Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Contents
1. Introduction 4
1.1 Purpose 4
1.2 User Safety 4
1.3 Product Description 5
2. Safety 6
2.1 Safety Precautions 6
2.2 Safety Practices 7
3. Limit Switch and Torque Switch Setting Procedures 8
3.1 Initial Actuator Preparation 8
3.2 Torque Switch 8
3.2.1 Setting Torque Switch 8
3.2.2 Balancing Torque Switch 9
3.3 Geared Limit Switch 10
3.3.1 Setting Limit Switch 10
3.3.2 Setting Procedure (Refer to Figure 3.2) 11
3.3.3 Combination of Contacts (Refer to Figure 3.2) 12
4. Removal of UEC-3 Electronic Controller 13
5. UEX Electronic Controller Installation 18
6. Standard Control Features 22
6.1 Basic Specifications 22
6.2 Local Control 23
6.3 Remote Control Modes of Operation 23
6.4 Emergency Shutdown (ESD) 24
6.5 Remote External Interlocks/Inhibits 25
6.6 Absolute Position Encoder 25
7. Protection Features 26
7.1 Autophase Protection and Correction 26
7.2 Jammed Valve Protection 26
7.3 Instantaneous Reversal Protection 26
7.4 Motor Thermal Protection 26
8. Optional Control Features 27
8.1 Modutronic 27
8.2 Analog Position Transmitter (APT) 28
8.3 Two-Speed Timer 28
8.4 Control Station (CSE) 28
9. Network Communications 29
9.1 Modbus™ 29
9.2 Master Station III 30
9.3 Foundation Fieldbus Communication 30
9.4 PROFIBUS DP V1 Communication 31
9.5 PROFIBUS PA Communication 31
9.6 DeviceNet 32
10. Monitoring and Diagnostic Features 33
10.1 Local Features 33
10.2 Diagnostics 34
2 11. Remote Indication Features 36
11.1 Actuator Status Contacts (S1a, S1b, S2a, S2b) 36
11.2 Monitor Relay (RM) 37
11.3 Exact End Position Indication 37
12. Auxiliary Power Supply 38
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
1
Introduction
1.1 Purpose
This Installation and Maintenance Manual explains how to install, setup, and maintain the UEX controller
for the L120-10, L120-20, L120-40, and L120-85 actuators. Information on installation, operation,
control features, and maintenance is provided.
Contact Flowserve Limitorque if assistance is needed or preferred for installation, upgrading, or training
in the operation of the UEX.
cc WARNING: Refers to personal safety. Alerts the user to potential danger. Failure to follow warning
notices could result in personal injury or death.
aa CAUTION: Directs the user’s attention to general precautions that, if not followed, could result in
personal injury and/or equipment damage.
OTE: Highlights information critical to the user’s understanding of the actuator’s installation and
N
4 operation.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Table 1.1 Standard Application Voltages with +/- 10% Nominal Range
A Lights (2)
Open
(Yes)
Blue
Knob
Close
(No) Red
A Knob
VIEW A-A
CSE Control
Station
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
2
Safety
cc WARNING: Be aware of electrical hazards. Turn off incoming power before working on the actuator
and before opening the switch compartment.
cc WARNING: Do not manually operate the actuator with devices other than installed Handwheel and
Declutch Lever. Using force beyond the ratings of the unit and/or using additive force devices such
as cheater bars, wheel wrenches, pipe wrenches, or other devices on the actuator Handwheel or
Declutch Lever may cause serious personal injury and/or damage to the actuator or valve.
cc WARNING: For maintenance and/or disassembly of the actuator while installed on the valve, ensure
that the actuator is not under thrust or torque load. If the valve must be left in service, the valve
stem must be locked in such a way as to prevent any movement of the valve stem.
cc WARNING: For maintenance and/or disassembly of the actuator while installed on the valve, ensure
that the actuator is not under thrust or torque load. If the valve must be left in service, the valve
stem must be locked in such a way as to prevent any movement of the valve stem.
cc WARNING: Do not attempt to remove the spring cartridge cap, housing cover, or stem nut locknut
from the actuator while the valve or actuated device is under load.
6 cc WARNING: Do not exceed any design limitations or make modifications to this equipment without
first consulting Limitorque.
cc WARNING: Actuators equipped with electrical devices (motors, controls) requiring field wiring must
be wired and checked for proper operation by a qualified tradesman.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
cc WARNING: Use of the product must be suspended any time it fails to operate properly.
aa CAUTION: Do not use oversized motor overload heaters. Instead, look for the cause of the overload.
aa CAUTION: Do not operate the valve under motor operation without first setting or checking the limit
switch setting and motor direction.
aa CAUTION: Do not force the declutch lever into the motor operation position. The lever returns to this
position automatically when the motor is energized.
aa CAUTION: Do not depress the declutch lever during motor operation to stop valve travel.
aa CAUTION: Do not use replacement parts that are not genuine Flowserve Limitorque parts, as
serious personal injury and/or damage to the actuator and valve may result.
aa CAUTION: Do not lift actuator/gearbox or actuator/valve combinations with only the eye bolts in the
L120 actuator. These eye bolts are designed for lifting the L120 actuator only.
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
aa CAUTION: Disconnect all incoming power before opening limit switch compartment or working on
the torque switch.
• Do not use abrasive cloth to clean the contacts on the torque switch.
• Do not torque seat 90° operation valves nor run them against the stops. This may cause damage
to the valve.
NOTE: If the actuator operation has been interrupted by the tripping of the torque switch, release torque
buildup by operating the actuator manually in the opposite direction until the load is released and the
dial has returned to the center position.
aa CAUTION: A torque switch limiter plate is provided on most actuators. Do not remove this plate. Do
8
not exceed the setting indicated by this plate without first contacting Flowserve Limitorque service.
• Removal or modification of the torque switch limiter plate will void the actuator warranty.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
aa CAUTION: Installing or adjusting the torque switch with the actuator under load will result in a loss
of torque protection.
1. Place the L120 actuator in manual mode by pulling the declutch lever in the direction shown on the lever.
2. Release the load on the wormshaft spring pack by rotating the handwheel until the valve disk
position approximates 50% open.
3. For open and close directions, loosen Screw (A) and move Pointer (B) to desired position. A higher
number indicates a high torque and/or thrust output.
5. Operate the valve electrically to seat the valve and to ensure tight shutoff.
6. Rebalance the torque switch if required. See Section 3.2.2 below for the steps to balance the torque
switch.
Figure 3.1 – Microswitch-Style Torque Switch and 600 Volt Torque Switch
B A
B
Maximum Stop A
Setting Plate Maximum Stop
Setting Plate
EN
OP
-20
-10
Balancing Balancing
Screws Screws
-20
-10
E
OS
CL
Mounting
Index Marks Mounting Index Marks Screw
Screw
B
A
B
A
If the torque switch has been removed from the unit or if a new torque switch is being installed, the
torque switch must be rebalanced using the following procedure:
2. Remove the load from the wormshaft spring pack by rotating the handwheel until the valve disk
approximates 50% open.
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
3. Note the open and close torque switch settings prior to reinstalling the torque switch.
4. Loosen Screws (A) and position both Pointers (B) at the #1 setting, tighten Screw (A). In this
position the index marks should be aligned.
5. Loosen balancing screws and install the torque switch. The base of the torque switch should be
flush against the compartment and the hole for the mounting screw should be aligned.
aa CAUTION: The balancing screws should not be touched except during the balancing procedure.
The switch is now balanced and ready for the pointers to be returned to their original settings.
• Disconnect all incoming power to the actuator prior to opening the limit switch compartment and
adjusting the switch.
