if the kVA deliv- shared by three phase conduc- determine whether there’s a prob-
ered is less than the nameplate tors. Because the typical loads lem in single phase branch cir-
rating. in these two areas are computer cuits. Once you know harmonics
• If the transformer second- and office machines they are are present you can use a Fluke
ary is a 4-wire system, often trouble spots for over- Model 39 or Model 41B to deter-
compare the measured loaded neutrals. mine the extent of the problem.
neutral current to the Note: The A/R ratio method is useful for
value predicted from the single phase branch circuit currents only
imbalance in the phase and should not be used on three phase
currents. (The neutral cur- loads.
rent is the vector sum of
the phase currents and
would normally be zero
if the phase currents are
balanced in both ampli-
tude and phase.) If the
neutral current is unex-
pectedly high, triplen har-
monics are likely and the
transformer may need to
be derated.
In Tune with Power Harmonics Fluke Corporation 5
Troubleshooting Tools

Multimeter performance comparison Know your crest factor


average responding vs. true-rms The crest factor of a waveform
is the ratio of the peak value to
Multimeter Measuring Sine Wave Square Wave Distorted Wave the rms value. For a sine wave,
Type Circuit Response* Response* Response* the crest factor is 1.414. A true-
rms meter will have a crest fac-
tor specification. This spec re-
lates to the level of peaking that
Average Rectified can be measured without errors.
Correct 10% High Up to 50% Low
Responding Average x 1.1 A quality true-rms handheld
True-rms RMS Calculating digital multimeter has a crest
converter. factor of 3.0 at full scale. This is
Correct Correct Correct more than adequate for most
Calculates
heating value. power distribution measure-
*Within multimeter’s bandwidth and crest factor specifications
ments. At half scale the crest
factor is double. For example, in
the 400 volt ac range, the Fluke
87 has a crest factor spec of 3.0
True-rms meters when measuring 400V ac, and
give you a headstart a crest factor of 6.0 when mea-
suring 200V ac.
Having the proper tools is cru-
Note: Most true-rms meters cannot be
cial to diagnosing harmonics used for signals below 5% of scale due
problems. The type of equip- to the measurement noise problem. Use
ment you use varies with the a lower range if it is available.
complexity of measurements
you need. Using a true-rms meter with
To determine whether you a “Peak” function—like the Fluke
have a harmonics problem you 87—or a “Crest” function—like
need to measure the true-rms the Fluke 33—the crest factor
value and the instantaneous can be easily calculated. A crest
peak value of the wave shape. factor other than 1.414 indicates
For this you need a true-rms the presence of harmonics. In
clamp meter like the Fluke 32, typical single phase cases,
33 or 36, or a handheld digital the greater the difference
multimeter that makes true-rms from 1.414, the higher the har-
measurements and has a high monic content. For voltage har-
speed (1 ms) peak hold circuit monics, the typical crest factor
such as a Fluke 87. is below 1.414, i.e. a “flat top”
waveform. For single phases
Getting the true picture current harmonics, the typical
crest factor is much above 1.414.
“True-rms” refers to the root- Three phase current waveforms
mean-square, or equivalent often exhibit the “double hump”
heating value of a current or waveform shown in Figure 3B,
voltage wave shape. “True” therefore the crest factor com-
distinguishes the measurement parison method should not be
from those taken by “average applied to three phase load
responding” meters. The vast current.
majority of low cost portable After you’ve determined that
amp clamp meters are average harmonics are present, you can
responding. These instruments make a more in-depth analysis
give correct readings for pure of the situation with a harmonic
sine waves only, and will typi- analyzer such as Fluke models
cally read low when confronted 39 or 41B.
with a distorted current wave-
form. The result is a reading
that can be up to 50% low.
True-rms meters give correct
readings for any wave shape
within the instrument’s crest
factor and bandwidth
specifications.

