Professional Documents
Culture Documents
Outboard Motor
Magneto Ignitions
Application Note
Coil
SERIES II MULTIMETER
23
kΩ
Introduction Flywheel
10
OFF
20 30 40
Secondary
V
Primary
300mV
10A V
FUSED
kΩ
could be wrong: The spark to the apart the magneto as follows: Set
Flywheel
10 20 30 40
plug(s) is weak or nonexistent, the the multimeter into the ohms (Ω) OFF
Secondary
V
spark plug heat range is too cold, function. Use the range button to
Primary
300mV
or the engine has been run for long manually select the 40 kΩ range.
periods of time at low speeds (Auto ranging may not work here A A
RANGE
AUTORANGE
PRESS
1 SEC
10A V
fuel/oil mixture. In the case of Now, touch one probe tip to the 300
mA
FUSED
! 100V
750V COM
multi-cylinder engines, if only one engine block and the other to the
plug shows difficulties, the problem metal connector inside the plug
Breaker
is likely to be a weak spark from wire cap. The meter should read Points
the ignition system. the resistance of the coil and HV
In any event, the next step is to wire in series. Good readings will
Condenser
check actual spark plug operation. range from 3 kΩ to 15 kΩ. Higher
If new plugs are available, use readings mean a poor connection, Engine Block
them for the next test. If not, clean which typically occurs either where
Figure 1: HV wire resistance/continuity test
the old ones as follows: using a the HV wire connects to the coil or
sharp object such as the point of a at the other end where the HV wire
safety pin or a straightened fish connects to the spark plug clip Coil
SERIES II MULTIMETER
23
hook, scrape off the deposits on the inside the cap. A reading of OL 10 20 30
kΩ
40
insulator that surrounds the center means an open circuit or break in OFF
Secondary
V
electrode. Dig down between the the electrical path. If a bad reading
Primary
300mV
1 SEC
wash out any remaining oil or nection with both test leads. 10A V
FUSED
! 100V
750V COM
in place.
the other since there is only one
Now, turn the engine over at
secondary coil which is not
normal cranking speed and watch
connected to the engine block. An
for a spark. If you are in bright sun,
open spark path will kill the spark
you may have to shade the plug to
to both cylinders.
see the spark. If this test shows no
spark or a weak spark, troubles
HV circuit repairs
with the breaker points or coil
inside the magneto are likely. A break in the HV circuit can occur
in several places as shown in
Coil and HV wire Figure 3.
resistance/continuity test If the poor connection or open Figure 3: Possible locations of breaks in
for one-cylinder engines circuit occurs at the spark plug clip, secondary HV circuit
you may be able to repair it without
The next test checks for a continu- taking anything else apart. If the
ous path for the spark through the problem is located inside the mag-
HV wire and the ignition coil. Refer neto, it will probably be necessary
to the electrical diagram in Figure 1. to remove the flywheel.
Note that for a one cylinder engine
there is a direct electrical path from
the plug cap through the HV wire,
Secondary
OFF V
Primary
300mV
1 SEC
damaging the underlying metal
which will shorten the life of the
TOUCH HOLD
10A V
300
mA
FUSED
! 100V
750V COM contacts. In any event do not use
sandpaper. The grit will imbed
itself in the contact metal, render-
Breaker
Points ing the points useless.
If you want a quick fix to get the
engine running, try the “old-timers
Condenser
Engine point cleaning trick” as follows:
Block With the crank shaft positioned so
that the points are closed, pry the
Figure 4: Breaker point contact resistance test
breaker arm open and insert a
clean business card between the
Breaker point test Measure the contact resistance contact surfaces. Release the
as follows: place the multimeter in breaker arm so that the points grip
The breaker points on a magneto
the Ω function and hold the probe the end of the card and then drag
ignition are often located under the
tips tightly together to obtain a the card through its width, wiping
flywheel. Remove any parts that
reference reading with the tips the contacts in the process. The
might interfere with the flywheel
shorted. The reading should show card has two properties which
removal. Hold the flywheel in a
between 0.0 and 0.3 ohms, note make it work. It is absorbent
stationary position with a strap
the value. This is the reference enough to remove oil and gently
wrench and remove the large nut
reading. abrasive enough to remove surface
that holds the flywheel to the
Now place the probe tips on contamination.