• Consult the relevant wiring diagram for limit switch contact development. All L120 units are
supplied with 16-contact limit switches - four switches on each of the four rotors. Two rotors are
used for end of travel indication. The remaining two rotors may be adjusted for any intermediate
point of travel.
• Do not use abrasive cloth to clean the contacts on the limit switch.
• Do not attempt to repair gearing in the limit switch. Replace entire gear frame assembly if necessary.
NOTE: The chart below provides the maximum number of drive sleeve turns for each actuator size. The
Intermediate Shaft (B), shown in Figure 3.2, may require a considerable number of turns before rotor trip occurs.
Table 3.1 – Maximum Number of Drive Sleeve Turns for Standard Four-Gear and Optional Five-Gear
Limit Switches
Actuator Size Four-Gear Five-Gear
L120-10 630 6300
L120-20 740 7400
L120-40 640 6400
cc WARNING: Potential Explosion Hazard. Do not use an electric drill for setting the limit switch in an
explosive environment.
aa CAUTION: When setting the limit switch rotor segments (cams) using a variable speed electric drill,
10 do not run drill at speeds higher than 200 RPM. Operating the drill at high speeds can damage the
gearing within the limit switch.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
7
8 6
4
9
3
2
1
2. Place the actuator into manual operation by pulling the declutch lever in the direction shown on the
lever. Use the handwheel to operate the valve in the “open” direction. While operating the valve, note
the direction of the Intermediate Shaft (B) corresponding to the rotor or rotors to be set.
3. When the valve is fully open, rotate the handwheel to operate the valve in the close direction a 11
sufficient number of turns to allow for coast of moving parts, or refer to the valve manufacturer
setting requirements.
4. Push in the Setting Rod (A) and turn one-quarter turn. The rod will latch in this depressed position.
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
5. Refer to the applicable wiring diagram for contact development. The limit switch contact is closed
when the rotor is engaged with the plunger. If the rotor to be set has not turned 90 degrees to
operate the plunger, turn the intermediate shaft in the same direction as noted in Step 2 until the
rotor clearly trips the switches. This rotor is now set correctly.
6. Before moving the valve disk, depress and turn the Setting Rod (A) one-quarter turn to the spring
released position. Insert a screwdriver into the intermediate shafts to ensure that they will not move.
aa CAUTION: Do not operate the valve when Setting Rod (A) is in a fully depressed position. Loss of
contact setting will occur and the setting rod will be damaged.
7. Operate the valve by handwheel to the fully “close” position; reverse direction by a sufficient
number of turns of the handwheel to allow for coast of moving parts, or refer to the valve manufac-
turer setting requirements.
Closed Open
position position
1. Remove Nuts (piece 8) and Fillister Head Machine Screws (piece 5, for a total of two fasteners on
each side of the switch).
4. Replace contact assembly on back-plate (ensuring that the registers fit correctly) and secure with
the machine screw and nuts.
12
5. Set limits according to the procedure above.
NOTE: For mechanical operation and maintenance of the L120 actuators, please see section 5 and 6 of
LMENIM1201.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
NOTE: Confirm that the limit switches are set properly prior to disassembly and removal of the UEC-3
and related components. Confirming the settings will allow for installation of the UEX Electronic
Controller without requiring a reset of the limit switches.
3. Cut and remove all wire ties from wiring that is connected to the UEC-3 assembly (pc# C-201).
5. Disconnect the Motor leads and Heater leads from the Interconnect Board.
6. Disconnect the Pushbutton Station ribbon cable from the Interconnect Board.
7. Disconnect the Analog-to-Digital Circuit Board (pc# C-223) ribbon cable from the Interconnect Board.
9. Uninstall the Potentiometer by removing the screws that fasten it to the MDPI assembly.
10. Uninstall the MDPI assembly by removing the screws that fasten it to the Geared Limit Switch
assembly.
11. Unplug the optional I/O Circuit Board (pc# C-223) from the SBC Board on the UEC-3 Assembly.
12. Label all customer wiring and disconnect from the Interconnect Boards.
13. Remove the four screws from the UEC-3 Assembly (pc# C-201) and carefully remove the Assembly
from the Controls Compartment.
14. Remove the Pushbutton Station with ribbon cable from the L120 gear housing conduit entry.
13
flowserve.com
14
A
SEE SHEET 2
A
TMI INTERGAL ITEMS
50 PC. QTY. DESCRIPTION
NO.
25 75 C23 1 HEATER ASSY
C C184 1 GROUND LUG
UNIVERSAL 23 (HEATER) C185 1 SCREW, PAN HD. MACH.
0 PERCENT 100 C186 1 LOCKWASHER,EXT. TOOTH
OPEN
ELECTRONICS CLOSE INT 1 C201 1 UNIVERSAL ELECTRONICS CONTROLLER
C202 4 SCREW,PAN HD.MACH.
C203 4 LOCKWASHER
C203-1 12 FLAT WASHER
CONTROLLER L120-10
OPEN INT 2 C204 1 TERMINAL STRIP (12 POINT)
C204-1 1 TERMINAL STRIP INSULATOR
4 GEAR C205 4 SCREW,PAN HD.MACH.
(UEC) C206 4 LOCKWASHER,EXT.TOOTH
C210 1 SIGNAL CONVERTER
C211 4 SCREW,PAN HD.MACH.
C212 4 LOCKWASHER,EXT.TOOTH
C216 1 BRACKET, TERMINAL STRIP
C217 2 SCREW, PAN HD. MACH.
-10-20
OS
CL (GROUND LUG) C218 2 LOCKWASHER,EXT. TOOTH
C220 1 BRACKET
C C C C221 2 SCREW,PAN HD.MACH.
184 185 186 C222 2 LOCKWASHER,EXT.TOOTH
C223 1 INTERFACE P.C. BOARD
C C224 2 SCREW, PAN HD. MACH.
Figure 4.1 - Removal of the UEC-3 Electronic Controller
C C
C 205 206
201
UEC UEC C C
204 204
-1
C C
217 218
9
13
9C
13C
UEC
14
10
14C
10C
C
216
15
11
15C
11C
16C
16
12
12C
INT.2 INT.1
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
15
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
16
17
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
25 28 32 15
36
A 13 18 19
SE FU
FU SE
25 31
1
4
10
33
34
B-E ELEC
14
ITEM QTY. DESCRIPTION
1 1 REVERSING CONTACTOR
2 1 POWER SUPPLY BOARD
3 1 HARNESS, ICB TO D. BOARD
9 4 1 GROUND WIRE, POWER
c c 24 27 VIEW C-C 5 1 HARNESS, HEATER
A 35 30 25 26
20 8
6
7
1
1
HARNESS, POWER
HARNESS, RIBBON 50PIN
ON CLEAR 31 25 37 29 8 1 BRACKET, TRANSFORMER
31 25 RIBBON FOR SW93 22
PLASTIC COVER 9 1 DAUGHTER BOARD (DDC ONLY)
ON BOM 4805-455 10 1 MOV SNUBBER, 12A/25A
FUSE 11 1 HARNESS, STARTER
7 12 1 INTERCONNECT BD (DDC SHOWN)
13 1 SBC W/ CIRCUIT TRACE
14 1 RAIL, DIN
21 15 1 STICKER, UEC-3 ALL
12
16 16 1 HARNESS, CONTACTOR
Figure 4.2 – UEC-3, MPC, DDC Assembly
17 1 INSULATOR, ICB
18 1 INSULATOR, SBC
19 1 SCREEN PLATE
20 1 LABEL, FRONT COVER
21 1 TERMINAL COVER, UEC
5 22 1 FRONT COVER, UEC
SUPPLY
23 1 CONTROL BOX, UEC
24 2 LOCKWASHER (EXT TOOTH)
3 25 5DDC/4 UEC LOCKWASHER (INT TOOTH)
26 1 HEX NUT
MOTOR HEATER
27 2 HEX NUT
2
28 1DDC/4 UEC SCREW, PAN HD
29 1 LOCKWASHER (INT TOOTH)
30 1 SCREW, PAN HD
FUSES 31 3 SCREW, PAN HD
32 1 SCREW, PAN HD
33 2 SCREW, PAN HD
6 34 1 SCREW, PT FLAT
B B 35
36
8
1
SCREW, PT OVAL HD
BITBUS/MODBUS PROM
37 1 SCREW, PAN HD
35
11 17 INSULATOR BEHIND PCB
23 SECTION A-A
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
5 UEX Electronic
Controller Installation
cc WARNING: Turn off all incoming power before installing or working on the UEX Electronic Controller.See
1.