6 Fluke Corporation In Tune with Power Harmonics


Solving the Problem

The following are some sugges- Derating transformers that involves several straightfor-
tions of ways to address some ward measurements that you
typical harmonics problems. One way to protect a trans- can get with commonly avail-
Before taking any such mea- former from harmonics is to limit able test equipment. It appears
sures you should call a power the amount of load placed on it. to give reasonable results for
quality expert to analyze the This is called “derating” the 208/120 Y receptacle transform-
problem and design a plan transformer. The most rigorous ers that supply low frequency
tailored to your specific derating method is described in odd harmonics (3rd, 5th, 7th)
situation. ANSI/IEEE standard C57.110- commonly generated by com-
1986. This method is somewhat puters and office machines
In overloaded neutrals impractical because it requires operating from single phase
extensive loss data from the branch circuits.
In a 3-phase 4-wire system, transformer manufacturer plus a The test equipment you use
the 60 Hz portion of the neutral complete harmonic spectrum of must be capable of taking both
current can be minimized by the load current. the true-rms phase current, and
balancing the loads in each The Computer & Business the instantaneous peak phase
phase. The triplen harmonic Equipment Manufacturers Asso- current for each phase of the
neutral current can be reduced ciation (CBEMA), recently rec- secondary.
by adding harmonic filters at ommended a second method
the load. If neither of these
solutions are practical, you can
pull in extra neutrals—ideally
one neutral for each phase. Or Derating factor
you can install an oversized
To determine the derating factor for the transformer, take the peak and
neutral shared by three phase
true-rms current measurements for the three phase conductors. If the
conductors.
phases are not balanced, average the three measurements and plug that
In new construction, under-
value into the following formula:
carpet wiring and modular
office partitions wiring should
HDF = Harmonic Derating Factor
be specified with individual
neutrals and possibly an iso- = (1.414)(true-rms Phase Current)
lated ground separate from the (Instantaneous Peak Phase Current)
safety ground. (Reference FIPS
Pub 94, Guideline on Electrical This formula generates a value between 0 and 1.0, typically
Power for ADP Installations,* between 0.5 and 0.9. If the phase currents are purely sinusoidal
and 1990 NEC Article 250-74 (undistorted) the instantaneous peaks are 1.414 times the
exception No. 4.) true-rms value and the derating factor is 1.0. If that is the case
no derating is required.
*Copies of this publication are for sale
by the National Technical Information However, with harmonics present the transformer rating is the product of
Service, U.S. Dept. of Commerce, the nameplate kVA rating times the HDF.
Springfield, VA 22161. When ordering,
refer to Federal Information Processing kVA derated = (HDF) x (kVA nameplate)
Standards Publication 94 and give title.
For example: 208/120 Y transformer rated at 225 kVA:
Note: National Electrical Code and NEC
are registered trademarks of the Conductor True-rms Instantaneous
National Fire Protection Association. Name Current Amps Peak Current
Load currents were measured
with a Fluke Model 87 and an 01 410A 804A
80i-600 ac current probe to 02 445A 892A
produce the following results: 03 435A 828A

I phase avg. = 410 + 445 + 435 = 430A


3

I pk avg. = 804 + 892 + 828 = 841A


3

HDF = (1.414) (430) = 72.3%


841

The results indicate that with the level of harmonics present the transformer
should be derated to 72.3% of its rating to prevent overheating.

In Tune with Power Harmonics Fluke Corporation 7


Case Study

Situation Defining the problem


A modern office building dedi- Transformer—Current measure- The results indicated that,
cated primarily to computer ments (see Table 1) were taken with the level of harmonics
software development con- on the neutral and on each present, the transformer should
tained a large number of per- phase of the transformer sec- be derated to 72.3% of its
sonal computers and other ondary using both a true-rms nameplate rating to prevent
electronic office equipment. multimeter and an average-re- overheating. In this case the
These electronic loads were fed sponding unit. A 600A clamp- transformer should be derated
by a 120/208V transformer on current transformer acces- to 72.3% of its 225 kVA rating,
configured with a delta primary sory was connected to each or derated to 162.7 kVA.
and a wye secondary. The PCs meter to allow them to make The actual load was calcu-
were fairly well distributed high current readings. The cur- lated to be 151.3 kVA. Although
throughout the building, except rent waveshapes are shown in that figure was far less than the
for one large room that con- Figures 4 and 5. nameplate rating, the trans-
tained several machines. The The presence of harmonics former was operating close to
PCs in this room, used exclu- was obvious by comparison of its derated capacity.
sively for testing, were served phase current and neutral cur- Subpanel—Next a subpanel
by several branch circuits. rent measurements. As Table 1 which supplied branch circuits
The transformer and main shows, the neutral current was for the 120V receptacles was
switch gear were located in a substantially higher than any of also examined. The current in
ground floor electrical room. the phase currents, even though each neutral was measured and
Inspection of this room immedi- the phase currents were rela- recorded (see Table 2).
ately revealed two symptoms of tively well balanced. The aver- When a marginal or over-
high harmonic currents: age-responding meter consis- loaded conductor was identi-
• The transformer was gener- tently took readings approxi- fied, the associated phase cur-
ating a substantial amount of mately 20% low on all the rents and the neutral-to-ground
heat. phases. Its neutral current read- voltage at the receptacle were
• The main panel emitted an ings were only 2% low. also measured. When a check of
audible buzzing sound. The The waveforms explain the neutral #6 revealed 15 amperes
sound was not the chatter discrepancy. The phase currents in a conductor rated for 16A, the
commonly associated with a were badly distorted by large phase currents of the circuits
faulty circuit breaker, but amounts of third harmonic cur- (#25, #27, and #29) that
rather a deep resonant buzz rent, while the neutral current shared that neutral were also
that indicated the mechani- was nearly a pure sinewave at measured (Table 3). Note that
cal parts of the panel itself the third harmonic frequency. each of the phase currents of
were vibrating. The phase current readings these three branch circuits was
listed in Table 1 demonstrate substantially less than 15A, and
Ductwork installed directly over clearly why true-rms measure- also the same phase conductors
the transformer to carry off ment capability is required to had significant neutral-to-
some of the excess heat kept accurately determine the value ground voltage drops.
the room temperature within of harmonic currents.
reasonable limits. The next step was to calcu-
late the “harmonic derating fac-
tor” or HDF (Refer to “Derating
Transformer” section on the
previous page.)

