FLEX I/O 4-Channel Pulse Counter North American Hazardous Location Approval Connecting Wiring for the 1794-IP4 Module
The following modules are North American Hazardous Location approved: (using a 1794-TB2, 1794-TB3, or 1794-TB3S terminal base unit)
Module 1794-IP4 Series B.
1. Connect individual input wiring (N, N) or (D, D) for each channel
Catalog Numbers 1794-IP4 Series B The following information applies
when operating this equipment in
Informations sur l’utilisation de cet
équipement en environnements
to numbered terminals on the 0-15 row (A) as indicated in the
hazardous locations: dangereux: Wiring Connections for I794-IP4 table.
Important User Information 2. Connect the associated input common to the corresponding
Products marked “CL I, DIV 2, GP A, B, Les produits marqués "CL I, DIV 2, GP A, terminal on the 16-33 row (B) for each input as indicated in the
Solid state equipment has operational characteristics differing from those of C, D” are suitable for use in Class I B, C, D" ne conviennent qu’à une
electromechanical equipment. Safety Guidelines for the Application, Installation Division 2 Groups A, B, C, D, Hazardous utilisation en environnements de
Wiring Connections for I794-IP4 table.
and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your Locations and nonhazardous locations Classe I Division 2 Groupes A, B, C, D
local Rockwell Automation sales office or online at only. Each product is supplied with dangereux et non dangereux. Chaque ATTENTION: Do not connect maximum input voltage
http://www.literature.rockwellautomation.com) describes some important markings on the rating nameplate produit est livré avec des marquages simultaneously to all inputs if the module ambient temperature
differences between solid state equipment and hard-wired electromechanical indicating the hazardous location sur sa plaque d’identification qui is expected to exceed 40 °C.
devices. Because of this difference, and also because of the wide variety of uses temperature code. When combining indiquent le code de température pour If the ambient temperature is expected to continuously exceed
for solid state equipment, all persons responsible for applying this equipment must products within a system, the most les environnements dangereux. Lorsque 40 °C, you must limit the input voltage using an external
satisfy themselves that each intended application of this equipment is acceptable. adverse temperature code (lowest “T” plusieurs produits sont combinés dans resistor on each input. A 1kΩ resistor effectively limits a 24V
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or number) may be used to help determine un système, le code de température le sensor signal to about 15V at the input. Do not limit the input to
consequential damages resulting from the use or application of this equipment. the overall temperature code of the plus défavorable (code de température less than 6V.
The examples and diagrams in this manual are included solely for illustrative system. Combinations of equipment in le plus faible) peut être utilisé pour
purposes. Because of the many variables and requirements associated with any your system are subject to investigation déterminer le code de température
particular installation, Rockwell Automation, Inc. cannot assume responsibility or by the local Authority Having global du système. Les combinaisons 3. Connect +V DC power to terminal 34 on the 34-51 row (C).
liability for actual use based on the examples and diagrams. Jurisdiction at the time of installation. d’équipements dans le système sont
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of 4. Connect DC return to terminal 16 on the 16-33 row (B).
sujettes à inspection par les autorités
information, circuits, equipment, or software described in this manual. locales qualifiées au moment de 5. If daisychaining power to the next terminal base, connect a jumper
Reproduction of the contents of this manual, in whole or in part, without written l’installation. from terminal 51 (+V DC) on this base unit to terminal 34 on the
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations. next base unit.
WARNING: WARNING:
EXPLOSION HAZARD RISQUE D’EXPLOSION 6. If continuing DC common to the next base unit, connect a jumper
WARNING: Identifies information about practices or from terminal 33 (common) on this base unit to terminal 16 on the
circumstances that can cause an explosion in a hazardous • Do not disconnect • Couper le courant ou
equipment unless power s’assurer que next base unit.
environment, which may lead to personal injury or death, has been removed or the l’environnement est
property damage, or economic loss. area is known to be classé non dangereux
nonhazardous. avant de débrancher
ATTENTION: Identifies information about practices or • Do not disconnect l'équipement. Inputs
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
circumstances that can lead to personal injury or death, property connections to this • Couper le courant ou
equipment unless power s'assurer que A
damage, or economic loss. Attentions help you identify a hazard,
has been removed or the l’environnement est
avoid a hazard and recognize the consequences. area is known to be classé non dangereux 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33
(1)
Any unused signals have to be connected to the associated common.
(2) Auxiliary terminal blocks are required when using these terminal base units.
D ATTENTION: Do not enable the filter with frequencies greater North American temp code T4
than 90 kHz. A loss of counts may result. Keyswitch position 1
Channel 1 D
Enclosure type rating None (open-style)
D
Wire size Belden 8761, 304.8 m (1000 ft.)
Channel 0 D
Wiring category(1) 2 - on signal ports
D
Description of Control Word 1 (1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication 1770-4.1.