2.
additional safety precautions and practices in Section 2.
Remove the qty (2) screws mounting the Terminal Strip Assembly (pc# 3-2) to the Geared Limit Switch (pc#
2-13). These will not be reused. (See Figure 5.2)
Install the Encoder Drive Assembly (pc# 2-3) to the Geared Limit Switch (pc# 2-13) using the two Socket
Head Cap Screws and Lockwashers (pc# 2-9, 2-10). (See Figure 5.1)
3. Reinstall the Terminal Strip Assembly (pc# 3-2) to the Geared Limit Switch (pc# 2-13) using the qty (2)
Button Head Socket Cap Screws and Lockwashers (pc# 3-6 & 3-9). (See Figures 5.1 & 5.2)
4. Install the Encoder Mounting Plate Assembly (pc# 2-2) with Transformer (pc# 2-4) onto the Geared Limit Switch
(pc# 2-13) using the qty (6) Button Head Socket Cap Screws and Hex Nuts (pc# 2-7, 2-8). (See Figure 5.1)
aa CAUTION: Ensure proper clearance between the top gear of the Encoder Drive Assembly (pc# 2-3) and the
mating bushing of the Encoder Mounting Plate Assembly (pc# 2-2). Add or remove Shims (pc# 2-11) to
achieve 0.015” to 0.030” clearance.
NOTE: Lightly apply Lithium NLGI Grade #2 general purpose grease to all shafts, bushings and gear teeth of
the Encoder Drive Assembly.
5. Connect the Primary leads (L1 & L2) and the Secondary leads (H1 & H2) to the matching terminals on the
Terminal Strip Assembly (pc# 3-2). (See Figures 5.2 & 5.6)
6. Install the Power / Interface Board Assembly (pc# 3-1) onto the Electrical Compartment Mounting Plate
(pc# 202) using the qty (5) Socket Head Cap Screws (pc# 3-4). (See Figure 5.2)
7. Connect the Power Board leads L1, L2, and L3 to the mating terminals on the Terminal Strip Assembly
(pc# 3-2). (See Figure 5.6)
8. Connect the Power Board Motor leads T1 to T3 on the Terminal Strip. Connect T2 to T2 on the Terminal Strip
and connect T3 to T1 on the Terminal Strip Assembly (pc# 3-2). (See Figure 5.6)
aa CAUTION: Ensure that wire connections are as described in Step 8 to prevent incorrect rotation.
9. Install the Encoder Assembly (pc# 2-1) onto the Encoder Mounting Plate Assembly (pc# 2-2) using the qty
(3) Socket Head Cap Screws (pc# 2-12). (See Figure 5.1)
10. Remove the Display Window Retention Plate (not shown) by removing the qty (4) Hex Head Self-Tapping
Screws (pc# 204-4) from the Controls Compartment Cover (pc# 201-1). The Display Window Retention
Plate will not be reused. Do not remove the Display Window (pc# 204-1), O-ring (pc# 204-3) or Gasket
18
(pc# 204-6). (See Figure 5.3)
NOTE: Retain the qty (4) Hex Head Self-Tapping Screws (pc# 204-4) for use in the following step.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
11. Install the Main Board Set Mounting Bracket (pc# 1-1) into the Controls Cover using the qty (4) Hex Head Self-Tapping Screws
(pc# 204-4) previously used to mount the Display Window Retention Plate. (See Figure 5.3)
12. Connect the Main Board Interconnect Harness to the Main LCS Board (pc# 1-2) and then to the Interface Board (pc# 3-1-3).
(See Figures 5.2 & 5.3)
13. Connect the Encoder Board (pc# 2-1) harness to the Main Board (pc#1-2) J-1 connector. (See Figures 5.1 & 5.3)
14. Install the Main LCS Board (pc# 1-2), with the Option Boards (pc# 1-3) if supplied, using qty (4) Pan Head Screws (pc# 1-4).
(See Figure 5.3)
15. Connect the existing UEC-3 Harness to the Interface Board (pc# 3-1-3). (See Figure 5.2)
NOTE: If an existing CSE Control Station is being utilized, proceed with Step 16 to retrofit for the UEX Controls Package.
Otherwise, skip to Step 19.
16. Remove the qty (4) Machine Screws and Lockwashers (pc# 3-7-28 & 3-7-29) and Printed Circuit Board (pc# 3-7-26) from the
back of the CSE Control Station (pc# 3-7). (See Figure 5.4)
17. Connect the Jumper Wire (pc# 3-10) from the S1-1 to S2-1 switches. (See Figure 5.4)
18. Install the Printed Circuit Board (pc# 3-7-26) to the back of the CSE Control Station (pc# 3-7) using the qty (4) Machine Screws
and Lockwashers (pc# 3-7-28 & 3-7-29). (See Figure 5.4)
19. Install the O-Ring (pc# 3-7-4) onto CSE Control Station (pc# 3-7) and slide the CSE into the Controls Compartment Cover,
ensuring the knobs are oriented as shown in Figure 5.5. Mount using qty (4) Socket Head Cap Screws and Lockwashers (pc#
3-7-24, 3-7-25). (See Figure 5.5)
20. Connect the CSE Ribbon Cable to the Interface Board (pc# 3-1-3). (See Figures 5.2 & 5.5)
21. Connect the 120V cable from the Main Board Interconnect Harness to the Terminal Strip Assembly (pc# 3-2). (See Figure 5.6)
22. Attach one UEX Conversion Label (pc# 3-5) on the Power Board Assembly (pc# 3-1-2) side of the Power / Interface Board
Chassis (pc# 3-1-1). Also attach one UEX Conversion Label (not shown) to the left of the existing unit nameplate on the
gearbox. (See Figure 5.2)
2-11 2-2
2-7 2-8 6X 3-1 3-4 2X
2X 3-9 3-6 -1
2-1 3-2
2-12 3X
2X 2-6
2-4
202
2-1
2-4
2-5 2X
3-5
19
2-3
2-2 Figure 5.2 - Power / Interface Board Assembly
VIEW 'A'
CONVERSION LABEL
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
204
-3
204
-1
204
-6
204 4X
-4
1-2
ASSEMBLY VIEW
1-3
1-1
1-4 4X
3-10
Jumper Wire
Connection S1-1 3-7
3-7
-26
3-10
3-7 3-7
-29 -28
ASSEMBLY VIEW
Jumper Wire
Connection S2-1
3-7
-4
ASSEMBLY VIEW
20
Display 3-7
Window
3-7 3-7
-25 -24
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Terminal Strip
Assembly
TERMINAL STRIP
H2
H2
H1
H2
GREEN
12 11 10 9 8 7 6 5 4 3 2 1
T1
T2
T3
GN/YL
(L3)BL
(L2)YL
(L1)RD
110VAC HOT
3/4
1/2
MTR. HTR.