Average
True-rms responding Instantaneous
Conductor multimeter multimeter peak current
name (amps) (amps) (amps)

Phase 1 410 328 804


Phase 2 445 346 892
Phase 3 435 355 828
Neutral 548 537 762
Table 1. Current readings at the receptacle transformer secondary

8 Fluke Corporation In Tune with Power Harmonics


B 1V OFF
In the branch circuits which
5ms/DIV SINGLE Trig:A! -1 DIV had high neutral current, the
relationship between the neu-
A
tral and the phase currents was
similar to that of the transformer
secondary. The neutral current
was higher than any of the as-
sociated phase currents. The
a! danger here is that the neutral
conductors could become over-
@ZOOM
loaded and not offer the warn-
ing signs of tripped circuit
SCOPE: breakers.
SINGLE FREE CAPTURE MIN MAX TRIGGER
RECURRENT RUN 10 20 DIV on A at 50%
Recommendations
Figure 4. Phase current
1. Refrain from adding addi-
tional loads to the receptacle
5ms/DIV SINGLE
B 1V OFF
Trig:A! -1 DIV
transformer unless steps are
taken to reduce the level of
harmonics.
2. Pull in extra neutrals to the
A
branch circuits that are
heavily loaded.
3. Monitor the load currents
a! on a regular basis using
true-rms measuring test
@ZOOM
equipment.
SCOPE:
SINGLE FREE CAPTURE MIN MAX TRIGGER
RECURRENT RUN 10 20 DIV on A at 50% Neutral-to-ground
Circuit Phase current voltage drop at
Figure 5. Neutral current
number (amps) receptacle

25 7.8 3.75V
Neutral 27 9.7 4.00V
conductor Current 29 13.5 8.05V
number (amps)
Table 3. Phase currents and neutral-to-ground voltage for neutral #06
01 5.0
02 11.3
03 5.0
04 13.1
05 12.4
06 15.0*
07 1.8
08 11.7
09 4.5
10 11.8
11 9.6
12 11.5
13 11.3
14 6.7
15 7.0
16 2.3
17 2.6