crankshaft.
opposite sides of the point contacts When you think the cleaning is
Use a puller to loosen the fly-
when the points are in the closed complete, verify the results by
wheel and lift it off the crankshaft.
position. The meter should now repeating the electrical resistance
Locate the breaker points and
read no more the 0.1Ω greater than test. Before leaving the points,
examine the contact surfaces.
the reference reading. Higher read- make a visual inspection of the gap
(Caution here: when rotating the
ings indicate contamination on the in the open position. A typical
crankshaft, turn it in the forward
contact surfaces. If the contact specification would be 0.020 inches.
direction only to prevent damage to
the water pump impeller). surfaces are pitted, the best choice
would be to replace the points. If Condenser test
For proper operation the breaker
point contact surfaces should be you can’t install new ones, then Next check the condenser as
clean and shining. Make an electri- carefully clean the ones you’ve got. follows: Disconnect the condenser
cal resistance test with your digital The object here is to remove all lead, then place the multimeter in
multimeter before attempting to contamination without damaging the capacitance function and hold
clean the contact surfaces. This will the underlying metal. one test lead to the capacitor case
allow a before and after indication. and the other to the terminal. (See
Refer to the diagram in Figure 4. Figure 5).
Note that the points are in parallel
with the primary coil. When the
points are open the resistance
SERIES II MULTIMETER
23
1 SEC
! 100V
V
FUSED
750V COM
73 MULTIMETER
27 MULTIMETER
VAC
MIN
k
30
0 10 20 30
0 10 20 30
OFF V
RANGE HOLD CAT 600V
600A
V 40 CAL
1000A
OFF A mV mV 200 V
600 V
36 CLAMP METER
10A V OFF
!
40 V A 10A MAX V DC
600V CAT mA
!
600V CAT 1000V MAX
300 FUSED COM 1000V CAT TRUE RMS
mA mA !
10A FUSED COM A 320 mA MAX COM 600V
COM V
Fluke 12B Fluke 73 Series III Fluke 26 Series III Fluke 27 Fluke 36
Put basic tests • Touch Hold ®
Same features as • Fully sealed, ClampMeter
on automatic captures stable Fluke 73 Series III, waterproof case Fluke. Keeping your world
readings plus: • True-rms up and running.
• VCheck™ auto- • Touch Hold ® responding
matically
switches from
• Auto and manual • Rugged, overmolded captures stable
• AC current to 600A
ranging case readings
measuring ohms/
• Holster with Flex- • Tough, electrical test • Volts, ohms, amps, • DC current to 1000A Fluke Corporation
continuity to ac • AC and DC voltage PO Box 9090, Everett, WA USA 98206
or dc volts Stand™ included lead set with continuity, diode
silicone insulation test to 600 Volts
• Capacitance, to • Volts ac and dc
and alligator clip • Max Hold
Fluke Europe B.V.
10k microfarads • Resistance • Current with ranges
from 320 µA to 10A
PO Box 1186, 5602 BD
• True-rms ac voltage • Continuity beeper Eindhoven, The Netherlands
• Continuity • Diode test/
• AC/DC current with
capture locates continuity beeper For more information call:
intermittent ranges from 4.0 mA
• AC/DC current with to 10A U.S.A. (800) 443-5853 or
opens and shorts ranges from 32 mA Fax (425) 356-5116
• Min/Max record- to 10A • Lo Ohms Europe/M-East (31 40) 2 678 200 or
ing with relative Fax (31 40) 2 678 222
time stamp Canada (905) 890-7600 or
Fax (905) 890-6866
Other countries (425) 356-5500 or
Fax (425) 356-5116
Other marine application notes available from Fluke: Web access: http://www.fluke.com
• Troubleshooting Marine Engine Electrical Systems ©1998 Fluke Corporation. All rights reserved.
• Testing Corrosion Protection Systems Printed in U.S.A. 11/98 B0271UEN Rev B
Printed on recycled paper.