MTR. HTR.
110VAC N
(10-2)RD
(10-1)RD
Table 5.1 – UEX Parts List
ITEM NO. QTY. DESCRIPTION ITEM NO. QTY. DESCRIPTION
1-1 1 Mounting Bracket, Main Board Set Power / Interface Board
3-1-1 1
1-2 1 Main LCS Board Power / Interface Chassis
3-1
4 3-1-2 1 Board Assembly Power Board Assembly
1-3 Option Boards
(Max) 3-1-3 1 Interface Board
1-4 4 Pan Head Screw 3-2 1 Terminal Strip Assembly
2-1 1 Encoder Assembly 3-4 5 Socket Head Cap Screw
2-2 1 Encoder Mtg Plate Assembly 3-5 2 Uex Conversion Label (1 Not Shown)
2-3 1 Encoder Drive Assembly 3-6 2 Button Head Socket Cap Screw
2-4 1 Transformer 3-7 1 Control Station
2-5 2 Button Head Socket Cap Screw 3-9 2 Lockwasher
2-6 2 Hex Nut 3-10 1 Jumper Wire
2-7 6 Button Head Socket Cap Screw 201-1 1 Controls Compartment Cover
2-8 6 Hex Nut (Not Shown) 202 1 Electrical Compartment Mtg Plate
2-9 2 Socket Head Cap Screw 204-1 1 Display Window
2-10 2 Lockwasher 204-3 1 O-Ring
As 204-4 4 Hex Head Self-Tapping Screw
2-11 Shim
Req'd 204-6 1 Gasket
2-12 3 Socket Head Cap Screw
2-13 1 Geared Limit Switch Assembly 21
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
A Lights (2)
Open
(Yes)
Blue
Knob
Close
(No) Red
A Knob
VIEW A-A
22 CSE Control Station
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Local Indication
The Control Panel includes the following:
• Red/Green LED Indicators – the color assignment for the red and green LEDs is reversible as
standard.
Red ON = Valve fully open
• Yellow LED
Yellow ON = Actuator available for remote operation,
Yellow “BLINKING” = Monitor Relay de-energized, actuator not available for remote operation.
NOTE: For UEX packages supplied without the encoder, position indication on the LCD display or
remotely is not available.
• Four-Wire Control – Three momentary contacts. Valve can be opened, closed or stopped.
• Two-Wire Control – Single open or closed contact. Valve can be opened or closed, but not stopped in
mid-travel.
• Three-Wire Maintained – Two momentary contacts for self-maintained control. Valve can be opened
or closed but not stopped in mid-travel.
• Three-Wire Inching – Two “push-to-run” contacts. Valve can be opened, closed and stopped in
mid-travel.
Refer to Figure 15.4 for remote wiring connections.
23
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
• Digital (Discrete) Only Control Type – Only digital input commands are recognized and acted upon.
All other types of remote control commands are ignored.
• Analog (Modutronic) Only Control Type – Only Modutronic 4-20 mA commands are recognized and
acted upon. All other types of remote control commands are ignored.
• Network Only Control Type – Only network (DDC, Fieldbus, Profibus, Device Net) commands are
recognized and acted upon. All other types of remote control commands are ignored.
• Multi-control Mode Operation - there are three modes of remote control when remote mode is
configured for multi control: digital control, analog control, and network control. Digital and network
control operation is based on the last command received. Analog operation is initiated by either
toggling user input 2 (configure for CSE input) or breaking and reapplying the analog control.
24
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
An absolute position encoder, incorporated into the L120 actuators, is the same as the encoder used in the
MXa. It includes 18 phototransistors that are switched on and off by a gear/wheel mechanism.Valve position
is sensed by an 18-bit, optical, absolute position encoder with redundant position sensing circuits designed
for Built-In Self-Test (BIST).
Each of the position sensing circuits is redundant, facilitating BIST. The BIST feature discerns which
failures will signal a warning only and require a warning plus safe shutdown of the actuator. Open and
closed positions are stored in permanent, nonvolatile memory. The encoder measures valve position at
all times, including both motor and handwheel operation, with or without power present, and without the
use of a battery. The absolute encoder is capable of resolving ±7° of output shaft position and over 10,000
output drive rotations, however, in the L120, the encoder is limited to the maximum geared limit switch
travel. Refer to Table 3.1.
This design permits continuous monitoring of valve position during motor and handwheel operation. The
encoder is 100% repeatable and requires no backup power source for operation. The output is used to
control the open and closed valve position and measure and report valve position, as well as provide local
and remote position feedback.
The positioning accuracy is better than 99% for valves requiring 50 or more turns. For the maximum
actuator turns and resolution, see Table 3.1.
25
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
7
Protection Features
aa CAUTION: Confirm that motor thermals are rated no higher than 120°C for Explosionproof service.
26
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
8
8.1 Modutronic
Optional Control Features
NOTE: For UEX packages supplied without the encoder, modulating control and position indication are
not available.
The Modutronic controller will alter valve position in proportion to an analog command signal. It
includes an automatic pulsing mode to reduce overshoot at the set point.
The following parameters may be easily set during the configuration of the unit:
Extrema Mode – If the command signal represents a position of 0–2% OPEN (nominal 4.00–4.32 mA)
or 98–100% OPEN (nominal 19.68–20.00 mA), then the UEX/L120 will move the valve directly to that 27
position, without pulsing.
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Positioning Frequency – The standard frequency is suitable for a rate of 600 starts/hour for short
periods, typical of process start-up. Typical process control of ≤ 100 starts/hour.
The user may select the minimum signal to represent either the fully OPEN or the fully CLOSE position
of the valve during the setup procedure.
• Accuracy = 99% of full scale value (for Drive Sleeve Turns > 50)
• Non-Linearity = ± 1% of full scale value
• Impedance = 0–600 ohms (4–20 mA signal)
• Minimum external load = 1000 ohms (0–10 VDC signal)
28
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
9 Network Communications
The UEX provides a comprehensive network option portfolio to the user. Network solutions are improved
for the user that has an L120 with UEC, with the addition of DeviceNet to complement Modbus, Foundation
Fieldbus H1, Profibus DP_V1 and Profibus PA. UEX provides the user with predictable, reliable, and safe
operation for years to come, in applications which are subject to the most rigorous requirements and
environmental extremes.
With each of the provided network protocols a user may configure the unit to move to a predefined
fail-safe position on loss of communication. Action on loss of command signal OPEN, CLOSE, STOP, or
MOVE-TO preconfigured position. The user may also configure the length of time communication must be
lost before the unit indicates communication loss and performs the communication loss action.
NOTE: For UEX packages supplied without the encoder, network control and position indication are not
available.
9.1 Modbus™
Modbus™ provides the ability to control and monitor up to 250 actuators over a single twisted-pair
cable. The communication network employs Modbus™ protocol on an RS-485 network and is redun-
dant. Redundancy assures that any single break or short in the communication cable will not disable
any actuators. Each actuator has included an addressable field unit that communicates over the twisted
pair network and executes open, close, stop, ESD, and GO TO position commands. The field unit
also communicates all actuator status and alarm diagnostic messages over the same communication
network.
Modbus Network
• Single-ended loop (as standard – See Figure 16.1)
• Modbus protocol 29
• High speed – up to 19.2K baud
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
The next-generation master station is designed specifically for use with Limitorque’s line of DDC
(Modbus) electric actuators. The Master Station III acts as a single-source controller for up to 250
actuators.