Table 2. Subpanel branch circuit neutral currents

In Tune with Power Harmonics Fluke Corporation 9


Fluke Products

® 39 POWER METER
® 41B POWER HARMONICS
ANALYZER

87 TRUE RMS MULTIMETER

100ms AVG H
CAT 600V
600A
76 TRUE RMS MULTIMETER 1000A
k
0 1 2 3 4 5 6 7 8 9 0
40

Hz
0 200 400 600 800 1000 MAX

MIN MAX RANGE HOLD H

200 A
REL Hz OFF VH 600 A
1000 A
PEAK MIN MAX

Hz 200
mV
200 V
mA V H
V A 600 V

OFF
V A mV H A ZERO DC / AC

OFF

A 40 PRESS
RANGE 36 CLAMP METER
AUTORANGE, 40 1 SEC
( TOUCH HOLD ) 2 SEC
A mA A COM V
40 V DC
mA

400mA MAX
FUSED TRUE RMS
10A MAX 1000V MAX
FUSED 10A CAT
600V COM
!
600V
FUSED

COM V

Fluke 87 Fluke 76 Fluke 39 Fluke 41B Fluke 36


• Volts, ohms, current, • Volts, ohms, • Direct 3Ø/three- • Direct 3Ø/three- • 2000 count digital
frequency, duty resistance phase readouts from phase readouts from display
cycle and diode test • True-rms, simple single- simple single- • 2% of reading,
• Analog/Digital smoothing phase measurements phase measurements basic accuracy for
display • Analog/Digital • True-rms voltage • True-rms voltage ac current
• True-rms, backlit display from 10V to 600V from 10V to 600V • 1.9% of reading,
display, 4 digit • Capacitance from • True-rms current • True-rms current basic accuracy for
mode 99.99 nF to 9999 from 1A to 500A from 1A to 500A dc current
• Auto/manual µF (1000A with (1000A with • One-year warranty
ranging • Frequency of optional probe) optional probe) • Max hold
• Automatic Touch voltage from 1 Hz to • Peak, dc, and crest • Peak, dc, and crest • Manual ranging
Hold® 20 kHz factor factor
• Ohms
• Continuity beeper • Lo ohms range to • Total harmonic • Total harmonic • Sleep mode
• MIN/MAX/AVG 0.01Ω distortion (%THDF distortion (%THDF
• 1 msec peak hold • Continuity beeper and %THDR) and %THDR) • True-rms ac
measurement, crest
for crest factor • Sleep mode • Active power from • Active power from factor ≤3
calculation • Holster/Flex-StandTM 10W to 300 kW 10W to 300 kW
• Holster/Flex-StandTM • 400 hour battery (600 kW with (600 kW with
• 400 hour battery life (alkaline) optional probe) optional probe)
life (alkaline) • CAT III-600V • Apparent power • Apparent power
• 3 year warranty • UL Listed (kVA) (kVA)
• CAT III-1000 • CSA, TÜV, CE, • Total power factor • Total power factor
• U L 3111 Listed (PF) (PF)
• CSA, CE, DVE • Displacement power • Displacement power
factor (DPF) factor (DPF)
• K-factor • K-factor
• Frequency from • Frequency from
6 Hz to100 Hz 6 Hz to100 Hz
(fundamental) (fundamental)
• Harmonics to 31st • Harmonics to 31st
• Phase angle of • Phase angle of
fundamental and fundamental and
Fluke Videos harmonics harmonics
• Waveform and • Waveform and
spectrum displays spectrum displays
Understanding and Managing Harmonics • Record mode – MIN, • Record mode – MIN,
• Length: 30 minutes MAX and AVG MAX and AVG
• Topics covered: • Zoom mode • Zoom mode
• Definition of harmonics • 48-hour battery life • 48-hour battery life
• Causes of harmonics (4 “C” cells) (4 “C” cells)
• Effects of harmonics • Handheld, 1 kg (2 lb) • Handheld, 1 kg (2 lb)
• Diagnosis of harmonics • Surge protection, • Surge protection,
• Selection of test tools 6 kV per IEC 1010-1 6 kV per IEC 1010-1
• Planning for harmonics CAT III-600V CAT III-600V
• Marks – CE, • Marks – CE,
The ABCs of Digital Multimeter Safety CSA NRTL, TÜV/GS CSA NRTL , TÜV/GS
• Length: 20 minutes • Includes 500A • Includes 500A
• Topics covered: current clamp and current clamp and
• Overvoltage categories “Managing Electrical “Managing Electrical
• Proper work procedures and equipment Power Systems” Power Systems”
• What to look for in a meter video
• Memory for eight
complete data sets
• Optically isolated
RS-232 interface
• FlukeView™ PC
software for
Windows® and DOS
included
• New data logging
software now

10 Fluke Corporation In Tune with Power Harmonics


HOLD H

33
TRUE RMS CLAMP METER
RECORD MAX
H SMOOTH
AUTO

A RMS
0 1 2 3 40 A

MIN SMOOTH ON
MAX CREST Hz RANGE OFF

Fluke 33 80i-1000s 80i-500s 80i-600 80i-400 80T-IR Infrared


• Combination • 1 to 1000 ampere • 1 to 500 ampere ac • 1 to 600 ampere ac • 1 to 400 ampere ac Temperature Probe
digital/analog ac clamp-on current clamp-on current clamp-on current clamp-on current • Non-contact
display probe for probe for probe for probe for temperature
• 4000 count digital oscilloscope oscilloscope multimeters multimeters accessory for DMMs
display (current); • Works with Model • Included with • Range: 0°F to 500°F
10,000 count digital 39 or 41B Power Model 39 or 41B or -18°C to 260°C
display (frequency) Meters Power Meters
• True-rms
• AC current 0.3A to
400A
• Frequency
• Display hold
• Crest/instantaneous
peak
• MIN/MAX/AVG
record mode
• Crest factor ≤2.5
• Sleep mode to
preserve battery life
• SmoothingTM
displays a 3 second
running average of
current or
frequency

In Tune with Power Harmonics Fluke Corporation 11


Fluke. Keeping your world
up and running.

Fluke Corporation
PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V.
PO Box 1186, 5602 BD
Eindhoven, The Netherlands
For more information call:
U.S.A. (800) 443-5853 or
Fax (425) 356-5116
Europe/M-East (31 40) 2 678 200 or
Fax (31 40) 2 678 222
Canada (905) 890-7600 or
Fax (905) 890-6866
Other countries (425) 356-5500 or
Fax (425) 356-5116
Web access: http://www.fluke.com
©1997 Fluke Corporation. All rights reserved.
Windows is a registered trademark of Microsoft
Corporation.
Printed in U.S.A. 8/97 B0221UEN Rev F
Printed on recycled paper.

12 Fluke Corporation In Tune with Power Harmonics

You might also like