sn
Specification Sheet
A. Programmable Logic Controller (PLC) Automation system
Quantity 03 Sets
Each PLC Automation system consists of the following items:
1. Central processing Unit
a. System characteristics:
Should be programmed with STEP 7 or higher,
Automatic routing via PROFINET / Profibus, independent of network
Data block routing via PROFINET / Profibus
Integrated Web server functionality
Integrated communication services (TCP/IP, UDP, ISO on TCP, SNMP, NTP,
PROFINET CBA/IO)
Isochronous operation on the bus system
b. Integrated work memory: 384 Kbyte
¢. Integrated load memory: 8 MByte
d. No. of timers: 256
e. No. of counters: 256
£. No. of bit memories: 2048 Byte
g. Processing times
For bit-operations, min.: 0,05 ps
For word operations: 0,09 us
For arithmetic operations: 0,12 ps
For floating point arithmetic: 0.45 ps
h. Interfaces
MPI (RS485), PROFIBUS (RS485), PROFINET (RJ 45-Ethernet), Integrated
PROFINET Switch
i. Integrated fuctions
Real-time clock, Buffer time 6 weeks, Password protection
|. Supply voltage
Rated value: 2av DC
la. Accessories
i, Micro memory card 2MB
ii, 19 inch DIN Rail channel
Note: The above CPU module should be functionally equivalent to $7 315 2PN/DP and should
be programmed by Step 7 Total Integration Automation portal VII2, Digital Input Module Qty.: 04 Numbers
|_| Supply voltage
24. V DC Yes
permissible range, lower limit (DC) 204 V
permissible range, upper limit (DC) 28.8 V
2 | Number of digital inputs 16
3 | Input voltage
Rated value, DC 24v
for signal "0" 301045 V
for signal "1" 13t030V
4 [Input delay for standard inputs Programmable 0.17,5/3/15/20 ms
5 | Status display Green LED per channel
Sensor supplies Green LED per group
3 | Galvanic isolation between channels Groups of 16
4 | Opto isolation between channels and backplane Opto isolation
5 | Permissible potential difference between different | 75 VDC/ 60 VAC
circuits
6 | Isolation 500 VDC
7 | Features Tsochronous mode, programmable
diagnostics, programmable
diagnostics interrupt, programmable
hardware interrupts, 2 short circuit
proof sensor supplies for each
group of 8 channels, support for
external redundant sensor suppl:
8 | Connection method
40-pin front connector
2a. Accessories: Front connectors
3. Relay Output Module
Qty.: 04 Numbers
1 | Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 204 V
permissible range, upper limit (DC) 28.8 V
2 | Relay outputs
Number of Relay outputs
8 with electrical isolation in groups
of I channel
3_| Maximum potential difference between outputs
500 VAC
4 | Isolation test voltage difference between outputs
2000 VAC3] Status display Green LED per channel
6 | Switching capacity with resistive load 24VDC @ 2A | 0.7 million
Inductive load 24VDC @ 2 A | 0.3 million
7 | Switching frequency
Mechanical 10 Hz
With resistive load 2He
8 [Connection method
40-pin front connector
3a, Accessories: Front connectors
4, Analog input module
Qty.: 02 Numbers
1. | Supply voltage
Load voltage 24 VDC
Reverse polarity protection Yes
2._| Number of analog inputs 8
Permissible input voltage for voltage input
75 V; 35 V continuous, 75 V for
max. 1s
Permissible input current for current input 40 mA
(@estruction limit), max.
3._| Measurement principle integrating
Resolution with overrange (bit including sign), 16 bits
Integrating time (Parametrizable) Yes: 23/ 72/ 83/ 95 ms
Basic conversion time, ms 10 ms (4-channel mode);
95/83/72/23 ms (8-channel mode)
Interference voltage suppression for interference
frequency fin Hz
50 Hz
Input Range
Voltage Range 40-10 V, +/-SV with input
resistance >= 10 Mohms
Current Range 0 to 20 mA , 4 to 20 mA with input
resistance <= 250 ohms
3. | Interrupts
Limit value monitoring
Programmable for 8 channels
Programmable Hardware interrupt
when limit exceeded
Hardware interrupt at end of cycle
5. | Errors (Operational limit in overall temperature
range)
Voltage, relative to input area
Current, relative to input area
H- 0.1%
#101 %
6. | Diagnostics
Diagnostic alarm, Limit value alarm
parametrizable for all channels
7. | Galvanic Isolation
Galvanic isolation between
channels in groups of 2, betweenchannels and backplane. Isolation
voltage 500 VAC
5. DC Power Supply Qt
nove
NOTE:
Accessories: Front connectors
AC Input: I-phase 170-264AC, SOHz. input Voltage range
Overvoltage resistance: 2.3xVin rated/1.3 ms
Mains buffering at lout rated min.: 20 ms
Bu -oming fuse
DC Output: 24VDC/10A
Peak to Peak Ripple typ/max : 50/150 my
Adjustment Range: 22.8V to 28V via potentiometer
Green LED Status Display
Efficiency: 90%
Output overvoltage protection <33V
Short circuit protection
Safety entra low output voltage Vout according to 50178 EN and 60950-1 EN
Screw type terminals, Rail mounting
‘Supplier should send the detailed specification sheet, module numbers, part numbers
along with quotation, failing which quotation will not be considered.
Supplier should quote for the entire PLC automation system. Incomplete quotations
will not be considered. Order will only be placed for the complete set, not for the
individual items in the set.
CPU and /O modules should be programmed by STEP 7 TIA V11 programming
software,
Material should be with latest version available from the original manufacturer.
Supplier should provide technical support for installation/testing of the system in an
integrated way.
Minimum 1-year product warranty should be given.
Material should be in original packing.