The Master Station III is a plug-and-play solution that provides complete control and diagnostics for
Limitorque field units through a simple touch-panel operator interface. The key features of the Master
Station III include:
• A network time protocol to allow for time synchronization of alarms/diagnostic data to Host device
• Multilingual support includes English, Spanish, German, French, Italian
• Asset management and diagnostic via Bluetooth V2.0+ Enhanced Data Rate (EDR) Class 100m
• Configuration of slave register polling schedule
• Industry standard Modbus RTU, ASCI, UDPor TCP/IP protocols
• Three levels of user password protection
• 5.6” TFT touch-screen display
• E-mail notification of configurable alarm conditions
• Data/event logging
• Network control of up to 250 devices
• Front access to peripheral ports: Ethernet, USB x 2, VGA, printer/debug
• Modular hot-swappable redundant design
• Built-in secure Web server for control, monitoring and asset management capabilities
30 Link Active Scheduler communication: Fieldbus segments have one active Link Active Scheduler (LAS)
at a given time, which is the bus arbiter, and does the following:
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
9.6 DeviceNet
DeviceNet complies with CAN based protocol and provides the following features:
Please see Section 16 for network connection topologies and cabling recommendations.
32
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
10
10.1 Local Features
Monitoring and
Diagnostic Features
LCD Displays – The LCD displays an array of data concerning the status of actuator components
in clear, graphical or textual language. The UEX is available with eleven languages:
English, Spanish, German, French, Italian, Portuguese, Mandarin, Russian, Bahasa
Indonesia, Turkish and Katakana.
Normal Display – The normal display illustrates current valve position and status.
Alarm Functions – Alarm functions (active alarms will be toggled every four seconds)
that may be displayed include:
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
10.2 Diagnostics
Standard Diagnostic Screens – Diagnostic screens may be accessed quickly through the Setup
dialogue or the UEX Dashboard Software solutions package. These screens provide detailed data of
actuator status. Included are:
• Hardware – status of electronic components such as thermistor, encoder, power board, DDC/FF/
PB/DeviceNet network board, analog board, DIGIN and ANIN (digital in and analog in)
• Motor – Phase rotation
• Power Supply – Maximum and minimum voltage, frequency
• Identification – Tag number, serial number, order number, software revision
• View Network Status – Checks for Standby, Recoverable Fault, Nonrecoverable Fault, and View
Network Status
• Operation Log – Actuator turns, contactor operations, motor run-time, stroke time, manual
operations
• View Control Compartment Temperature (View Power Supply Menus)
34
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
50% OPEN
STATUS OK
50% OPEN
MOTOR OVERTEMP
Typical Display
ENCODER
(FAULT) NEXT?
35
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
36
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
During configuration, the following parameters may be added to the monitor relay function:
37
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
12
Auxiliary Power Supply -
Uninterruptible Power Supply
(UPS) Connection
If the main three-phase power supply is not available during the configuration of the actuator, an optional
module contains provisions for connecting a 24 VDC, 1 A power source to the auxiliary input terminals
shown in the wiring diagram on the following pages. Power supply will draw up to 0.5 A.
38
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
13
Isolated Commons
The UEX is provided with isolated commons for control functions. Please refer to wiring diagram in
Section 15 for locations.
39
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
14
Actuator Configuration
• Direction of rotation
• Action on ESD
• External inhibits
• Remote control operating mode
• Motor thermostat action
• Stop valve on torque or position
• All optional features (Modutronic, Modbus, FF H1, PB-DPV1, PB-PA, DeviceNet, Timers, APT, etc.)
OPEN
1 Place selector switch in "STOP." The LCD (YES)
display will read "% OPEN" and "STATUS OK."
Operate the selector switch to the (YES) (NO)
0% OPEN (YES) positions. The message "SETUP?" will
STATUS OK be displayed for 10 seconds. Answer "YES" to
enter setup routine.
CLOSE
(NO)
Configuration screens are displayed in English. Languages such as Spanish, French, German, Italian,
Portuguese, Mandarin, Russian, Bahasa Indonesia, Turkish and Katakana are also available and can be
configured via the actuator control panel.
A three-digit numeric password is included as part of the initial setup procedure to prevent unauthorized
changing of the configured parameters. If the password is entered incorrectly, settings may be viewed,
but not changed. The default value for the password is 100.
41
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
42
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
PORT 43
RESTRICTED SETUP
flowserve.com
44
Allows the user to
100% OPEN SETUP? SETUP CHANGE go in and change
STATUS OK ENGLISH? SETTINGS? actuator parameter
settings
MANDARIN
SPANISH
GERMAN
RUSSIAN Allows the user to
FRENCH VIEW go in and view but
ITALIAN SETTINGS? not change
PORTUGUESE actuator parameter
settings
INDONESIAN
KATAKANA
TURKISH
EXIT
SETUP?
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
If the “POSITION INDICATION” option is disabled
during setup, then the network modes for FF, PB
Menu available only Menu available only
when “POSITION when “POSITION and DN will be OPEN/CLOSE only. If the “POSITION
Menu available only INDICATION” option is enabled during setup , then
when valve is configured INDICATION” option is INDICATION” option is
enabled during setup the network modes for FF, PB and DN can be either
for torque seating enabled during setup OPEN/CLOSE or POSITION.
Menu available only Menu available only Menu available only If the “POSITION INDICATION”
when “POSITION when “POSITION option is disabled during setup,
when “POSITION
INDICATION” option is INDICATION” option is there is no POSITON option for User
INDICATION” option is Input 0, 1 or 2 ESD Action or Partial
enabled during setup enabled during setup enabled during setup
Stroke option
CHANGE CHANGE CHANGE CHANGE LCD CHANGE CHANGE MOTOR CHANGE VALVE CHANGE RESTRICTED
MONITOR DIAGNOSTIC PASSWORD? DATA? PORT? SETUP?
RELAY? RESET? TAG? CONTRAST? THERMOSTAT?
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
45
46
SETUP?
Change Valve Setup: Allows the user to configure the actuator closing direction and
how the valve is seated
CLOSE SEATING
(TORQUE) – OK?
CHANGE VALVE CLOSE DIRECTON CLOSE SEATING OPEN SEATING CHANGE VALVE
SETUP? (CW) – OK? (POSITION) – OK? (POSITION) – OK? SETUP?
Change Position Setup: Allows the user to set the OPEN and CLOSE encoder limits based on the geared limit switch settings
Note: This menu option is available to the user only when the “POSITION INDICATION” option has
been ENABLED during the initial actuator setup.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
47
48
Change Modutronic: Allows the user to configure the actuator to be controlled with a 4-20 mA input signal
CHANGE STATUS PROP BAND FAIL POSITION DEADBAND POLARITY DELAY AFTER
20 MA = OPEN STOP 0
MODUTRONIC? (OFF) – OK? (5%) – OK? (CLOSE) – OK? +/- 2% - OK? SECONDS – OK?
4-20 MA SIGNAL SET HIGH APPLY HIGH Apply the 20 mA HIGH REFERENCE FILTER FACTOR CHANGE
REFERENCE – LEVEL signal
RANGE OK? CONTROL SIGNAL (OK)? 20 – OK? MODUTRONIC?
CHANGE STATUS PROTOCOL BAUD RATE DDC ADDRESS ANALOG SCALE ESD ACTION
DDC? (OFF) – OK? MODBUS RTU (9600) – OK? 1 – OK? (0-100) – OK? (IGNORE) – OK?
CHANGE PROP/ PROP BAND DEADBAND COMM LOSS COMM LOSS CHANGE
DEADBAND ACTION DELAY
(5%) – OK? +/- 2% - OK? (NONE) – OK? (0 SEC) – OK? DDC?
– OK?