Bit Description
00 Clock Frequency for period time measurement, Channel 0
0 = period time measurement with 10 MHz internal clock selected Environmental Specifications
1 = period time measurement with 1 MHz internal clock selected
Attribute Value
01...03 03 02 01 Number of periods for measurement – Channel 0
8 9 10 11 12 13 14 15 Operating temperature IEC 60068-2-1 (Test Ad, Operating Cold),
Signal Inputs 0 8 9 10 11 12 13 14 15 A 0 0 0 1 period
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
External 0V DC
16 24 25 26 27 28 29 30 31 32 33
B 0 0 1 2 periods IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
Power Supply 42 43 44 45 46 47 48 49 50
12/24V DC 34 51
0 1 0 4 periods 0…55 °C (32…131 °F)
12/24V DC C
0 1 1 8 periods Storage temperature IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
NOTE: To reduce noise, attach N to 0V DC. 1 0 0 16 periods
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
1 0 1 32 periods -40…85 °C (-40…185 °F)
Configure Your Module 1 1 0 64 periods Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
1 1 1 128 periods 5…95% non-condensing
Input (Read) Image 04 Clock frequency for period time measurement, Channel 1 – refer to bit 00 Vibration IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz
05...07 Selection of number of periods for measurement, Channel 1 – see bits 01...03
Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
08 Clock frequency for period time measurement, Channel 2 – refer to bit 00
Shock IEC60068-2-27 (Test Ea, Unpackaged shock):
Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0 Operating 30 g
09...11 Selection of number of periods for measurement, Channel 2 – see bits 01...03 Non-operating 50 g
0 Reserved
12 Clock frequency for period time measurement, Channel 3 – refer to bit 00 Emissions CISPR 11:
1 Counter 00 – 16-bit period measurement for channel 0
13...15 Selection of number of periods for measurement, Channel 3 – see bits 01...03 Group 1, Class A (with appropriate enclosure)
2 Counter 01 – pulse counter for channel 0 – 16-bit pulse counting
ESD immunity IEC 61000-4-2:
1 32-bit period measurement for channel 0
6 kV contact discharges
Description of Control Word 2
2 32-bit period measurement for channel 0 8 kV air discharges
3 Counter 10 – 16-bit period measurement for channel 1 Bit Description Radiated RF immunity IEC 61000-4-3:
4 Counter 11 – pulse counter for channel 1 – 16-bit pulse counting 10V/m with 1 kHz sine-wave 80% AM from 30...1000 MHz
00 Start new measurement, Channel 0 – when set, start new measurement on positive edge
3 32-bit period measurement for channel 1 01 Start new measurement, Channel 1 – when set, start new measurement on positive edge
EFT/B immunity IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports
4 32-bit period measurement for channel 1 02 Start new measurement, Channel 2 – when set, start new measurement on positive edge
5 Counter 20 – 16-bit period measurement for channel 2
Surge transient immunity IEC 61000-4-5:
03 Start new measurement, Channel 3 – when set, start new measurement on positive edge ±1 kV line-earth(CM) on shielded ports
6 Counter 21 – pulse counter for channel 2 – 16-bit pulse counting 04 Reset Counter, Channel 0 – a positive edge on this bit resets counter 01 Conducted RF immunity IEC 61000-4-6:
5 32-bit period measurement for channel 2 05 Reset Counter, Channel 1– a positive edge on this bit resets counter 11 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
6 32-bit period measurement for channel 2 06 Reset Counter, Channel 2 – a positive edge on this bit resets counter 21
7 Counter 30 – 16-bit period measurement for channel 3 07 Reset Counter, Channel 3 – a positive edge on this bit resets counter 31 Certifications
8 Counter 31 – pulse counter for channel 3 – 16-bit pulse counting 08...15 Reserved for factory use
Certifications Value
7 32-bit period measurement for channel 3 (when product
8 32-bit period measurement for channel 3 Description of Control Word 2 Readback is marked)(1)
9 Readback of Control Word 2 c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada.
Reserved RD3 RD2 RD1 RD0 M3 M2 M1 M0
Bit Description See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for
10 Revision Read - software version code 00 Positive edge, Channel 0 – measurement ready
U.S. and Canada. See UL File E193170.
Where M = Measurement ready bit – positive edge measurement ready for the respective channel 01 Positive edge, Channel 1 – measurement ready
CE European Union 2004/108/EC EMC Directive, compliant with:
RD = Reset done 02 Positive edge, Channel 2 – measurement ready EN 61326-1; Meas./Control/Lab., Industrial Requirements
03 Positive edge, Channel 3 – measurement ready EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
Output/Configuration Image 04 Reset Counter, Channel 0 – a positive edge on this bit indicates counter 01 reset done
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
05 Reset Counter, Channel 1 – a positive edge on this bit indicates counter 11 reset done
Dec 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 KC Korean Registration of Broadcasting and Communications Equipment, compliant
06 Reset Counter, Channel 2 – a positive edge on this bit indicates counter 21 reset done with: Article 58-2 of Radio Waves Act, Clause 3
Oct 17 16 15 14 13 12 11 10 7 6 5 4 3 2 1 0
07 Reset Counter, Channel 3 – a positive edge on this bit indicates counter 31 reset done EAC Russian Customs Union TR CU 020/2011 EMC Technical Regulation
0 Control Word 0 – selects the measure function
08...15 Reserved for factory use
1 Control Word 1 – sets the clock frequency and period multiple RCM Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
2 Control Word 2 – sets the start of a new measurement
(1)
3 Not used See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.
Allen-Bradley, Rockwell Automation, FLEX I/O, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.