OPEN
CLOSE
Toggling “NO” will Toggling “NO” will STOP Toggling “NO” will
change the proportional change the deadband POSITION change the delay
band value. Toggling value.Toggling value
“YES” will accept “YES” will accept the Range: 0 – 120
the changed value changed value seconds
Range: 0 – 50%
Range: 0 – 100%
Toggling “YES” will prompt the
user to select the “move to”
position. Toggling “NO” will
change the “move-to” position
value, toggling “YES” will accept
the changed value
Range: 0-100%
Note: If the “POSITION INDICATION” option is disabled during setup, then there will be no POSITION option in either the ESD Action
menu or the Comm Loss Action menu.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
49
50
Change FF: Allows the user to configure the actuator to be controlled over a Foundation Fieldbus network
CHANGE STATUS ANALOG SCALE ESD ACTION COMM LOSS COMM LOSS OPEN/CLOSE
(OFF) – OK? ACTION DELAY MODE
FF? (0-100) – OK? (IGNORE) – OK? (NONE) – OK? (0 SEC) – OK?
Change PB: Allows the user to configure the act uator to be controlled over a ProfiBus network
CHANGE STATUS PB ADDRESS ESD ACTION COMM LOSS COMM LOSS OPEN/CLOSE
(OFF) – OK? ACTION DELAY
PB? (1) – OK? (IGNORE) – OK? (NONE) – OK? (0 SEC) – OK? MODE
STOP OPEN
OPEN CLOSE
Toggling “NO” will CLOSE STOP Toggling “NO” will
change the address POSITION POSITION change the delay value
value. Toggling “YES” will
Toggling “YES” will accept the changed
STATUS accept the changed Toggling “YES” will prompt the value POSITION CHANGE PROP/ PROP BAND DEADBAND CHANGE
(ON) – OK? value user to select the “move to” Range: 0 – 120 MODE DEADBAND – OK? (5%) – OK? +/- 2% - OK? PB?
Range: 1-126 position seconds
Toggling “NO” will change the
“move-to” position value,
toggling “YES” will accept the
changed value
Range: 0-100%
CHANGE STATUS DNET BAUD DNET ADDRESS ESD ACTION COMM LOSS COMM LOSS OPEN/CLOSE
RATE (AUTO) – ACTION DELAY
DN? (OFF) – OK? NET CTRL – OK? (IGNORE) – OK? (NONE) – OK? (0 SEC) – OK? MODE
OK?
Change HART: Allows the user to configure th e actuator to be controlled by a HART controller
CHANGE STATUS MULTI-DROP POLLING SAVE CHANGE PROP/ PROP BAND DEADBAND ESD ACTION CHANGE
ADDRESS SETTINGS?
HART? (OFF) – OK? (ENABLED) – OK? (1) – OK? DEADBAND – OK? (5%) – OK? +/- 2% - OK? (IGNORE) – OK? HART?
STOP
Toggling “YES” will prompt
OPEN the user to select the
Toggling “NO” will Toggling “NO” will CLOSE “move to” position
change the proportional change the deadband POSITION Toggling “NO” will change
band value value the “move-to” position
STATUS FAIL POSITION Toggling “YES” will Toggling “YES” will value, toggling “YES” will
MULTI-DROP accept the changed
(ON) – OK? accept the changed accept the changed value
(DISABLED) – OK? (CLOSE) – OK? value value Range: 0-100%
Range: 0 – 100% Range: 0 – 50%
Note: This menu option is available to the user only when the “POSITION INDICATION” option has been ENABLED during the initial actuator setup.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
51
52
Change Status and Alarm Contacts: Allows the user to configure the status and alarm contacts
CHANGE STATUS CHANGE CHANGE STATUS STATUS FUNCTION CONTACT CHANGE STATUS
ALARM CONTACTS? CONTACTS
S1a – S2a CONTACT S1a? (CLOSE) – OK? (CLOSE) – OK? CONTACT S1a?
Change 2-Speed Timers: Allows the user to configure the OPEN and/or CLOSE 2-speed timers to increase the actuator operating ti me
CHANGE CHANGE STATUS START POSITION STOP POSITION PULSE TIME PULSE TIME CHANGE
2-SPEED TIMERS? OPEN TIMER? (OFF) – OK? (90%) – OK? (100%) – OK? (ON = 2 SEC)–OK? (OFF = 1 SEC)-OK? OPEN TIMER?
Toggling “NO” will Toggling “NO” will Toggling “NO” will Toggling “NO” will
change the start change the stop change the pulse on change the pulse off
position value position value time value time value
STATUS Toggling “YES” will Toggling “YES” will Toggling “YES” will Toggling “YES” will
(ON) – OK? accept the changed accept the changed accept the changed accept the changed
value value value value
Range: 0 – 100% Range: 0 – 100% Range: 0 – 20 seconds Range: 0 – 20 seconds
CHANGE STATUS START POSITION STOP POSITION PULSE TIME PULSE TIME CHANGE CHANGE
CLOSE TIMER? (OFF) – OK? (10%) – OK? (0%) – OK? (ON = 2 SEC)–OK? (OFF = 1 SEC)-OK? CLOSE TIMER? 2-SPEED TIMERS?
Toggling “NO” will Toggling “NO” will Toggling “NO” will Toggling “NO” will
change the start change the stop change the pulse on change the pulse off
position value position value time value time value
STATUS Toggling “YES” will
Toggling “YES” will Toggling “YES” will Toggling “YES” will
(ON) – OK? accept the changed accept the changed accept the changed
accept the changed
value value value value
Range: 0 – 100% Range: 0 – 100% Range: 0 – 20 seconds Range: 0 – 20 seconds
Note: This menu option is available to the user only when the “POSITION INDICATION” option has been ENABLED during the initial actuator setup.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Change Analog Out: Allows the user to configure the Analog Output option to provide positional feedback
CHANGE CHANGE STATUS STATUS ANALOG OUT OFFSET POLARITY SAVE CALIBRATE 20 MA CHANGE
ANALOG 1? (ON) – OK? FUNCTION 4-20 MA? 20 MA = OPEN SETTINGS? HIGH SIGNAL? OK?
ANALOG OUT? APT – OK? CURRENT – OK? ANALOG OUT?
Note: This menu option is available to the user only when the “POSITION INDICATION” option has been ENABLED during the initial actuator setup.
Change Remote: Allows the user to configure the actuator to respond to a certain type of signal
Note: This menu option is available to the user only when the “POSITION INDICATION” option has been ENABLED during the initial actuator setup.
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
53
54
Change Local Control: Allows the user to enable/disable the upfront control knobs, to configure the local operation of the act uator and to configure the red
and green LED orientation
RED/GREEN LED
MX REVERSED-OK?
RED/GREEN LED
MX STANDARD-OK?
ESD > INHIBIT ESD > LOCAL CMD ESD > STOP ESD > JAMMED ESD > LOST PHASE
ESD > OVERTORQUE ESD > THERMOSTAT ESD > 2-SPD LOCAL ESD > NW ESD ESD > TORQUE TIMER
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
CHANGE STANDARD MODE CHANGE STATUS STATUS FUNCTION SIGNAL ESD ACTION CHANGE
INPUTS? CONTROL? 3 WIRE MAINT-OK? INPUT 0? (OFF) – OK? ESD – OK? PRESENT – OK? (IGNORE)-OK? INPUT 0?
flowserve.com
55
56
Change Monitor Relay: Allows the user to configure the monitor relay
CHANGE SELECT LOCAL SELECTED LOCAL STOP/OFF OVERTORQUE INHIBIT SIGNAL ESD SIGNAL CHANGE
MONITOR RELAY? SETTINGS? ENABLED – OK? ENABLED – OK? DISABLED – OK? DISABLED – OK? DISABLED – OK? MONITOR RELAY?
CHANGE ENTER DIGIT #1 ENTER DIGIT #2 ENTER DIGIT #3 ENTER DIGIT #4 ENTER DIGIT #5 ENTER DIGIT #6 ENTER DIGIT #7 ENTER DIGIT #8
TAG? MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER
XX TAG NUMBER MX TAG NUMBER MXXTAG NUMBER MX XAG NUMBER MX TXG NUMBER MX TAX NUMBER MX TAGXNUMBER MX TAG XUMBER
ENTER DIGIT #9 ENTER DIGIT #10 ENTER DIGIT #11 ENTER DIGIT #12 ENTER DIGIT #13 ENTER DIGIT #14 ENTER DIGIT #15 ENTER DIGIT #16 RECORD TAG CHANGE
MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER OK? TAG?
MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER MX TAG NUMBER
flowserve.com
57
58
Change Password: Allows the user to change the actuator password
DISABLED
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Change Valve Data: Allows the user to enter the valve type, serial number and model number
CHANGE VALVE CHANGE VALVE ENTER DIGIT #1 ENTER DIGIT #2 ENTER DIGIT #3 ENTER DIGIT #4 ENTER DIGIT #5 ENTER DIGIT #6 ENTER DIGIT #7 ENTER DIGIT #8
DATA? S/N? V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789
ENTER DIGIT #9 ENTER DIGIT #10 ENTER DIGIT #11 ENTER DIGIT #12 ENTER DIGIT #13 ENTER DIGIT #14 ENTER DIGIT #15 ENTER DIGIT #16 RECORD VALVE
V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 V SN 123456789 S/N?
CHANGE VALVE ENTER DIGIT #1 ENTER DIGIT #2 ENTER DIGIT #3 ENTER DIGIT #4 ENTER DIGIT #5 ENTER DIGIT #6 ENTER DIGIT #7 ENTER DIGIT #8
MODEL #? V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678
X MODEL 12345678 VXMODEL 12345678 V XODEL 12345678 V MXDEL 12345678 V MOXEL 12345678 V MODXL 12345678 V MODEX 12345678 V MODELX12345678
ENTER DIGIT #9 ENTER DIGIT #10 ENTER DIGIT #11 ENTER DIGIT #12 ENTER DIGIT #13 ENTER DIGIT #14 ENTER DIGIT #15 ENTER DIGIT #16 RECORD VALVE
V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 V MODEL 12345678 MODEL #?
V MODEL X2345678 V MODEL 1X345678 V MODEL 12X45678 V MODEL 123X5678 V MODEL 1234X678 V MODEL 12345X78 V MODEL 123456X8 V MODEL 1234567X
LINEAR
ROTARY
OTHER
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
flowserve.com
59
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
DISABLED OFF
Restricted Setup: Allows the user to enable actuator options and perform certain
functions that require a factory supplied keycode
Initiates the
RESTRICTED S/N DO SOFT THIS WILL CHANGE soft re-
SETUP? V#12345678-OK? REINITIALIZE CONFIGURATION–OK? initialization
–OK? routine
15
UEX Wiring Diagrams
61
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
62
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
63
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
64
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
INT ROTORS
LIMIT SWITCHES 9-16 MUST BE WIRED DIRECTLY TO THE LIMIT
SWITCH ASSEMBLY.
CONNECTIONS
CONNECTION LANDED ON INTERFACE BOARD.
65
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Figure 15.5 – Modbus, Foundation Fieldbus, Profibus DP V1, and Profibus PA, and DeviceNet Network Wiring Diagrams
LOSS OF COMMUNICATION ON A1 => REGISTER 9 CHANNEL A CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN
(BIT 0x0400) SET TO 1 TERMINAL 3 AND CHASIS GROUND FOR SURGE PROTECTION.
PREFERRED NETWORK WIRING IS TO CONNECT SHIELD TO
LOSS OF COMMUNICATION ON A2 => REGISTER 9 CHANNEL B EARTH/GROUND AT BOTH ENDS OF THE SEGMENT. ATTACH
(BIT 0x0800) SET TO 1 SHIELD TO TERMINAL 3 ONLY IF DEVICE IS LOCATED AT THE
ENDS OF THE SEGMENT. CUSTOMER MUST CONNECT REMAINING
PREFERRED NETWORK WIRING IS TO CONNECT ONLY ONE SHIELD TO INDIVIDUAL NETWORK CABLE SHIELDS TOGETHER TO ENSURE
EARTH/GROUND. REFER TO DDC INSTALLATION DOCUMENTATION. PROPER SHIELDING OF THE ENTIRE NETWORK.
DDC-100:
JP1 AND JP2 MUST BE IN POSITION “A”. THE 6-[IN CONNECTOR WITH
BLUE WIRES SHOULD BE CONNECTED TO J2 OF THE DDC-100 BOARD. Profibus_PA
SURGE 28
FOUNDATION Fieldbus_H1
PBPA1 (–) 35
PROFIBUS
SURGE 28 PA PBPA1 (+) 36
IEC 61158–2
FF1 (–) 35 PBPA1 (–) 33
FOUNDATION
FIELDBUS FF1 (+) 36 PBPA1 (+) 34
IEC 61158–2
FF1 (–) 33
CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 3
FF1 (+) 34 AND CHASIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK
WIRING IS TO CONNECT SEGMENT SHIELD TO EARTH/GROUND AT ONE
POINT ONLY. ATTACH SHIELD TO TERMINAL 3 ONY IF SEGMENT IS NOT
CUSTOMER IS REQUIRED TO CONNECT WIRE BETWEEN TERMINAL 3 GROUNDED. ELSEWHERE, CUSTOMER MUST CONNECT INDIVIDUAL
AND CHASIS GROUND FOR SURGE PROTECTION. PREFERRED NETWORK NETWORK CABLE SHIELDS TOGETHER TO ENSURE PROPER SHIELDING
WIRING IS TO CONNECT SEGMENT SHIELD TO EARTH/GROUND AT ONE OF THE ENTIRE NETWORK.
POINT ONLY. ATTACH SHIELD TO TERMINAL 3 ONLY IF SEGMENT IS NOT
GROUNDED. ELSEWHERE, CUSTOMER MUST CONNECT INDIVIDUAL
NETWORK CABLE SHIELDS TOGETHER TO ENSURE PROPER SHIELDING
OF THE ENTIRE NETWORK. NOTES:
TERMINALS 13 &14 FOR FOUNDATION FIELDBUS, PROFIBUS PA, PROFIBUS DP_V1
FOUNDATION FIELDBUS
ARE USED FOR
TERMINALS 29CHANNEL B ONREDUNDANT
AND 41 ARE OPTIONAL REDUNDANT NETWORK
AND MAY BE BOARD.
USED FOR DAISY CHAIN
DeviceNet CONFIGURATION.
J8.5 SHIELD 28
BLU
EGND RED
DEVICENET BOARD
VIA STANDOFF
• Resistance/1000 ft = 22 AWG (7 x 30) 14.7 ohms each conductor (29.4 ohms for the pair)
• Capacitance/ft. = 11.0 pF (conductor-to-conductor)
• Capacitance/ft. = 20.0 pF (conductor-to-shield)
• Belden 3074F specifications
Total cable length between repeaters or nodes with repeaters:
• Resistance/1000 ft = 18 AWG (7x26) 6.92 ohms each conductor (13.84 ohms for the pair)
• Capacitance/ft. = 14 pF (conductor-to-conductor)
• Capacitance/ft. = 14 pF (conductor-to-shield)
• Belden 9841 specifications
67
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
MOV-2 MOV-1
A2 A2
16 A1 16 A1
41 41
A2* 15 A2* 15
Shield A1* Shield A1*
29 29
30 30
N/C N/C
•
•
•
MOV-250
A2
16 A1
41
A2* 15
Shield A1*
29
30
N/C
Legend: Notes:
Legend:
MOV - Motor Operated Valve • Correct polarity for Notes:
field unit and master station
MOV - Motor Operated Valve • Correct polarity for field unit and master station
A1 -Data Channel 1 connections is necessary for proper operation.
A1 -Data Channel 1 connections is necessary for proper operation.
A1*-Data Channel 1* • The connections shown are typical. The number of
A1*-Data Channel 1* • The connections shown are typical. The number of
A2 -Data Channel 2 MOVs will vary up to a maximum of 250.
A2 -Data Channel 2 MOVs will vary up to a maximum of 250.
A2*-Data Channel 2* • The ground connection should be a ground rod or
A2*-Data Channel 2* • The ground connection should be a ground rod or
N/C-No Connection ground grid.
68 N/C-No Connection-Shielded cable ground grid.
-Shielded cable
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Limitorque’s Foundation Fieldbus field unit conforms to open Fieldbus standard IEC 61158. It is suitable
for use on the H1 highway and uses a twisted-pair cable for connection to the highway.
The UEX FF field unit fits in the actuator in the sealed electrical housing. All adjustments to the UEX FF
settings may be made over the Foundation Fieldbus data highway using a network configuration tool.
The UEX FF unit may command its actuator to open, stop, close, move to a set position, or perform an
emergency shutdown operation. Commands to the unit come over the network from the host system,
which may be a PC, Distributed Control System (DCS), Programmable Logic Controller (PLC), or some
other microprocessor-based device. Commands may also be generated in another network actuator or
device and transmitted over fieldbus using peer-to-peer, publisher/subscriber communication.
A fieldbus device is an intelligent device within the actuator that can send multiple variables to the
control system over a high-resolution and distortion-free digital communication network. The device
provides control and self-test capabilities, which allow abnormal conditions to be easily and immediately
identified before an unplanned shutdown.
• Reduces cost of wiring and installation – existing wiring and multi-drop connections can be used.
• Interoperable devices – devices from different suppliers can communicate with one another on the
same network.
A typical UEX FF system is shown in Figure 16.2.
69
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Figure 16.2 – Typical Foundation Fieldbus System with a DCS Host (Daisy Chain Shown)
Distributed Control
System (Host)
Control Highway
Fieldbus
Interface
Fieldbus
Terminator
Power
Supply Fieldbus Network Terminator
9-32 V
UEX UEX UEX UEX
For fieldbus technology and cabling information, refer to the following documents:
• Foundation Fieldbus Wiring and Installation 31.25 kbits/s, Voltage Mode, Wire Medium AG-140
• Foundation Fieldbus Technical Overview, FD-043
• Relcom Inc. Fieldbus Wiring Design and Installation Guide
• ANSI/ISA-S50.02, Part 2-1992, Fieldbus Standard for Use in Industrial Control Systems Part 2:
Physical Layer Specification and Service Definition
• Foundation Fieldbus FF-890 and FF-891, Foundation Specification, Function Block Application
Process, Part 1 and 2.
Reference can be made to the following books:
• Fieldbuses for Process Control: Engineering, Operation, and Maintenance. ISBN 1-55617-760-7.
Network Wiring – Foundation Fieldbus
Profibus is based on RS 485 communication. The standard EN 50170 specifies the cable for use with
Profibus DP and PA. Table 16.1 shows specifications that need to be fulfilled by the Profibus cable.
In general, there are two different types of cables available. The most commonly used cable has
solid wire for the Profibus line.
When there is a need for more flexiblity (bending) and higher environmental resistance, a cable with
stranded wire for the Profibus line and special jackets shall be used.
• Capacitance/ft = 8.5 pF
• Nominal Impedance (ohms) – 150.0
Network Wiring – Profibus PA – Belden 3076F
Please refer to IEC 61158 and ANSI/ISA S.50.02 Part 2-1992 for network wiring guidelines.
Data transfer
9.6 19.2 45.45 93.75 187.5 500 1500 3000 6000 12000
rate in kbit/s
Maximum
segment 1200 1200 1200 1200 1000 400 200 100 100 100
length in m
71
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
Figure 16.3 – Typical Profibus System with a DCS Host (Daisy Chain Shown)
Distributed Control
System (Host)
Control Highway
Profibus DP
Interface
PB PB PB PB
DeviceNet is a CAN - based protocol that uses 5 wires including a shield. Two of the conductors are
used for 24V DC power & up to 8 amps (4 amps for NEC Class 2) may be passed along the hi-way from
a suitable power source. Two conductors are used for the CAN bus signals, CAN_H and CAN_L, which
are usually smaller in diameter. Limitorque recommends Belden cable for connecting to a DeviceNet
network. The specifications for thick and thin cable (per site requirements) are as follows:
72
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
73
flowserve.com
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
17
How to Order Parts
To order parts or obtain further information about your Limitorque L120 valve actuators, contact your
local Limitorque distributor sales office, or:
Flowserve Limitorque
1. Actuator Size
74
Limitorque UEX FCD LMENIM1205-04-A4 – 11/15
18
Regulatory Information
75
flowserve.com
Flowserve Corporation
United States
Flowserve Limitorque
5114 Woodall Road
P.O. Box 11318
Lynchburg, VA 24506-1318
Phone: 434-528-4400
Fax: 434-845-9736
England
Flowserve Limitorque
Euro House
Abex Road
Newbury
Berkshire, RG14 5EY
United Kingdom
Phone: 44-1-635-46999
Fax: 44-1-635-36034
Singapore
Limitorque Asia, Pte., Ltd.
12, Tuas Avenue 20
Singapore 638824
Phone: 65-6868-4628
Fax: 65-6862-4940
China
Limitorque Beijing, Pte., Ltd.
RM A1/A2
FCD LMENIM1205-04-A4 Printed in USA. November 2015
22/F, East Area, Hanwei Plaza
No. 7 Guanghua Road, Chaoyang
District
To find your local Flowserve Limitorque representative
Beijing 100004, Peoples Republic
visit www.limitorque.com or call 1 434 528 4400 of
China
Phone: 86-10-5921-0606
Fax: 86-10-6561-2702
India
Flowserve Limitorque
Plot No. #4, 1 A, Road No. 8,
EPIP
Whitefield, Bangalore – 560066
Karnataka
India
Flowserve Corporation has established industry leadership in the design and manufacture of its products. When properly selected, this Flowserve product is designed to perform Phone: 91-80-40146200
its intended function safely during its useful life. However, the purchaser or user of Flowserve products should be aware that Flowserve products might be used in numerous
applications under a wide variety of industrial service conditions. Although Flowserve can (and often does) provide general guidelines, it cannot provide specific data and warnings Fax: 91-80-28410286
for all possible applications. The purchaser/user must therefore assume the ultimate responsibility for the proper sizing and selection, installation, operation, and maintenance of
Flowserve products. The purchaser/user should read and understand the Installation Operation Maintenance (IOM) instructions included with the product, and train its employees
and contractors in the safe use of Flowserve products in connection with the specific application. Italy
While the information and specifications contained in this literature are believed to be accurate, they are supplied for informative purposes only and should not be considered
Flowserve Limitorque
certified or as a guarantee of satisfactory results by reliance thereon. Nothing contained herein is to be construed as a warranty or guarantee, express or implied, regarding any Fluid Power Systems
matter with respect to this product. Because Flowserve is continually improving and upgrading its product design, the specifications, dimensions and information contained herein
are subject to change without notice. Should any question arise concerning these provisions, the purchaser/user should contact Flowserve Corporation at any one of its worldwide Via Rio Vallone 17
operations or offices.